E658130
- 17 -
5.5.
I/O signal list
5.5.1. One station is occupied (CC-Link Ver.1) (
c122
=0)
This option occupies one station area of the buffer memory of the PLC.
In the case of
c122
= 0, there are remote I/O (RX, RY both 32 bits) and the remote register
(RWw, RWr both 4 word) in the communication data for one station area.
Remote I/O
(Default value
= 0)
Inverter (Slave)
→
PLC (Master)
PLC (Master)
→
Inverter (Slave)
Device No.
Signal
Device No.
Signal
RXn0
Forward running
RYn0
Forward rotation command
RXn1 Reverse
running
RYn1 Reverse
rotation
command
RXn2
Output terminal 1 (RY-RC)
RYn2
Input terminal 3 (S1)
RXn3
Output terminal 2 (OUT)
RYn3
Input terminal 4 (S2)
RXn4
Output terminal 3 (FL)
RYn4
Input terminal 5 (S3)
RXn5
Failure FL
RYn5
Input terminal 6 (S4)
RXn6
PI control OFF
RYn6
Input terminal 7 (PIOFF)
RXn7
Acceleration/deceleration
pattern selection (1 or 2)
RYn7
Input terminal 8 (AD1)
RXn8
Emergency stop
RYn8
Input terminal 9 (ESTP)
RXn9
Coast stop (ST = OFF)
RYn9
Intercept output to inverter
(Coast stop)
RXnA Alarm
RYnA Frequency
priority
CC-Link
RXnB Reserved*
RYnB Command
priority
CC-Link
RXnC Monitoring
RYnC Monitor
command
RXnD
Frequency setting completion
(RAM)
RYnD
Frequency setting command
(RAM)
RXnE Reserved*
RYnE Reserved**
RXnF
Instruction code execution
completion
RYnF
Instruction code execution request
RX(n+1)0
to
RX(n+1)9
Reserved*
RY(n+1)0
to
RY(n+1)9
Reserved**
RX(n+1)A Error
status
flag
RY(n+1)A
Error reset request flag
(A reset request is during switched
ON)
RX(n+1)B
Remote station ready
RY(n+1)B
Reserved**
RX(n+1)C
to
RX(n+1)F
Reserved*
RY(n+1)C
to
RY(n+1)F
Reserved**
"n" is depend on the station number.
* The bit described "
Reserved
" is unstable. Don't use the “
Reserved
" bit for the judgment.
** Set OFF (“0”) to reserved bit.
Remote register (Default value
= 0)
RWr Inverter
→
PLC
RWw PLC
→
Inverter
Address Signal Address Signal
RWr n
Monitor value 1
RWw n
Monitor code (1 and 2)
RWr n+1
Monitor value 2
(output frequency)
RWw n+1
Set frequency
RWr n+2
Reply code
RWw n+2
Instruction code
RWr n+3
Read data
RWw n+3
Write data
"n" is depend on the station number.