16
GX7R ASD Quick Start Guide
I/O and Control
The
GX7R ASD
can be controlled by several input types and combinations thereof, as well as operate
within a wide range of output frequency and voltage levels. This section discusses the ASD control
methods and supported I/O functions.
The
Terminal Board
supports discrete and analog I/O functions and is shown in
.
lists the names and the default settings of the input and output terminals of the
Terminal Board
.
See the section titled
Terminal Board Descriptions on pg. 17
for an expanded description of each
terminal.
Note:
Set the
Command Mode
to
Terminal Board
to use the input control lines of the
Terminal Board
for command input (Program
Fundamentals
Standard Mode
Selection
Command Mode
Terminal Board). Output lines of the
Terminal
Board
need not be selected to enable the output. However, output lines may be set to
a user-selected function.
shows the typical connection diagram for the GX7R ASD system.
Table 2. Terminal Board Terminal Names and Functions.
Default Term.
Setting
Input/Output
Default Function
(also see
Terminal Board Descriptions on pg. 17
)
Circuit Config.
ST
Discrete Input
Connect to CC
to activate
(Sink mode).
Sink/Source
Switching
applies to
discrete input
terminals only.
Standby
— Multifunctional programmable discrete input. Activation
required for normal ASD operation.
RES
Reset
— Multifunctional programmable discrete input. Resets a faulted
ASD.
F
Forward
— Multifunctional programmable discrete input.
R
Reverse
— Multifunctional programmable discrete input.
S1
Preset Speed 1
— Multifunctional programmable discrete input.
S2
Preset Speed 2
— Multifunctional programmable discrete input.
S3
Preset Speed 3
— Multifunctional programmable discrete input.
S4
Emergency Off
— Multifunctional programmable discrete input.
RR
Analog Input
RR
— Multifunction programmable analog input
(0.0 to 10 volt input — 0 to 80 Hz output).
RX
RX
— Multifunctional programmable analog input
(-10 to +10 VDC input — -80 to +80 Hz output).
II
II
— Multifunctional programmable analog input (4 [0] to 20 mADC
input — 0 to 80 Hz output).
VI
VI
— Multifunctional programmable analog input
(0 to 10 VDC input — 0 to 80 Hz output).
AM
Analog Output
Produces an output current that is proportional to the magnitude of the
function assigned to this terminal.
FM
OUT1 (C-A)
Switched
Output
Low Frequency
— Programmable contact (N.O.).
OUT2 (C-A)
Reach Frequency
— Programmable contact (N.O.).
FLA
Fault relay (N.O.).
FLB
Fault relay (N.C.).
FLC
Fault relay (Common).
FP
Pulsed Output
Frequency Pulse
— an output pulse train that has a frequency which is
based on the output frequency of the ASD.
P24
DC Output
24 VDC @ 50 mA output.
PP
PP
— 10.0 VDC voltage source for the external potentiometer.
CC
—
Return for analog and discrete input terminals.
DO NOT
connect to
Earth Gnd.
Summary of Contents for GX7R ASD
Page 1: ...GX7R ASD Quick Start Guide TOSHIBA GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 2: ...GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 76: ...68 GX7R ASD Quick Start Guide Figure 23 480 Volt 30 100 HP GX7R ASD ...
Page 77: ...GX7R ASD Quick Start Guide 69 Figure 24 480 Volt 125 150 HP GX7R ASD ...