OUTDOOR UNIT

OUTDOOR UNIT

Installation Location

CAUTION

Align the centers of the connecting pipes and tighten the 

fl

 are nut as far as 

possible with your 

fi

 ngers. Then tighten the nut with a two wrenches as show 

below.

     

Tightening connection

Do not apply excess torque. Otherwise, the nut may crack depending on 
the conditions.

Outer dia. of copper pipe 

Tightening torque

Ø1/4 in. (Ø6.35 mm)

10 to 13 lbf.ft (14 to 18 N·m)

Ø1/2 in. (Ø12.70 mm)

37 to 46 lbf.ft (50 to 62 N·m)

Half union

Flare nut

Externally
threaded side

Internally
threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

•  A location which provides enough spaces around the outdoor unit as 

shown in the diagram above.

•  A location which can bear the weight of the outdoor unit and does not 

allow an increase in noise level and vibration.

•  A location where the operation noise and discharged air do not disturb 

your neighbors.

•  A location which is not exposed to a strong winds.
•  A location free of combustible gases leaks.
•  A location which does not block a passage.
•  A location where drain water does not cause any problems.
•  Depending on snow level, use a 

fi

 eld fabricated ice or snow stand.

•  When the outdoor unit is to be installed in an elevated position, be sure to 

secure its feet as described in the section above.

CAUTION

1.  Install the outdoor unit in a location where there are no obstructions 

near its air intake or air outlet.

2.  When the outdoor units is installed in a place that is always exposed 

to strong winds like on the coast or on a high story of a building, use 

fi

 eld fabricated wind baf

fl

 e. To minimize the effect of strong winds, 

specially in windy areas, install the unit as shown below.

Strong
wind

90

Refrigerant Piping Connection

1.  Make sure you have enough pipe to reach to the indoor unit.
2.  Cut the pipe with a pipe cutter.

     Flaring

Obliquity

Roughness

Warp

3. Insert a 

fl

 are nut into the pipe and 

fl

 are the pipe.

•  Do not use the supplied drain nipple for draining water. Drain the water 

from all drain holes directly.

•  To protect the outdoor unit from snow accumulation, install a holding 

frame, and attach a snow protection hood and plate.

*  Do not use a double-stacked design.

Precautions about Installation in Regions

with Snowfall and Cold Temperatures

Snow protection plate

Snow protection hood

Snow accumulation line

Holding frame

At least
19-11/16 in. (500 mm)

Install the unit at least
19-11/16 in. (500 mm)
above the snow
accumulation line.

Anchor
bolts

Front

Wiring Connection

1.  MOUNT THE OUTDOOR UNIT POWER DISCONNECT.
2.  RUN POWER WIRING FROM MAIN BOX TO DISCONNECT PER NEC 

AND LOCAL CODES.

3.  Remove the valve cover and the cord clamp from the outdoor unit.
4.  Fix conduit connector to conduit plate by lock nut and secure it tightly.
 

Connect the power supply and connecting cables to the terminal block as 
shown in the 

fi

 gure below and secure it tightly with screws.

5.  You should not have extra cables.
6.  Secure the power cord and the connecting cable with the cord clamp.
7.  Attach the electric parts cover and the valve cover to the outdoor unit.
8.  RUN PIPING AND INTERCONNECTING CABLE TO THE INDOOR 

UNIT.

Electrical Work

WARNING

ELECTRICAL SHOCK HAZARD

 

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted or unbroken ground 
to minimize personal injury if an electrical fault should occur. The 
ground may consist of electrical wire or metal conduit when installed in 
accordance with existing electrical codes.

Make sure main power switch is turned OFF before performing service or 
maintenance. 

All wiring and connections must comply with NEC, CEC, and local codes.
•  Connect all wires to the correct terminal on the wiring terminal blocks.
•  Make sure that all connectors are secure.
•  Size connectors per the ratings listed in the system requirement section.
•  System interconnections should be minimum AWG14.

 

NOTE

• 

Tightening torque for connection of 

fl

 are pipe

 

The pressure of R410A is higher than 
R22. (Approx. 1.6 times.) Therefore 
securely tighten the 

fl

 are pipes 

which connect the outdoor unit and 
the indoor unit with the speci

fi

 ed 

tightening torque using a torque 
wrench.

Flare at
indoor unit side

Flare at
outdoor unit side

1110651824-1 EN.indd   7

1110651824-1 EN.indd   7

11/13/13   2:02 PM

11/13/13   2:02 PM

Summary of Contents for Carrier RAS-15

Page 1: ...FRANÇAIS Indoor unit RAS 15 17 22EK Series Outdoor unit RAS 15 17 22EA Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 1110651824 1 1110651824 1 EN indd 1 1110651824 1 EN indd 1 11 13 13 2 02 PM 11 13 13 2 02 PM ...

Page 2: ...jo Eléctrico 7 UNIDAD INTERIOR 8 Situación de Instalación 8 Corte de un Orificio y Montaje de la Placa de Montaje 8 Conexión de Cables 9 Instalación la Tubería y el Tubo de Desagüe 9 Instalación de la Unidad Interior 10 Drenaje 11 Mando a distancia A B Selección 11 EVACUACIÓN 11 Evacuación 11 OTROS 12 Comprobación de Fugas 12 Prueba de Operación 12 Ajuste de Reinicio Automático 12 Troubleshooting ...

