MB Interface

Installation Manual

2

-EN

Safety instructions

 WARNING

Follow carefully these safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the interface 
and/or the Air-conditioning unit. 
• This interface must be installed by accredited technical personnel (electrician, installer, or technical personnel) and following all the safety instructions. 
• Before manipulating the Air-conditioning unit, be sure it is completely disconnected from Mains power. 
• Do not modify the unit. (A fire or an electric shock may occur)
• This interface must only be installed in a restricted access location by user. 
• Do not install the unit in any of the following places. 

• Humid or wet place 
• Dusty place 
• Place exposed to direct sunlight 
• Place where there is a TV set or radio within one meter 
• Place exposed to rain (outdoors, under eaves, etc.) 

• Use predefined cable and connect them certainly. Keep the connecting terminal free from external force. 

It may cause an exothermic or a fire. 

• Strip the insulation from the cable that connects to the connector (RS-485 and A B bus) following the dimensions shown in the diagram below. 
• When connecting the cable to the connector (RS-485 and A B bus), ensure the core wires do not protrude from the connector. 
• Use two-core cabtyre cable. 

Installation instructions

• Disconnect the Air-conditioning from Mains Power. 
• Fix the interface beside the Air-conditioning (wall mounting) following the instructions in the diagram below or install it inside the Air-conditioning (respect the 

safety instructions given above). 

• Connect the interface to A B bus in any point of the bus. The A B bus is the bus that connects the Air-conditioning unit, and the wired remote controller, is a two-

wire bus connecting terminals A B of both, this A B connection has no specific polarity. 

• Connect the RS-485 bus to the connector RS-485 of the interface. 
• Close the Air-conditioning unit and reconnect it to Mains Power. 

• Follow the instructions on the user manual for configuring and commissioning the interface. 
• Follow the instructions of the next page to configure the interface through on-board DIP-switches. 

IMPORTANT: 

•  Use only one remote controller. A sub-remote controller cannot be connected when connecting this interface. 

NOTE

The cable used for connection of BMS-IFMB0TLR-E to A B bus can be any two-core cabtyre cable, the maximum distance for bus A B is 300 meters, consult the 
manual of the Air-conditioning for more details. 
Respect the maximum distance of 500 meters for the bus, no loop or star topologies are allowed for RS-485 bus, a terminator resistor of 120 

 must be present at 

each end of the bus to avoid signal reflections and also a fail-safe biasing mechanism.

NOTE

In its place there is a pair of cables to connect the Remote Controller. Use these cables to connect the AB bus. Check your Air-Conditioning user or service manual 
for more information. 

A B

TOSHIBA

BMS-IFMB0TLR-E

RS-485

A+

A

A B

B

B-

53 mm

90 mm

(20 mm)

(5 mm)

Indoor unit

Internal Block in 
the indoor unit.

Connection to A B bus.
Two-core cabtyre cable.

Max. 300 m

MODBUS RTU
RS-485 
Bus

Interface installation
• Install the 

interface on the 
DIN rail.

• For wall mount 

extract the upper 
and down 
staples until you 
hear the “click”.

Length of stripped RS-485 and A B bus communication 
cable

DIN rail

Remote Control

Summary of Contents for BMS-IFMB0TLR-E

Page 1: ...English Installation Manual MB Interface Model name BMS IFMB0TLR E ...

Page 2: ...ructions given above Connect the interface to A B bus in any point of the bus The A B bus is the bus that connects the Air conditioning unit and the wired remote controller is a two wire bus connecting terminals A B of both this A B connection has no specific polarity Connect the RS 485 bus to the connector RS 485 of the interface Close the Air conditioning unit and reconnect it to Mains Power Fol...

Page 3: ...Add Switches 1 2 3 4 5 6 0 8 16 24 32 40 48 56 1 9 17 25 33 41 49 57 2 10 18 26 34 42 50 58 3 11 19 27 35 43 51 59 4 12 20 28 36 44 52 60 5 13 21 29 37 45 53 61 6 14 22 30 38 46 54 62 7 15 23 31 39 47 55 63 Switches 7 8 Description 2400bps 4800bps 9600bps default value 19200bps Switches 1 2 3 4 Description x x x Temperature values in Modbus register are represented in degrees x1 default value x x ...

Page 4: ... VN 2HEX1E Hot Water Module MMW AP LQ 电器电子产品有害物质声明 1 环保使用期限标识的说明 环保使用期限标识是根据 电器电子产品有害物质限制使用管理办法 以及 电子电气产品有害物质限制使用标识要求 SJ T11364 制定的 适用于中国境内销售的电器电子产品的标识 只要按照安全及使用说明内容在正常使用电器电子产品情况下 从生产日期算起 在此期限内产品中含有的有害物质不致发 生外泄或突变 不致对环境造成严重污染或对其人身 财产造成严重损害 产品正常使用后 要废弃在环保使用年限内或者刚到年限的产品 请根据国家标准采取适当的方法进行处置 另外 此期限不同于质量 功能的保证期限 The Mark and Information are applicable for People s Republic of China only 2 有害物质表示表 注 请将本申...

Reviews: