https://www.toshiba.com/tic/
17
Installation and Connections
assigned to this terminal). This terminal may be
programmed to provide an output pulse rate that is
proportional to the magnitude of the user-selected
item from
. For further
information on this terminal see
.
AM —
The default function assigned to this output
terminal is Output Current. This output terminal
produces an output current or voltage that is
proportional to the magnitude of the Output Current
of the Q9 Plus ASD (or the function assigned to this
terminal). The available assignments for this output
terminal are listed in
. For
further information on this terminal see
FM
— This output terminal produces an output
current or voltage that is proportional to the output
frequency of the ASD or of the magnitude of the
function assigned to this terminal. The available
assignments for this output terminal are listed in
For further information on
The Voltage/
Current output selection is performed at
.
FLA
— A normally open contact that, under a user-
defined condition, connects to FLC.
FLB
— A normally closed contact that, under a
user-defined condition, opens the FLB-to-FLC
connection.
FLC
— FLC is the common leg of a single-pole
double-throw form C relay. The FL relay is the Fault
Relay by default, but may be programmed to any of
the selections of
. For further
information on this terminal see
Note:
The FLA, FLB, and FLC contacts are rated
at 2A/120 VAC and 2A/30 VDC.
for terminal descriptions.
for information on the proper cable/
terminal sizes and torque specifications when
making
Terminal Board
connections.
AM+
FM+
FLC
FLA
FLB
Figure 8. The relay is shown in the normal operating condition (default
setting). During a faulted condition the relay connection is FLC-to-FLA.
J101
TB1
TB2
TB3
J100
SW200
TB4
SW301
R
ES
C
C
F
R
S1
S2
S3
S4
C
C
ST
FP
+S
U
Ensure that the ground screw is securely in place to
prevent arcing, intermittent operation, or system failure.
1 to 2 = Sink (
*
)
2 to 3 = Source
1 to 2 = Sys. Supplied (
*
)
2 to 3 = Ext. Supplied
(24 V)
V/I Switch (
*
I)
See
for more information on the Terminal Board connections.
Half/Full Duplex(
*
) Switch
CAUTION
S4
RS485 4-Wire Communication
(*)
= Default Setting
Figure 9. Terminal Board.
Terminal Board
SW301
S4
SW200
SW301
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......