Page 3: ... 4 6 35 Drain hose 19 11 16 0 5m Connecting pipe 15 5 16 0 39m Flare Ø1 2 12 70 For stud bold Ø2 1 4 6 8 15 32 215 5 Hanger Hanger Center line Installation plate outline Grille Inlet 2 7 8 73 5 2 7 8 73 5 Air outlet Hanger Hanger Hanger 10 5 16 262 5 10 5 16 262 5 Outline of indoor unit For stud bold Ø5 16 8 Ø13 32 10 10 9 278 7 9 200 8 7 222 7 9 200 5 9 150 20 7 525 5 2 132 1 9 16 47 6 1 32 154 4...

Page 4: ...Detail A Rear Leg R7 32 R5 5 Ø1 4 Hole Ø6 Hole Ø1 4 Hole Ø6 Hole Ø7 16x9 16 Oval Hole Ø11x14 Oval Hole Detail B Front Leg COVER PACKED VALVE View Z WIRE GUARD View Z Liquid side Flare Nut Ø1 4 Ø6 35 Gas side Flare Nut Ø1 2 Ø12 7 Service Port Air Inlet Air Outlet 3 15 16 or more 100 mm or more 23 5 8 or more 600 mm or more 2 R7 32x43 64L R5 5x17L U Shape For Ø5 16 Ø13 32 Ø8 Ø10 Anchor Bolt 2 Ø7 16x...

Page 5: ...components The power supply shall be connected to the outdoor unit by 3 wires The connecting cable between the indoor unit and outdoor unit needs to have 4 wires This cable provides the power for the indoor unit and the communication signal between the outdoor unit and indoor unit Consult local building codes NEC National Electrical Code or CEC Canadian Electrical Code for special requirements The...

Page 6: ...IS MIXED WITH THE REFRIGERANT THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS IN THE EVENT OF REFRIGERANT LEAKAGE DURING INSTALLATION ALLOW FRESH AIR INTO THE ROOM IMMEDIATELY IF THE REFRIGERANT GAS IS HEATED BY FIRE OR OTHER MEAN IT GENERATES POISONOUS GAS Installing staring up and servicing air conditioning e...

Page 7: ...t can sufficiently bear its weight If the load bearing of the unit is not enough or installation of the unit is improper the unit may fall and result in injury Electrical work must be performed by trained qualified installers and service mechanics in accordance with the code governing such installation work internal wiring regulations and the manual A dedicated circuit and the rated voltage must b...

Page 8: ...ial polyethylene foam 5 16 in 8 mm thick 1 C Putty PVC tapes One each Field Supplied Installation Parts Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong winds Use Ø5 16 in Ø8 mm or Ø3 8 in Ø10 mm anchor bolts and nuts Fixing bolt arrangement of outdoor unit 4 1 4 in 108 mm 1 1 8 in 28 mm 4 15 16 in 125 mm Ø 1 in 2 5 m m Air inlet Air outlet 3 3 8 i...

Page 9: ...oor unit from snow accumulation install a holding frame and attach a snow protection hood and plate Do not use a double stacked design Precautions about Installation in Regions with Snowfall and Cold Temperatures Snow protection plate Snow protection hood Snow accumulation line Holding frame At least 19 11 16 in 500 mm Install the unit at least 19 11 16 in 500 mm above the snow accumulation line A...

Page 10: ... 9 1 6 in 6 5 m m 1 in 23 mm 5 in 132 mm 7 in 170 mm 2 in 50 mm 1 1 2 in 40 mm Stripping length of the Power supply cord and Interconnecting cable L1 L2 L1 L2 S Interconnecting cable Power supply cord Terminal block Unit inch mm L1 L2 L1 L2 S Ground line Connecting cable Power cord Ground line 3 8 10 3 8 10 1 3 16 30 2 12 16 70 3 8 10 3 8 10 1 3 16 30 1 9 16 40 Conduit plate Connector Lock nut Val...

Page 11: ...itations Fig 2 Fig 1 Construction L1 L2 S L1 L2 S Cord clamp Terminal block Terminal cover Screw Ground line Screw Connecting cable Front panel Fig 3 Wiring CAUTION Failure to firmly install the unit may result in personal injury and property damage if the unit falls In case the unit is to be installed in a block brick concrete or similar type walls make 3 16 in 5 mm dia holes in the wall Insert c...

Page 12: ...ch a case use the provided screws to fix the unit to the mounting plate Firmly insert the drain hose and drain cap otherwise water may leak In case of right or left piping After making slits of the front panel with a knife or a making off pin cut them with a pair of nippers or an equivalent tool In case of bottom right or bottom left piping After making slits of the front panel with a knife or a m...

Page 13: ...ontrol with the tip of a pencil 00 will be shown on the display 4 Press MODE while pushing CHK B will show on the display and 00 will disappear and the air conditioner will turn OFF B is now memorized Note 1 Repeat above step to reset Remote Control back to A 2 Remote Control does not display A 3 Default setting of Remote Control from factory is A B Display 00 Display Evacuating After the piping h...

Page 14: ...indoor unit for 3 seconds to cancel the operation 3 beeps will sound but OPERATION lamp does not blink 2 Press and hold the RESET button on the indoor unit for 3 seconds to set the operation 3 beeps will sound and OPERATION lamp blink 5 time sec for 5 seconds Do not operate ON timer and OFF timer Note Default setting of auto restart operation is ON Check places with flare nut connections indoor un...

Reviews: