Installation of hanging bolts

• Consider the piping/wiring after the unit is hung to 

determine the location of the indoor unit installation 
and orientation.

• The hanging bolt pitches are given in the outline 

drawing and the attached installation pattern.

• When a ceiling already exists, lay the drain pipe, 

refrigerant pipe, control wires, and remote control 
wires to their connection locations before hanging 
the indoor unit.

Procure hanging bolts and nuts for installing the indoor 
unit (these are not supplied).

Using the installation pattern (accessory)

Using the pattern, positioning of the hanging bolt and 
pipe hole can be performed.
* As an error to some degree may generate on the 

pattern size due to temperature and humidity, be 

sure to confirm the size.

Installation of hanging bolt

Use 3/8” (M10) hanging bolts (4 pcs, to be local 
procure). Matching to the existing structure, set pitch 
according to size in the unit external view as shown 
below.

„

Draw-out direction of pipe/
wire

• Decide installation place of the unit and draw-out 

direction of pipe and wire.

„

Pipe knockout hole

Piping from rear side

* Cut off the groove section with a plastic cutter, etc.

Piping from right side

* Cut off the groove section with a metal saw or 

plastic cutter, etc.

Piping from left side
Taking pipe from left side is applied only to the 
drain pipe.
The refrigerant pipe cannot be taken out from the 
left side.

* Cut off the groove section with a metal saw or 

plastic cutter, etc.

Piping from upper side
Taking pipe from upper side is applied only to 
the refrigerant pipe.
When taking out the drain pipe from the upper 
side, use a drain up kit sold separately.

Open the upper pipe draw-out port (Knockout hole) 
shown in the external view.
(Knockout hole of thin plate)
After piping, cut off the attached heat insulator of the 
top plate to pipe shape, and then seal the knockout 
hole.

Hanging bolt

3/8” (M10)

4 pieces

Nut

3/8” (M10)

12 pieces

New concrete slab

Install the bolts with insert brackets or anchor bolts.

Steel flame structure

Use existing angles or install new support angles.

Existing concrete slab

Use a hole-in anchors, hole-in plugs, or a hole-in bolts.

Ceiling surface

Installation pattern

Wall face

Rubber

Anchor bolt

(Blade type 

bracket)

(Slide type 

bracket)

(Pipe hanging 

anchor bolt)

Hanging bolt

Hanging bolt Support angle

100

Rear cover

Opened when 

refrigerant pipe is 

taken out from the 

rear side

Grooves

Opened when only drain pipe is taken 

out from the rear side

Groove

Side panel (Right side)

Groove

Side panel 

(Left side)

„

Installation of indoor unit

Preparation before holding down main unit

* Confirm the presence of the ceiling material 

beforehand because the fixing method of hanging 

metal when the ceiling material is set differs from 

that when the ceiling material is not set.

There is ceiling material

* Tighten the hanging metal with upper/lower nuts 

as shown in the figure.

There is no ceiling material

• Holding down of main unit

(1) Attach washer and nuts to the hanging bolt.

(2) Hang the unit to the hanging bolt as shown the 

figure below.

(3) As shown in the figure below, fix the ceiling material 

securely with the double nuts.

REQUIREMENT

The ceiling surface may not be horizontal. Be sure 
to confirm that width and depth directions are 
level.

„

Installation of remote control 
(Sold separately)

For installation of the wired remote control, follow the 
Installation Manual attached with the remote control.
• Pull out the remote control cord together with the 

refrigerant pipe or drain pipe.
Pass the remote control cord through upper side of 
the refrigerant pipe and drain pipe.

• Do not leave the remote control at a place exposed 

to the direct sunlight and near a stove.

Ceiling surface

Double nut

(Procured locally)

Hanging bolt

(Procured locally)

Washer (Accessory)

Hanging metal

Indoor 

unit

2.

0”

 (5

0 mm)

Ceiling surface

Double nut

(Procured locally)

Hanging bolt

(Procured locally)

Washer (Accessory)

Hanging metal

Indoor 

unit

Nut

(Procured locally)

Washer

(Procured locally)

Double nut

(Procured locally)

Hanging bolt 

(Procured locally)

Washer (Accessory)

Indoor 

unit

Double nut 

(Procured locally)

Hanging bolt

Ceiling surface

Washer

(Accessory)

0.8

” - 

1.

2”

(2

- 3

0

 m

m

)

9-EN

10-EN

+00EH99876401_00Ta.book  Page 5  Monday, January 17, 2011  10:47 AM

Summary of Contents for Carrier MMC-AP0181H2UL

Page 1: ...uel d installation 17 Français AIR CONDITIONER MULTI TYPE Indoor Unit Model name Ceiling type MMC AP0181H2UL MMC AP0241H2UL MMC AP0361H2UL MMC AP0421H2UL Installation manual 00EH99876401_00Ta book Page 1 Monday January 17 2011 10 47 AM ...

Page 2: ...ly refrigerant 1 Accessory Parts Accessory parts Part name Q ty Shape Usage Installation Manual 1 This manual Installation pattern 1 Drawing out port of hanging bolt pipe Heat insulation pipe 2 For heat insulation of pipe connecting section Washer 4 3 8 M10 Ø1 0 25 mm For holding down unit Hose band 2 For connecting drain pipe Drain hose 1 For connecting drain pipe Bushing Ø2 2 Ø56 1 For protectio...

Page 3: ... cycle If air or any other gas is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons Perform installation work properly according to the Installation Manual Inappropriate installation may result in water leakage electric shock or fire When the air conditioner is installed in a small room provide ...

Page 4: ... abnormal control or problems due to noise to such appliances equipment may occur When the wireless remote control is used in a room equipped with an inverter type fluorescent light or at a place exposed to direct sunlight signals from the remote control may not be received correctly Place where organic solvent is used Place near a door or window exposed to humid outside air Dew drop may form Plac...

Page 5: ... only Do not apply force to the other parts refrigerant pipe drain pan foamed parts or resin parts Carry the package by two or more persons and do not bundle it with plastic band at positions other than specified External view Unit in mm A Unit in mm Model MMC A B C D AP018 35 8 910 33 7 855 Ø1 4 6 4 Ø1 2 12 7 AP024 46 5 1180 44 3 1125 Ø3 8 9 5 Ø5 8 15 9 AP036 AP042 62 8 1595 60 6 1540 Conduit hol...

Page 6: ...nchor bolts Steel flame structure Use existing angles or install new support angles Existing concrete slab Use a hole in anchors hole in plugs or a hole in bolts Ceiling surface Installation pattern Wall face Rubber Anchor bolt Blade type bracket Slide type bracket Pipe hanging anchor bolt Hanging bolt Hanging bolt Support angle 100 Rear cover Opened when refrigerant pipe is taken out from the rea...

Page 7: ...ction CAUTION Do not apply excessive torque Otherwise the nut may crack depending on the conditions Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Use a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak b...

Page 8: ...2 m Arched shape Trap NO GOOD VP25 As long as possible 3 9 100 mm Downward slope 1 100 or more VP30 or more VP25 VP25 Drain pipe connecting port Hard socket Attached flexible hose VP20 vinyl chloride pipe procured locally Soft socket Soft socket Adhesive agent prohibited Attached hose band Attached hose band Drain pan Plug Drain pan Drain up When not securing down slope on the drain pipe use a Dra...

Page 9: ...y be caused Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Power supply Control wiring Central control wiring 2 core with non polarity wires are used for the control wiring between indoor unit and outdoor unit and Central control wiring To prevent noise trouble use 2 core shielded wire The length of the co...

Page 10: ...the control wire and the remote control wire Do not connect the high voltage circuit Loosen the cover mounting screws 2 positions of the electrical control box and then remove the cover Attach the conduit pipe to the conduit hole with a lock nut Slit the film of bushing attached to the hole for control wire and remote control wire and then pass through wires Connect the power supply wires control ...

Page 11: ...minal numbers on the indoor units and circuit breakers terminal blocks and firmly screw the wires to the corresponding terminals 3 Secure the ground wire with the ground screw 4 Fix the wires with a cord clamp Unit in mm CAUTION Firmly tighten the screws of the terminal block Keep the wire length as shown in figure below when it is connected to the terminal block Control wires Because a hole for c...

Page 12: ... 6 1 3 2 5 4 Display content varies with the indoor unit model Procedure 3 Specify CODE No with temp setup buttons Procedure 4 Select SET DATA with timer time buttons Procedure 5 Push button When the display changes from flashing to lit the setup is completed To change settings of another indoor unit repeat from Procedure 2 To change other settings of the selected indoor unit repeat from Procedure...

Page 13: ...For address setup refer to the Installation Manual attached to the outdoor unit SET DATA Filter sign lighting time 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temp shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA 0000 0001 Remote control sensor Not used fact...

Page 14: ...ttons Cooling test run Heating test run After confirming a signal receiving sound beep immediately set the temperature to 64 F 18 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 86 F 30 C with the temp setup buttons 3 4 5 6 2 7 2 2 Always select HIGH fan speed 10Troubleshooting Confirmation and check When an error occurred in the air ...

Page 15: ...F E16 E16 00 Capacity over 01 No of connected units Capacity over No of connected indoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during automatic address I F E23 E23 Sending error in ...

Page 16: ...d remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 c 02 c 03 c c 04 c 05 c c 06 c c 07 c c c 08 c 09 c c 0A c c 0B c c c 0C c c 0D c c c 0E c c c 0F c c c c c IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp T...

Page 17: ...E 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22lbs 10kg The possible amount of leaked refrigerant gas in rooms D E and F is 33lbs 15kg NOTE 2 The standards for minimum room volume...

Page 18: ...CEILING 1 0001 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to Applicable controls in this manual Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 ...

Reviews: