GX7R ASD Quick Start Guide
17
Terminal Board Descriptions
Note:
The programmable terminal assignments may be accessed and changed from the
default settings as mapped on
or via the
Direct Access
method: Program
Direct Access
applicable parameter number
. See the section titled
Screen Menu Navigation on pg. 40
for the applicable
Direct Access
parameter
numbers. For further information on terminal assignments and default setting
changes, see the sections titled
Default Setting Changes on pg. 33
and
Note:
See the section titled
Cable/Terminal Specifications on pg. 71
for the ASD conductor
and terminal electrical specifications.
ST
— The default terminal assignment is the
Standby
mode controller. As the default setting, this
terminal must be activated for normal system operation. The
ST
terminal is activated by connecting
CC
to this terminal (Sink mode). When deactivated,
OFF
is displayed on the LCD screen. This input
terminal may be programmed to any of the functions listed in the
GX7R ASD Install and Op Manual
(see
F113
).
RES
— The default terminal assignment is
Reset
. As the default setting, this terminal resets any active
alarms or faults. The
RES
terminal is activated by connecting
CC
to this terminal (Sink mode). A
momentary connection to
CC
resets the ASD and any fault indications from the display.
Reset
is
effective when faulted only. This input terminal may be programmed to any of the functions listed in the
GX7R ASD Install and Op Manual
(see
F114
).
F
— The default terminal assignment is
Forward
run. As the default setting, this terminal provides a
forward run command. The
F
terminal is activated by connecting
CC
to this terminal (Sink mode). A
connection to
CC
provides a forward run command for the duration of the activation. This input
terminal may be programmed to any of the functions listed in the
GX7R ASD Install and Op Manual
(see
F111
).
R
— The default terminal assignment is
Reverse
run. As the default setting, this terminal provides a
reverse run command. The
R
terminal is activated by connecting
CC
to this terminal (Sink mode). A
connection to
CC
provides a forward run command for the duration of the activation. This input
terminal may be programmed to any of the functions listed in the
GX7R ASD Install and Op Manual
(see
F112
).
S1
— The default terminal assignment is
Preset Speed 1
(see the
GX7R ASD Install and Op Manual
).
As the default setting, this terminal provides a run command for the
Preset Speed 1
setting (
F118
). The
S1
terminal is activated by connecting
CC
to this terminal (Sink mode). A connection to
CC
provides a
Preset Speed 1
run command for the duration of the activation. This input terminal may be
programmed to any of the functions listed in the
GX7R ASD Install and Op Manual
(see
F115
).
S2
— The default terminal assignment is
Preset Speed 2
(see the
GX7R ASD Install and Op Manual
).
As the default setting, this terminal provides a run command for the
Preset Speed 2
setting (
F019
). The
S2
terminal is activated by connecting
CC
to this terminal (Sink mode). A connection to
CC
provides a
Preset Speed 2
run command for the duration of the activation. This input terminal may be
programmed to any of the functions listed in the
GX7R ASD Install and Op Manual
(see
F116
).
S3
— The default terminal assignment is
Preset Speed 3
(see the
GX7R ASD Install and Op Manual
).
As the default setting, this terminal provides a run command for the
Preset Speed 3
setting (
F020
). The
S3
terminal is activated by connecting
CC
to this terminal (Sink mode). A connection to
CC
provides a
Preset Speed 3
run command for the duration of the activation. This input terminal may be
programmed to any of the functions listed in the
GX7R ASD Install and Op Manual
(see
F117
).
S4
— The default terminal assignment is
Emergency Off
(see the
GX7R ASD Install and Op
Manual
). As the default setting, this terminal provides a
Stop
command (terminate ASD output and
decel at programmed rate) upon activation (
F021
). The
S4
terminal is activated by connecting
CC
to
this terminal (Sink mode). A connection to
CC
provides a
Emergency Off
command and the system
Summary of Contents for GX7R ASD
Page 1: ...GX7R ASD Quick Start Guide TOSHIBA GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 2: ...GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 76: ...68 GX7R ASD Quick Start Guide Figure 23 480 Volt 30 100 HP GX7R ASD ...
Page 77: ...GX7R ASD Quick Start Guide 69 Figure 24 480 Volt 125 150 HP GX7R ASD ...