background image

EN

SI

11

Drainage

1.  Run the drain hose slopping downward.

 

NOTE

•  The hole should be made at a slight downward slant on the outdoor side.
•  The drain is internally trapped. An external trap is not required.

Do not rise the
drain hose.

Do not form the
drain hose into
a wavy shape.

2 in. 
(50 mm)
or more

Do not put the
drain hose end
into water.

Do not put the
drain hose end
in the drainage ditch.

2.  Put water in the drain pan and make sure that the water is drained out.
3.  When connecting an extension drain hose, insulate it with shield pipe.

Shield pipe

Drain hose

Extension drain hose

Inside the room

Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.

This air conditioner has the structure designed 
to drain water collected from dew, which forms 
on the back of the indoor unit, to the drain pan. 
Therefore, do not store the power cord and other 
parts at a height above the drain guide.

CAUTION

Wall

Drain
guide

Space for pipes

     

Remote control

•  Place the remote control away from obstacles (such as curtain) that may 

block the signal coming from the remote control.

•  Do not install the remote control in a place exposed to direct sunlight or 

close to a heating source such as a stove.

•  Keep the remote control at least 3.3 ft (1 m) apart from the nearest TV set 

or stereo equipment. (This is necessary to prevent image disturbances or 
noise interference.)

•  The location of the remote control should be determined as shown below.

5

4

°

45

°

5

7

°

Indoor unit

(Side view)

(Top view)

Indoor unit

Remote
control

Remote
control

Reception
range

Reception range

Remote Control A-B Selection

In case of two systems operating nearby, follow the instructions below to set 
the remote control to operate with one indoor unit at a time.

Remote Control B Setup.

  1. Press RESET button on the indoor unit to turn the air conditioner ON.
  2. Point the remote control at the indoor unit.
  3. Push and hold CHK 

 button on the Remote Control with the tip of a 

pencil. “00” will be shown on the display.

 4. 

Press 

MODE

 while pushing CHK 

. “B” will show on the display and 

“00” will disappear and the air conditioner will turn OFF. B is now 
memorized.

Note:

  1.  Repeat above step to reset Remote Control back to A.

 

2.  Remote Control does not display “A”.

 

3.  Default setting of Remote Control from factory is A.

“B” Display

“00” Display

Evacuating

After the piping has been connected to the indoor unit, you vacuum both 
units at once.

Be sure to use a vacuum pump with counter-

fl

 ow prevention function so 

that inside oil of the pump does not 

fl

 ow backward into pipes of the air 

conditioner when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which uses 
R410A, refrigeration cycle trouble may happen.)
1.  Connect the charge hose from the manifold valve to the service port of 

the packed valve at the gas side.

2.  Connect the charge hose to the port of the vacuum pump.
3.  Open fully the low pressure side handle of the manifold valve gauge.
4.  Operate the vacuum pump to start evacuating. Perform evacuation for 

about 15 minutes if the piping length is 66 feet (20 m). (assuming a 
pump capacity of 27 liters per minute) Then con

fi

 rm that the compound 

pressure gauge reading is –101 kPa (–76 cmHg).

     Using a vacuum pump

Evacuate the air in the connecting pipes and in the indoor unit using a 
vacuum pump. Do not re-use the refrigerant in the outdoor unit. For details, 
see the vacuum pump manual.

     VACUUMING

EVACUATING

EVACUATING

Packed valve at 
liquid side

Service port (Valve core 
(Setting pin))

Packed valve at gas side

Vacuum

pump

Vacuum pump adapter for
counter-

fl

 ow prevention

(For R410A only)

Charge hose
(For R410A only)

Handle Hi
(Keep full closed)

Manifold valve

Pressure gauge

Compound pressure gauge

Handle Lo

Charge hose 
(For R410A only)

Connecting pipe

–101 kPa

(–76 cmHg)

5.  Close the low pressure side valve handle of the manifold valve gauge.
6.  Open fully the valve stem of the packed valves (both gas and liquid 

sides).

7.  Remove the charging hose from the service port.
8.  Securely tighten the caps of packed valves.

1110651824-1 EN.indd   11

1110651824-1 EN.indd   11

11/13/13   2:02 PM

11/13/13   2:02 PM

Summary of Contents for Carrier RAS-15

Page 1: ...FRANÇAIS Indoor unit RAS 15 17 22EK Series Outdoor unit RAS 15 17 22EA Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 1110651824 1 1110651824 1 EN indd 1 1110651824 1 EN indd 1 11 13 13 2 02 PM 11 13 13 2 02 PM ...

Page 2: ...jo Eléctrico 7 UNIDAD INTERIOR 8 Situación de Instalación 8 Corte de un Orificio y Montaje de la Placa de Montaje 8 Conexión de Cables 9 Instalación la Tubería y el Tubo de Desagüe 9 Instalación de la Unidad Interior 10 Drenaje 11 Mando a distancia A B Selección 11 EVACUACIÓN 11 Evacuación 11 OTROS 12 Comprobación de Fugas 12 Prueba de Operación 12 Ajuste de Reinicio Automático 12 Troubleshooting ...

Page 3: ... 4 6 35 Drain hose 19 11 16 0 5m Connecting pipe 15 5 16 0 39m Flare Ø1 2 12 70 For stud bold Ø2 1 4 6 8 15 32 215 5 Hanger Hanger Center line Installation plate outline Grille Inlet 2 7 8 73 5 2 7 8 73 5 Air outlet Hanger Hanger Hanger 10 5 16 262 5 10 5 16 262 5 Outline of indoor unit For stud bold Ø5 16 8 Ø13 32 10 10 9 278 7 9 200 8 7 222 7 9 200 5 9 150 20 7 525 5 2 132 1 9 16 47 6 1 32 154 4...

Page 4: ...Detail A Rear Leg R7 32 R5 5 Ø1 4 Hole Ø6 Hole Ø1 4 Hole Ø6 Hole Ø7 16x9 16 Oval Hole Ø11x14 Oval Hole Detail B Front Leg COVER PACKED VALVE View Z WIRE GUARD View Z Liquid side Flare Nut Ø1 4 Ø6 35 Gas side Flare Nut Ø1 2 Ø12 7 Service Port Air Inlet Air Outlet 3 15 16 or more 100 mm or more 23 5 8 or more 600 mm or more 2 R7 32x43 64L R5 5x17L U Shape For Ø5 16 Ø13 32 Ø8 Ø10 Anchor Bolt 2 Ø7 16x...

Page 5: ...components The power supply shall be connected to the outdoor unit by 3 wires The connecting cable between the indoor unit and outdoor unit needs to have 4 wires This cable provides the power for the indoor unit and the communication signal between the outdoor unit and indoor unit Consult local building codes NEC National Electrical Code or CEC Canadian Electrical Code for special requirements The...

Page 6: ...IS MIXED WITH THE REFRIGERANT THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS IN THE EVENT OF REFRIGERANT LEAKAGE DURING INSTALLATION ALLOW FRESH AIR INTO THE ROOM IMMEDIATELY IF THE REFRIGERANT GAS IS HEATED BY FIRE OR OTHER MEAN IT GENERATES POISONOUS GAS Installing staring up and servicing air conditioning e...

Page 7: ...t can sufficiently bear its weight If the load bearing of the unit is not enough or installation of the unit is improper the unit may fall and result in injury Electrical work must be performed by trained qualified installers and service mechanics in accordance with the code governing such installation work internal wiring regulations and the manual A dedicated circuit and the rated voltage must b...

Page 8: ...ial polyethylene foam 5 16 in 8 mm thick 1 C Putty PVC tapes One each Field Supplied Installation Parts Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong winds Use Ø5 16 in Ø8 mm or Ø3 8 in Ø10 mm anchor bolts and nuts Fixing bolt arrangement of outdoor unit 4 1 4 in 108 mm 1 1 8 in 28 mm 4 15 16 in 125 mm Ø 1 in 2 5 m m Air inlet Air outlet 3 3 8 i...

Page 9: ...oor unit from snow accumulation install a holding frame and attach a snow protection hood and plate Do not use a double stacked design Precautions about Installation in Regions with Snowfall and Cold Temperatures Snow protection plate Snow protection hood Snow accumulation line Holding frame At least 19 11 16 in 500 mm Install the unit at least 19 11 16 in 500 mm above the snow accumulation line A...

Page 10: ... 9 1 6 in 6 5 m m 1 in 23 mm 5 in 132 mm 7 in 170 mm 2 in 50 mm 1 1 2 in 40 mm Stripping length of the Power supply cord and Interconnecting cable L1 L2 L1 L2 S Interconnecting cable Power supply cord Terminal block Unit inch mm L1 L2 L1 L2 S Ground line Connecting cable Power cord Ground line 3 8 10 3 8 10 1 3 16 30 2 12 16 70 3 8 10 3 8 10 1 3 16 30 1 9 16 40 Conduit plate Connector Lock nut Val...

Page 11: ...itations Fig 2 Fig 1 Construction L1 L2 S L1 L2 S Cord clamp Terminal block Terminal cover Screw Ground line Screw Connecting cable Front panel Fig 3 Wiring CAUTION Failure to firmly install the unit may result in personal injury and property damage if the unit falls In case the unit is to be installed in a block brick concrete or similar type walls make 3 16 in 5 mm dia holes in the wall Insert c...

Page 12: ...ch a case use the provided screws to fix the unit to the mounting plate Firmly insert the drain hose and drain cap otherwise water may leak In case of right or left piping After making slits of the front panel with a knife or a making off pin cut them with a pair of nippers or an equivalent tool In case of bottom right or bottom left piping After making slits of the front panel with a knife or a m...

Page 13: ...ontrol with the tip of a pencil 00 will be shown on the display 4 Press MODE while pushing CHK B will show on the display and 00 will disappear and the air conditioner will turn OFF B is now memorized Note 1 Repeat above step to reset Remote Control back to A 2 Remote Control does not display A 3 Default setting of Remote Control from factory is A B Display 00 Display Evacuating After the piping h...

Page 14: ...indoor unit for 3 seconds to cancel the operation 3 beeps will sound but OPERATION lamp does not blink 2 Press and hold the RESET button on the indoor unit for 3 seconds to set the operation 3 beeps will sound and OPERATION lamp blink 5 time sec for 5 seconds Do not operate ON timer and OFF timer Note Default setting of auto restart operation is ON Check places with flare nut connections indoor un...

Reviews: