background image

3

-EN

MB Interface

Installation Manual

Configuration through micro switches

S1 - MB Interface Setting

S3 - Modbus slave address and baudrate

 * Default value

S4 - Degrees/Decidegrees (x10), temperature magnitude (ºC) and RS-485 termination resistor 

 * Only in the interfaces conected at both ends of the bus must be activated the termination resistor, not in the rest. The RS-485 bus can be biased through internal 

jumpers JP2 and JP3. Consult the user manual for details. 

WEEE Document and e-waste document for India
http://www.toshiba-carrier.co.jp/global/products/network/index.htm

Switches

 1  2  3  4 

Description

  x  x  x

Connet Wired Remote Controller and/or Wireless Remote Controller (default setting)

  x  x  x

Not Connet Wired Remote Controller and Wireless Remote Controller.

x  

  x  x

Reserve.

x  x  

  x

Reserve.

x  x  x  

Reserve.

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

Add

Switches

 1  2  3  4  5  6 

0

  

  

  

  

  

8

  

  

  

  

  

16

  

  

  

  

  

24

  

  

  

  

  

32

  

  

  

  

  

40

  

  

  

  

  

48

  

  

  

  

  

56

  

  

  

  

  

1*

  

  

  

  

  

9

  

  

  

  

  

17

  

  

  

  

  

25

  

  

  

  

  

33

  

  

  

  

  

41

  

  

  

  

  

49

  

  

  

  

  

57

  

  

  

  

  

2

  

  

  

  

  

10

  

  

  

  

  

18

  

  

  

  

  

26

  

  

  

  

  

34

  

  

  

  

  

42

  

  

  

  

  

50

  

  

  

  

  

58

  

  

  

  

  

3

  

  

  

  

  

11

  

  

  

  

  

19

  

  

  

  

  

27

  

  

  

  

  

35

  

  

  

  

  

43

  

  

  

  

  

51

  

  

  

  

  

59

  

  

  

  

  

4

  

  

  

  

  

12

  

  

  

  

  

20

  

  

  

  

  

28

  

  

  

  

  

36

  

  

  

  

  

44

  

  

  

  

  

52

  

 

  

  

  

60

  

  

  

  

  

5

  

  

  

  

  

13

  

  

  

  

  

21

  

  

  

  

  

29

  

  

  

  

  

37

  

  

  

  

  

45

  

  

  

  

  

53

  

  

  

  

  

61

  

  

  

  

  

6

  

  

  

  

  

14

  

  

  

  

  

22

  

  

  

  

  

30

  

  

  

  

  

38

  

  

  

  

  

46

  

  

  

  

  

54

  

  

  

  

  

62

  

  

  

  

  

7

  

  

  

  

  

15

  

  

  

  

  

23

  

  

  

  

  

31

  

  

  

  

  

39

  

  

  

  

  

47

  

  

  

  

  

55

  

  

  

  

  

63

  

  

  

  

  

Switches

 7  8

Description

  

 2400bps 

  

 4800bps 

  

 9600bps (default value) 

  

 19200bps 

Switches

 1  2  3  4 

Description

  x  x  x

Temperature values in Modbus register are represented in degrees (x1) (default value) 

  x  x  x

Temperature values in Modbus register are represented in decidegrees (x10) 

x  x  x  

RS-485 bus without termination resistor (default value) 

x  x  x  

Internal termination resistor of 120

 connected to RS-485 bus * 

TOSHIBA

BMS-IFMB0TLR-E

RS-485

A+

A B

B-

L1 L2 S1

S4

S3

ON 1 2 3 4 

S4

ON  1 2 3 4 5 6 7 8 

S3

 

ON 1 2 3 4 

S1

 

L1 (green)

L2 (red)

MB Interface Setting. This setting depend on Remote Controller connection.  
Please check Remote Controller connect or not.

Normal operation: At device start-up, both LEDs are on during 5 seconds. 
Afterwards only the green LED remains flashing (1900ms Off/100ms On). For 
any other indication, consult the User Manual.

Modbus slave address and Baudrate 
configuration. 

Configuration degrees/decidegrees (x10), 
temperature magnitude (ºC) and RS-  485 
termination resistor. 

Summary of Contents for BMS-IFMB0TLR-E

Page 1: ...English Installation Manual MB Interface Model name BMS IFMB0TLR E ...

Page 2: ...ructions given above Connect the interface to A B bus in any point of the bus The A B bus is the bus that connects the Air conditioning unit and the wired remote controller is a two wire bus connecting terminals A B of both this A B connection has no specific polarity Connect the RS 485 bus to the connector RS 485 of the interface Close the Air conditioning unit and reconnect it to Mains Power Fol...

Page 3: ...Add Switches 1 2 3 4 5 6 0 8 16 24 32 40 48 56 1 9 17 25 33 41 49 57 2 10 18 26 34 42 50 58 3 11 19 27 35 43 51 59 4 12 20 28 36 44 52 60 5 13 21 29 37 45 53 61 6 14 22 30 38 46 54 62 7 15 23 31 39 47 55 63 Switches 7 8 Description 2400bps 4800bps 9600bps default value 19200bps Switches 1 2 3 4 Description x x x Temperature values in Modbus register are represented in degrees x1 default value x x ...

Page 4: ... VN 2HEX1E Hot Water Module MMW AP LQ 电器电子产品有害物质声明 1 环保使用期限标识的说明 环保使用期限标识是根据 电器电子产品有害物质限制使用管理办法 以及 电子电气产品有害物质限制使用标识要求 SJ T11364 制定的 适用于中国境内销售的电器电子产品的标识 只要按照安全及使用说明内容在正常使用电器电子产品情况下 从生产日期算起 在此期限内产品中含有的有害物质不致发 生外泄或突变 不致对环境造成严重污染或对其人身 财产造成严重损害 产品正常使用后 要废弃在环保使用年限内或者刚到年限的产品 请根据国家标准采取适当的方法进行处置 另外 此期限不同于质量 功能的保证期限 The Mark and Information are applicable for People s Republic of China only 2 有害物质表示表 注 请将本申...

Reviews: