11
C.
Mag Connect
# 10 Ga. Copper
A B E X Y
G
On LF this is a
common terminal
Note
:
For best protection of
To Ground rod
LF or GF Detector
3
rd
wire of excitation does not
connect to E unless tube
is not grounded as shown.
LF*** Converter from Lightning,
connect meter tube to earth
ground.
Toshiba Signal Cable [2A]
2-core individually shielded
conductors in rubber covered cable.
Magmeter connections
for Remote
If meter tube is grounded as shown.
(If meter tube is not grounded, please
connect “E” in Excitation cable.)
Toshiba Excitation Cable [3A]
3-core 16/3 SOOW rubber
covered Cable
LF6** or LF4** Series
Note:
4-20 Ma signal should
have shield grounded on
the receiving end only
Note: Terninal G is not
ground. It is an input to the
measuring circuit.
+
Toshiba Meters
-
Source the 4-20 signal
Converter Setup for
Remote Installation
All remote converter installations require
that Menu A be setup in the field.
Excitation Current from meter tube
MUST be set in A1 and meter Size
MUST be set in A2. Please note that
meters larger than 8" require lower
excitation frequency.
NOTE: LF 664 Large meters
require P menu set to K-Factor
B
L
K
WHT
Shield
A
B
G
X
E
Y
GREEN
B
L
K
WHT
GND
Both terminals MUST
be grounded
FG
To Ground
Drawn by D Ziegler – rev 4 April, 24 2012
Magmeter connections for
Remote Style Converters