background image

Ceiling type

Installation Manual

EN

Ceiling type

Installation Manual

– 12 –

„

Filter sign setting

According to the installation condition, the lighting time 
of the filter sign (Notification of filter cleaning) can be 
changed.
Follow to the basic operation procedure
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

 ).

• For the CODE No. in Procedure 

3

, specify [01].

• For the [Set data] in Procedure 

4

, select the SET 

DATA of filter sign lighting time from the following 
table.

„

To secure better effect of 
heating

When it is difficult to obtain satisfactory heating due to 
installation place of the indoor unit or structure of the 
room, the detection temperature of heating can be 
raised. Also use a circulator or other device to circulate 
heat air near the ceiling.
Follow to the basic operation procedure
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

 ).

• For the CODE No. in Procedure 

3

, specify [06].

• For the set data in Procedure 

4

, select the SET 

DATA of shift value of detection temperature to be 
set up from the table below.

„

Remote control sensor

The temperature sensor of the indoor unit senses room 
temperature usually. Set the remote control sensor to 
sense the temperature around the remote control.
Select items following the basic operation procedure 
(

1

 

 

2

 

 

3

 

 

4

 

 

5

 

 

6

 ).

• Specify [32] for the CODE No. in Procedure 

3

.

• Select the following data for the SET DATA in 

Procedure 

4

.

When 

 flashes, the remote control sensor is 

defective.
Select the SET DATA [0000] (not used) or replace the 
remote control.

„

Group control

In a group control, a remote control can control up to 
maximum 8 units.
• The wired remote control only can control a group 

control. The wireless remote control is unavailable 
for this control.

• For wiring procedure and wires of the individual line 

(Identical refrigerant line) system, refer to “Electric 
work” in this Manual.

• Wiring between indoor units in a group is performed 

in the following procedure.

• Connect the indoor units by connecting the remote 

control wires from the remote control terminal blocks 
(A, B) of the indoor unit connected with a remote 
control to the remote control terminal blocks (A, B) of 
the other indoor unit. (Non-polarity)

• For address setup, refer to the Installation Manual 

attached to the outdoor unit.

SET DATA

Filter sign lighting time

0000

None

0001

150 H

0002

2500 H (Factory default)

0003

5000 H

0004

10000 H

SET DATA

Detection temp shift value

0000

No shift

0001

+1.8 °F (+1 °C)

0002

+3.6 °F (+2 °C) 

(Factory default)

0003

+5.4 °F (+3 °C)

0004

+7.2 °F (+4 °C)

0005

+9.0 °F (+5 °C)

0006

+10.8 °F (+6 °C)

SET DATA

0000

0001

Remote control 

sensor

Not used 

(factory setting)

Used

9

Test Run

„

Before test run

• Before turning on the circuit breaker, carry out the 

following procedure.
1) By using 500V-megger, check that resistance of 

1M

Ω

 or more exists between the terminal block L

1

 

to L

2

 and the ground (grounding).

If resistance of less than 1M

Ω

 is detected, do not 

run the unit.

2) Check the valve of the outdoor unit being opened 

fully.

• To protect the compressor at activation time, leave 

power-ON for 12 hours or more be for operating.

• Before starting a test run, be sure to set addresses 

following the Installation Manual supplied with the 
outdoor unit.

„

Execute a test run

Operate the unit with the remote control as usual.
For the procedure of the operation, refer to the 
attached Owner’s Manual.
A forced test run can be executed in the following 
procedure even if the operation stops by thermo.-OFF.
In order to prevent a serial operation, the forced test 
run is released after 60 minutes have passed and 
returns to the usual operation.

CAUTION

• Do not use the forced test run for cases other than the 

test run because it applies an excessive load to the 
devices.

Wired remote control

Procedure 

1

Push

 

 

button for 4 seconds or more. [TEST] is 

displayed on the display part and the selection of mode 
in the test mode is permitted.

Procedure 

2

Push  

button.

Procedure 

3

Select the operation mode with 

 button, [COOL] 

or [HEAT].
• Do not run the air conditioner in a mode other than 

[COOL] or [HEAT].

• The temperature controlling function does not work 

during test run.

• The detection of error is performed as usual.

Procedure 

4

After the test run, push 

 button to stop a test 

run.
(Display part is same as procedure 1.)

Procedure 

5

Push 

 check button to cancel (release from) the test 

run mode.
([TEST] disappears on the display and the status 
returns to a normal.)

2, 4
3

1,5

23-EN

24-EN

+00EH99876401_00Ta.book  Page 12  Monday, January 17, 2011  10:47 AM

Summary of Contents for Carrier MMC-AP0181H2UL

Page 1: ...uel d installation 17 Français AIR CONDITIONER MULTI TYPE Indoor Unit Model name Ceiling type MMC AP0181H2UL MMC AP0241H2UL MMC AP0361H2UL MMC AP0421H2UL Installation manual 00EH99876401_00Ta book Page 1 Monday January 17 2011 10 47 AM ...

Page 2: ...ly refrigerant 1 Accessory Parts Accessory parts Part name Q ty Shape Usage Installation Manual 1 This manual Installation pattern 1 Drawing out port of hanging bolt pipe Heat insulation pipe 2 For heat insulation of pipe connecting section Washer 4 3 8 M10 Ø1 0 25 mm For holding down unit Hose band 2 For connecting drain pipe Drain hose 1 For connecting drain pipe Bushing Ø2 2 Ø56 1 For protectio...

Page 3: ... cycle If air or any other gas is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons Perform installation work properly according to the Installation Manual Inappropriate installation may result in water leakage electric shock or fire When the air conditioner is installed in a small room provide ...

Page 4: ... abnormal control or problems due to noise to such appliances equipment may occur When the wireless remote control is used in a room equipped with an inverter type fluorescent light or at a place exposed to direct sunlight signals from the remote control may not be received correctly Place where organic solvent is used Place near a door or window exposed to humid outside air Dew drop may form Plac...

Page 5: ... only Do not apply force to the other parts refrigerant pipe drain pan foamed parts or resin parts Carry the package by two or more persons and do not bundle it with plastic band at positions other than specified External view Unit in mm A Unit in mm Model MMC A B C D AP018 35 8 910 33 7 855 Ø1 4 6 4 Ø1 2 12 7 AP024 46 5 1180 44 3 1125 Ø3 8 9 5 Ø5 8 15 9 AP036 AP042 62 8 1595 60 6 1540 Conduit hol...

Page 6: ...nchor bolts Steel flame structure Use existing angles or install new support angles Existing concrete slab Use a hole in anchors hole in plugs or a hole in bolts Ceiling surface Installation pattern Wall face Rubber Anchor bolt Blade type bracket Slide type bracket Pipe hanging anchor bolt Hanging bolt Hanging bolt Support angle 100 Rear cover Opened when refrigerant pipe is taken out from the rea...

Page 7: ...ction CAUTION Do not apply excessive torque Otherwise the nut may crack depending on the conditions Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Use a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak b...

Page 8: ...2 m Arched shape Trap NO GOOD VP25 As long as possible 3 9 100 mm Downward slope 1 100 or more VP30 or more VP25 VP25 Drain pipe connecting port Hard socket Attached flexible hose VP20 vinyl chloride pipe procured locally Soft socket Soft socket Adhesive agent prohibited Attached hose band Attached hose band Drain pan Plug Drain pan Drain up When not securing down slope on the drain pipe use a Dra...

Page 9: ...y be caused Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Power supply Control wiring Central control wiring 2 core with non polarity wires are used for the control wiring between indoor unit and outdoor unit and Central control wiring To prevent noise trouble use 2 core shielded wire The length of the co...

Page 10: ...the control wire and the remote control wire Do not connect the high voltage circuit Loosen the cover mounting screws 2 positions of the electrical control box and then remove the cover Attach the conduit pipe to the conduit hole with a lock nut Slit the film of bushing attached to the hole for control wire and remote control wire and then pass through wires Connect the power supply wires control ...

Page 11: ...minal numbers on the indoor units and circuit breakers terminal blocks and firmly screw the wires to the corresponding terminals 3 Secure the ground wire with the ground screw 4 Fix the wires with a cord clamp Unit in mm CAUTION Firmly tighten the screws of the terminal block Keep the wire length as shown in figure below when it is connected to the terminal block Control wires Because a hole for c...

Page 12: ... 6 1 3 2 5 4 Display content varies with the indoor unit model Procedure 3 Specify CODE No with temp setup buttons Procedure 4 Select SET DATA with timer time buttons Procedure 5 Push button When the display changes from flashing to lit the setup is completed To change settings of another indoor unit repeat from Procedure 2 To change other settings of the selected indoor unit repeat from Procedure...

Page 13: ...For address setup refer to the Installation Manual attached to the outdoor unit SET DATA Filter sign lighting time 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temp shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA 0000 0001 Remote control sensor Not used fact...

Page 14: ...ttons Cooling test run Heating test run After confirming a signal receiving sound beep immediately set the temperature to 64 F 18 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 86 F 30 C with the temp setup buttons 3 4 5 6 2 7 2 2 Always select HIGH fan speed 10Troubleshooting Confirmation and check When an error occurred in the air ...

Page 15: ...F E16 E16 00 Capacity over 01 No of connected units Capacity over No of connected indoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during automatic address I F E23 E23 Sending error in ...

Page 16: ...d remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 c 02 c 03 c c 04 c 05 c c 06 c c 07 c c c 08 c 09 c c 0A c c 0B c c c 0C c c 0D c c c 0E c c c 0F c c c c c IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp T...

Page 17: ...E 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22lbs 10kg The possible amount of leaked refrigerant gas in rooms D E and F is 33lbs 15kg NOTE 2 The standards for minimum room volume...

Page 18: ...CEILING 1 0001 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to Applicable controls in this manual Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 ...

Reviews: