200
https://www.toshiba.com/tic/
Direct Access Parameter Information
MON2 Terminal Meter Selection
Program
Terminal
Analog Output Terminals
This parameter is used to set the output function of the MON2
analog output terminal. The available assignments for this output
terminal are listed in
The MON2 analog output terminal produces an output voltage or
current that is proportional to the magnitude of the function
assigned to this terminal.
Note: The Expansion IO Card Option 2 option board (P/N
ETB004Z) is required to use this terminal.
See the Expansion IO Card Option 2
instruction manual (P/N
58686) for additional information on the function of this terminal.
MON2 Terminal Setup Parameters
— MON2 Terminal Meter Adjustment
— MON2 Voltage/Current Output Switching
— MON2 Output Gradient Characteristic
— MON2 Bias Adjustment Set Zero Level
Direct Access Number —
F674
Parameter Type —
Selection List
Factory Default —
Output Fre
-
quency
Changeable During Run —
Yes
MON2 Terminal Meter Adjustment
Program
Terminal
Analog Output Terminals
This parameter is used to set the gain of the
MON2
output termi
-
nal and is used in conjunction with the settings of parameter
for additional information on this parameter.
Direct Access Number —
F675
Parameter Type —
Numerical
Factory Default —
682
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
Pulse Output Function
Program
Terminal
Analog Output Terminals
This parameter sets the functionality of the FP output terminal to
any one of the user-selectable functions listed in
.
As the assigned function changes in magnitude or frequency, the
pulse count of the FP output terminal pulse train changes in
direct proportion to changes in the assigned function.
Note: The duty cycle of the output pulse train remains at
65 ±5.0 µS.
This parameter is used in conjunction with
Direct Access Number —
F676
Parameter Type —
Selection List
Factory Default —
Output Fre
-
quency
Changeable During Run —
Yes
Summary of Contents for DN-68249-003
Page 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Page 2: ......
Page 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Page 305: ......