11 |
P a g e
Specifications
North American Models
Electrical Specifications
Model Number
Input Voltage
Nominal
Output
Voltage
Nominal
Input
Fuses
Output
Circuit
Breakers
Maximum
Available Output
Current
Number of IP
Addressable Zones
WM 40 BAL AVR-2 ELITE
240VAC, 60Hz
(Operating Range
170V to 270V)
120VAC
± 4V
2 x 25A
2 x 20A
40A
7 + R
WM 60 BAL AVR-2 ELITE
2 x 30A
3 x 20A
60A
7 + R
WM 90 BAL AVR-2 ELITE
2 x 45A
5 x 20A
90A
7 + R
Mechanical Specifications
Model Number
Weight (Kg / lbs)
Size (HxWxD)(cm/inch)
Construction
WM 40 BAL AVR-2 ELITE
65 / 143
82.6 x 62.7 x 26.1
32.5 x 24.7 x 10.3
NEMA Type 1 Enclosure, 14 gauge steel,
black powder coated finish, door has
¼
turn latch and slip hinges for easy
removal.
WM 60 BAL AVR-2 ELITE
83 / 182.6
WM 90 BAL AVR-2 ELITE
131 / 288.2
Surge Suppression
Series Mode Surge Suppression (SMSS)
All models include non sacrificial SMSS surge suppression on the output side of the transformer.
Transient Voltage Surge Suppression (TVSS)
TVSS surge suppression option can be added to provide protection on the input side of the transformer Models
with the TVSS option use same size cabinet and add 1 Kg (2.2 lbs) of weight. Electrical specifications remain
the same for each model with or without the TVSS surge suppression option.