background image

VALVE WON'T OPEN

(a)

Control (field) wires severed. 

(Electric)

– Isolate and repair.

(b)

No power to controller. 
– Establish controller power.

(c)

No power from controller to solenoid. 
– Check for blown fuse and replace.

(d)

Manual control selector on pilot valve assembly turned to "OFF" position. 
– Turn to "AUTO" position.

(e)

Pilot valve solenoid inoperative.

– Remove and replace.

(f)

Pilot valve plunger movement restricted.

– Inspect, clean and/or replace.

(g)

No supply from main valve. 

– Debris in control tube, main valve assembly and/or communication passages in 

body. Flush thoroughly.

VALVE WON'T OPEN

(a)

Plugged controller discharge line or discharge port in pilot valve. 

(Hydraulic)

– Verify by checking for discharge at discharge line when station is

activated. If no discharge, refer to Controller Service Manual.

SPRINKLER WEEPING

(a)

Damaged or blocked valve seat. 

(Slow leak in valve)

– Remove blockage and, if necessary, replace valve assembly.

(b)

Damaged piston seal or piston assembly. 
– Replace valve assembly.

(c)

Low pressure on supply line .
– Check for low pressure reason and correct.

(d)

Elevation of normally closed sprinkler exceeds 75' (22.9 m) differential.

SEVERAL VALVES ON DIFFERENT

(a)

Control tubing leak which lowers supply pressure to other stations. 

STATIONS FAIL TO CLOSE

– Turn controller from station to station until a station is reached where

(Hydraulic)

only valves on that station stay open. The leak would be in the tubing 
on that station.  Isolate and repair.

(b)

Leak in supply line to controller. 
– Verify by checking pressure in all control lines.

(c)

Leak in controller pilot valve. 
– Verify by constant discharge from controller. 

(d)

Plugged supply line filter. 
– Replace filter if more than 3 psi (0.21 bar) differential exists.

7

Summary of Contents for 860S Series

Page 1: ...Circle or Adjustable Part Circle 30 330 Recommended Operating Pressure 50 100 PSI 3 4 6 9 bar Minimum Pressure 40 PSI 2 8 bar Maximum Pressure 150 PSI 10 3 bar Precipitation Rate Minimum 0 39 hr 9 9...

Page 2: ...71 36 1 71 80 18 4 57 24 1 65 26 7 67 32 3 71 38 9 77 40 4 77 42 5 77 47 1 77 100 20 6 60 27 0 69 29 9 71 36 3 77 43 7 81 45 4 81 47 8 83 52 9 83 Radius shown in feet Sprinkler radius of throw per ASA...

Page 3: ...ble 1 for proper application Note Wire length data provided in Table 1 is the sum of the station and common wire legs See example in Figure 2 2 Attach control wires to solenoid leads using an approved...

Page 4: ...ts do not compress air and then relieve it bleed the air continuously while filling the system 3 After water has filled all lines and all air is removed remove the quick coupler keys 4 Table 2 Hydraul...

Page 5: ...stment is completed Pilot Valve Operation Electric Models Only _______________________________________________ The main function of the pilot valve is to control the operation of the main valve locate...

Page 6: ...b Nozzle orifice damaged Replace nozzle c Low operating pressure Determine why system overloaded and correct Main Valve PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION VALVE WON T CLOSE a Continuous 24 VAC t...

Page 7: ...refer to Controller Service Manual SPRINKLER WEEPING a Damaged or blocked valve seat Slow leak in valve Remove blockage and if necessary replace valve assembly b Damaged piston seal or piston assembl...

Page 8: ...support slots engage riser assembly alignment tabs Refer to Figure 7 for the location of the alignment tabs 9 Using a 5 8 nut driver P N 995 99 unscrew main nozzle from nozzle base assembly 10 Using a...

Page 9: ...n carrier as shown Locate position of communication tube in bottom of sprinkler body and orient insertion tool accordingly Insert tool straight down into sprinkler body aligning bosses on t handle wit...

Page 10: ...ed Parts Breakout Book form number 368 0044 for service part numbers Flushing Sprinkler ______________________________________________________________ 1 With sprinkler operating carefully step down on...

Reviews: