EN

SI

5

CAUTION

•  Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water.
•  After unpacking the unit, examine it carefully for possible damage. Report any damages to your distributor.
•  Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of the unit or where noise and 

discharged air might disturb neighbors.

•  Please read this installation manual carefully before installing the unit. It contains further important instructions for proper installation.
•  This appliance must be connected to the main power supply by means of a circuit breaker depending on the place where the unit is installed. Failure to do 

so may cause electrical shock. 

•  Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit. Ensure that drained water is discharged. 

Improper drainage can result in water leakage, causing water damage to furniture.

•  Tighten the 

fl

 are nut with a torque wrench using the prescribed method. Do not apply excess torque. Otherwise, the nut may crack after a long period of 

usage and it may cause the leakage of refrigerant.

•  Wear gloves (heavy gloves such as cotton gloves) for installation work. Failure to do so may cause personal injury when handling parts with sharp edges. 
•  Do not touch the air intake section or the aluminum 

fi

 ns of the outdoor unit. It may cause injury. 

•  Do not install the outdoor unit in a place which can be a nest for small animals. Small animals could enter and contact internal electrical parts, causing a 

failure or 

fi

 re.

•  Request the user to keep the place around the unit tidy and clean.
•  Make sure to conduct a trial operation after the installation work, and explain how to use and maintain the unit to the customer in accordance with the 

manual. Ask the customer to keep the operation manual along with the installation manual.

•  The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.

WARNING

• 

ELECTRICAL SHOCK HAZARD

  Failure to follow this warning could result in personal injury or death.
  Main electrical disconnect switch must be in the OFF position before installing, modifying, or servicing the system. There may be more than 1 disconnect 

switch. Lock out and tag switch with a suitable warning label.

•  Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock switches.
•  Installation work must be performed by quali

fi

 ed personnel only.

•  Speci

fi

 ed tools and pipe parts for model R410A are required, and installation work must be done in accordance with the manual. HFC type refrigerant 

R410A has 1.6 times more pressure than that of conventional refrigerant (R22). Use the speci

fi

 ed pipe parts, and ensure correct installation, otherwise 

damage and/or injury may be caused. At the same time, water leakage, electrical shock, and 

fi

 re may occur.

•  Be sure to install the unit in a place that can suf

fi

 ciently bear its weight. If the load bearing of the unit is not enough, or installation of the unit is improper, 

the unit may fall and result in injury. 

•  Electrical work must be performed by trained, quali

fi

 ed installers and service mechanics in accordance with the code governing such installation work, 

internal wiring regulations, and the manual. A dedicated circuit and the rated voltage must be used. Insuf

fi

 cient power supply or improper installation 

may cause electrical shock or 

fi

 re.

•  Use a cabtyre cable to connect wires in the indoor/outdoor units. Midway connection is not allowed. Improper connection or 

fi

 xing may cause a 

fi

 re.

•  Wiring between the indoor unit and outdoor units must be well shaped so that the cover can be 

fi

 rmly placed. Improper cover installation may cause 

increased heat, 

fi

 re, or electrical shock at the terminal area.

•  Be sure to use only approved accessories or speci

fi

 ed parts. Failure to do so may cause the unit to fall, water leakage, 

fi

 re or electrical shock.

•  After the installation work, ensure that there is no leakage of refrigerant gas. If the refrigerant gas leaks out of the pipe into the room and is heated by 

fi

 re or something else from a fan heater, stove or gas range, it causes generation of poisonous gas.

•  Make sure the equipment is properly grounded. Do not connect the ground wire to a gas pipe, water pipe, lightning conductor, or telephone earth wire. 

Improper earth work may be the cause of electrical shock. 

•  Do not install the unit where 

fl

 ammable gas may leak. If there is any gas leakage or accumulation around the unit, it can cause a 

fi

 re.

•  Do not select a location for installation where there may be excessive water or humidity, such as a bathroom. Deterioration of insulation may cause 

electrical shock or 

fi

 re.

•  Installation work must be performed following the instructions in this installation manual. Improper installation may cause water leakage, electrical shock 

or 

fi

 re. Check the following items before operating the unit.

  -  Be sure that the pipe connection is well placed and there are no leaks.
  -  Check that the service valve is open. If the service valve is closed, it may cause overpressure and result in compressor damage. At the same time, if 

there is a leak in the connection part, it may cause air suction and overpressure, resulting in damage to the unit or injury.

•  In a pump-down operation, be sure to stop the compressor unit before removing the refrigerant pipe. If removing the refrigerant pipe while the 

compressor is operating with the service valve opened, it may cause air suction and overpressure, resulting in damage to the unit or injury.

•  Do not modify the power cable, connect the cable midway, or use a multiple outlet extension cable. Doing so may cause contact failure, insulation 

failure, or excess current, resulting in 

fi

 re or electrical shock.

•  If you detect any damage, do not install the unit. Contact your dealer immediately.
•  Do not use any refrigerant different from the one speci

fi

 ed for complement or replacement.

  Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to 

your body.

1110651824-1 EN.indd   5

1110651824-1 EN.indd   5

11/13/13   2:02 PM

11/13/13   2:02 PM

Summary of Contents for Carrier RAS-15

Page 1: ...FRANÇAIS Indoor unit RAS 15 17 22EK Series Outdoor unit RAS 15 17 22EA Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 1110651824 1 1110651824 1 EN indd 1 1110651824 1 EN indd 1 11 13 13 2 02 PM 11 13 13 2 02 PM ...

Page 2: ...jo Eléctrico 7 UNIDAD INTERIOR 8 Situación de Instalación 8 Corte de un Orificio y Montaje de la Placa de Montaje 8 Conexión de Cables 9 Instalación la Tubería y el Tubo de Desagüe 9 Instalación de la Unidad Interior 10 Drenaje 11 Mando a distancia A B Selección 11 EVACUACIÓN 11 Evacuación 11 OTROS 12 Comprobación de Fugas 12 Prueba de Operación 12 Ajuste de Reinicio Automático 12 Troubleshooting ...

Page 3: ... 4 6 35 Drain hose 19 11 16 0 5m Connecting pipe 15 5 16 0 39m Flare Ø1 2 12 70 For stud bold Ø2 1 4 6 8 15 32 215 5 Hanger Hanger Center line Installation plate outline Grille Inlet 2 7 8 73 5 2 7 8 73 5 Air outlet Hanger Hanger Hanger 10 5 16 262 5 10 5 16 262 5 Outline of indoor unit For stud bold Ø5 16 8 Ø13 32 10 10 9 278 7 9 200 8 7 222 7 9 200 5 9 150 20 7 525 5 2 132 1 9 16 47 6 1 32 154 4...

Page 4: ...Detail A Rear Leg R7 32 R5 5 Ø1 4 Hole Ø6 Hole Ø1 4 Hole Ø6 Hole Ø7 16x9 16 Oval Hole Ø11x14 Oval Hole Detail B Front Leg COVER PACKED VALVE View Z WIRE GUARD View Z Liquid side Flare Nut Ø1 4 Ø6 35 Gas side Flare Nut Ø1 2 Ø12 7 Service Port Air Inlet Air Outlet 3 15 16 or more 100 mm or more 23 5 8 or more 600 mm or more 2 R7 32x43 64L R5 5x17L U Shape For Ø5 16 Ø13 32 Ø8 Ø10 Anchor Bolt 2 Ø7 16x...

Page 5: ...components The power supply shall be connected to the outdoor unit by 3 wires The connecting cable between the indoor unit and outdoor unit needs to have 4 wires This cable provides the power for the indoor unit and the communication signal between the outdoor unit and indoor unit Consult local building codes NEC National Electrical Code or CEC Canadian Electrical Code for special requirements The...

Page 6: ...IS MIXED WITH THE REFRIGERANT THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS IN THE EVENT OF REFRIGERANT LEAKAGE DURING INSTALLATION ALLOW FRESH AIR INTO THE ROOM IMMEDIATELY IF THE REFRIGERANT GAS IS HEATED BY FIRE OR OTHER MEAN IT GENERATES POISONOUS GAS Installing staring up and servicing air conditioning e...

Page 7: ...t can sufficiently bear its weight If the load bearing of the unit is not enough or installation of the unit is improper the unit may fall and result in injury Electrical work must be performed by trained qualified installers and service mechanics in accordance with the code governing such installation work internal wiring regulations and the manual A dedicated circuit and the rated voltage must b...

Page 8: ...ial polyethylene foam 5 16 in 8 mm thick 1 C Putty PVC tapes One each Field Supplied Installation Parts Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong winds Use Ø5 16 in Ø8 mm or Ø3 8 in Ø10 mm anchor bolts and nuts Fixing bolt arrangement of outdoor unit 4 1 4 in 108 mm 1 1 8 in 28 mm 4 15 16 in 125 mm Ø 1 in 2 5 m m Air inlet Air outlet 3 3 8 i...

Page 9: ...oor unit from snow accumulation install a holding frame and attach a snow protection hood and plate Do not use a double stacked design Precautions about Installation in Regions with Snowfall and Cold Temperatures Snow protection plate Snow protection hood Snow accumulation line Holding frame At least 19 11 16 in 500 mm Install the unit at least 19 11 16 in 500 mm above the snow accumulation line A...

Page 10: ... 9 1 6 in 6 5 m m 1 in 23 mm 5 in 132 mm 7 in 170 mm 2 in 50 mm 1 1 2 in 40 mm Stripping length of the Power supply cord and Interconnecting cable L1 L2 L1 L2 S Interconnecting cable Power supply cord Terminal block Unit inch mm L1 L2 L1 L2 S Ground line Connecting cable Power cord Ground line 3 8 10 3 8 10 1 3 16 30 2 12 16 70 3 8 10 3 8 10 1 3 16 30 1 9 16 40 Conduit plate Connector Lock nut Val...

Page 11: ...itations Fig 2 Fig 1 Construction L1 L2 S L1 L2 S Cord clamp Terminal block Terminal cover Screw Ground line Screw Connecting cable Front panel Fig 3 Wiring CAUTION Failure to firmly install the unit may result in personal injury and property damage if the unit falls In case the unit is to be installed in a block brick concrete or similar type walls make 3 16 in 5 mm dia holes in the wall Insert c...

Page 12: ...ch a case use the provided screws to fix the unit to the mounting plate Firmly insert the drain hose and drain cap otherwise water may leak In case of right or left piping After making slits of the front panel with a knife or a making off pin cut them with a pair of nippers or an equivalent tool In case of bottom right or bottom left piping After making slits of the front panel with a knife or a m...

Page 13: ...ontrol with the tip of a pencil 00 will be shown on the display 4 Press MODE while pushing CHK B will show on the display and 00 will disappear and the air conditioner will turn OFF B is now memorized Note 1 Repeat above step to reset Remote Control back to A 2 Remote Control does not display A 3 Default setting of Remote Control from factory is A B Display 00 Display Evacuating After the piping h...

Page 14: ...indoor unit for 3 seconds to cancel the operation 3 beeps will sound but OPERATION lamp does not blink 2 Press and hold the RESET button on the indoor unit for 3 seconds to set the operation 3 beeps will sound and OPERATION lamp blink 5 time sec for 5 seconds Do not operate ON timer and OFF timer Note Default setting of auto restart operation is ON Check places with flare nut connections indoor un...

Reviews: