Direct Access Parameter Information
https://www.toshiba.com/tic/
243
Analog Function Assigned Object 11
Program
My Function
My Function Analog
This parameter plays a role in the setup of the My Function fea
-
ture by selecting the functionality to which the adjustment of
is applied.
Settings:
0 — Disabled (None)
1 — Acceleration Rate
2 — Upper-Limit Frequency
3 — Acceleration Multiplication Factor
4 — Deceleration Multiplication Factor
5 — Manual Torque Boost
6 — Over-Current Stall (
7 — Thermal Protection
8 — Speed Loop Proportional Gain (
)
9 — Drooping Gain (
)
10 — PID Proportional Gain (
See the My Function Instruction Manual (P/N E6581335) for a
complete description of the setup requirements and operational
information of the Analog Function Assigned Object parameter.
Direct Access Number —
F961
Parameter Type —
Selection List
Factory Default —
0 (Disabled)
Changeable During Run —
No
Analog Input Function Target 21
Program
My Function
My Function Analog
This parameter plays a role in the setup of the My Function fea
-
ture by selecting the functionality of the programmable Analog
Input Function Target 21 terminal.
may be adjusted using the input
analog control signal selected here.
Settings:
0 — None (Disabled)
1 — V/I
2 — RR
3 — RX
4 — Optional RX2+, RX2-
5 — Optional V/I
6 — Internal Memory
Direct Access Number —
F962
Parameter Type —
Selection List
Factory Default —
0 (Disabled)
Changeable During Run —
Yes
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......