C.

 

Mag Connect

 

 

 

 

 

 

 

# 10 Ga. Copper 

 

 

A     B     E       X     Y 

 

 

 

 

 

On LF this is a 

common terminal 

 

 

 

 

 

Note

For best protection of 

 

 

 

 

 

To Ground rod

 

 

 

 

 

LF or GF Detector 

 

3

rd 

wire of excitation does not 

connect to E unless tube 

is not grounded as shown. 

LF*** Converter from Lightning, 

connect meter tube to earth 

ground. 

 

Toshiba Signal Cable [2A] 

2-core individually shielded 

conductors in rubber covered cable. 

 

 

 

 

 

Magmeter connections 

for Remote

 

If meter tube is grounded as shown.

 

 

(If meter tube is not grounded, please 

connect “E” in Excitation cable.) 

Toshiba Excitation Cable [3A] 

3-core 16/3 SOOW rubber 

covered Cable 

 

 

LF6** or LF4** Series 

Note: 

4-20 Ma signal should 

have shield grounded on 

the receiving end only 

 

 

Note: Terninal G is not 

ground.  It is an input to the 

measuring circuit. 

Toshiba Meters 

Source the 4-20 signal 

Converter Setup for 

Remote Installation 

All remote converter installations require 

that Menu A be setup in the field. 

Excitation Current from meter tube 

MUST be set in A1 and meter Size 

MUST be set in A2.  Please note that 

meters larger than 8" require lower 

excitation frequency. 

 

NOTE: LF 664 Large meters 

require P menu set to K-Factor 

 

 

 

 

 

 

 

WHT 

Shield 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GREEN 

 

 

 

 

 

 

 

WHT 

 

 

 

 

 

 

 

 

 

GND 

 

 

 

Both terminals MUST 

be grounded 

 

 

FG 

 

 

 

 

 

 

 

To Ground 

 

Drawn by D Ziegler – rev 4 April, 24 2012

 

Magmeter connections for 

Remote Style Converters

 

Summary of Contents for GF632

Page 1: ...Magquickstart1_ver3 TOSHIBA INTERNATIONAL CORPORATION Magmeter Quick Start Guide NOTE CHECK THE OPERATION MANUAL FOR SAFETY AND STORAGE PRECAUTIONS BEFORE INSTALLATION ...

Page 2: ...ation 2 II I Procedure 3 III Additional Set up if required 6 III 1 Totalizer 6 IV Verification Check 7 IV 1 Procedure 7 i Appendix A 8 A Magmeter Operation Preparation 8 B Magmetger installation Connection 9 C Mag Connect 11 D DO Connect 12 Magquickstart1_ver3 ...

Page 3: ...h the E terminal on the converter and the detector With proper grounding of detector E terminal can be left un connected Additional information is given in the magmeter installation and Mag connect application notes See Appendix A A combine style magmeter only need to be installed and power applied II Configuration All remote style converters have to be configured in the field They are ship from t...

Page 4: ...f the box 11 1 Procedure After converter has been connected and power up hold finger over the center key for 3 seconds or longer cover don t have to be removed and enter code a series of arrows displayed on the screen if code is not entered correctly unlocking failure error will be displayed and after three 3 failed attempts unit will resort to the measurement screen After correct code is entered ...

Page 5: ...4 At the first menu A DECTECTOR press enter Select EXC CUR and press enter default 0 2000 A Set right excitation current for detector note 3 ...

Page 6: ...nter default 6 in Set correct meter size and verify excitation frequency under the EXC FREQ option note 4 Next go to menu C RANGE and press enter Select R1 and press enter default 2500 gal min Set desired range for meter note 5 ...

Page 7: ...refore there is no need to set but one can always verify Note 5 Range Type is default at SINGLE but can be change if other flow options are required Also when there is a meter size change from the default or otherwise the range value will be change to m s When changing to gal min it is necessary to change units first then set correct range value III Additional Setup if required III I Totalizer Cou...

Page 8: ...e see appendix A When COUNT is chosen as a unit for totalizer display and totalizer reaches its maximum value 99999999 it will automatically roll over and reset itself if any other unit is chosen such as gal totalizer have to be manually reset when it reaches its maximum value IV Verification Check After converter and detector connected and unit powered up and configured a verification check of th...

Page 9: ...luid go through the detector pipe When the detector is filled with the fluid stop the fluid and keep it still in the detector pipe and prepare to do a meter zero Power supply Make sure the power supply is as specified Checking converter parameters Check the configuration parameter settings refer to instruction manual Zero Adjustment Warm up flow meter for 30 minutes Make sure the fluid holds still...

Page 10: ...re in instruction manual Note Cable length may not exceed 300m The allowable cable length between the detector and the converter depends on The electrical conductivity of the object fluid see chart in spec sheet The signal cable is a double shielded cable i e both conductors are individually shielded and the overall cable is also shielded Locate it as far as possible from other large current carry...

Page 11: ...tor at site e g pit installation ground the detector by connecting the E terminal of the detector to the E terminal of the converter using a 3 core cable The E terminal of the converter is connected internally to the FG terminal and the converter case If the pipeline is not of conductive material GROUNDING RINGS MUST BE USED If converter is being installed outdoors or in an area where it might be ...

Page 12: ... 3 SOOW rubber covered Cable LF6 or LF4 Series Note 4 20 Ma signal should have shield grounded on the receiving end only Note Terninal G is not ground It is an input to the measuringcircuit Toshiba Meters Source the 4 20 signal Converter Setup for RemoteInstallation All remote converter installations require that Menu A be setup in the field Excitation Current from meter tube MUST be set in A1 and...

Page 13: ...12 D DO Connection for Magmeter Note 7 Refer to operation manual for complete DI DO connection diagram ...

Reviews: