Note:
If the S
TART
button is not pressed within 10
seconds after pressing the R
OTATE
R
IGHT
button, or
any other button is pressed in this period, the Engine
Start Enable Condition expires
Note:
Engine Start Enable Condition persists for
10 seconds after pressing the R
OTATE
R
IGHT
button
allowing momentary activation of Engine Start by
pressing the S
TART
button. Pressing the S
TART
button
does not extend this time period—the maximum length
of time that the Start Relay Control can be active is
10 seconds from pressing the R
OTATE
R
IGHT
button.
After the Engine Start Enable Condition expires, the
Engine Start Enable Sequence must be performed
again in order to energize the Start Relay Control with
the S
TART
button. This cannot be performed for 10
seconds after the S
TART
button is released.
Note:
If the sequence is aborted or the Engine Start
Enable Condition expires, normal functionality of the
R
OTATE
R
IGHT
and R
OTATE
L
EFT
buttons return to
control the Chute Motor.
Important:
Do not engage starter for more than
10 seconds at a time. If engine fails to start allow
10 second cool-down period between attempts.
Failure to follow these instructions can burn out
starter motor.
5.
After the engine starts, move the choke control to the
O
FF
position. If the engine stalls or hesitates, move
the choke back to the O
N
position for a few seconds,
then set the engine speed to the desired setting. Repeat
this as required.
Stopping the Engine
1.
Decrease the engine speed to 3/4 throttle.
2.
Press the S
TOP
button on the remote control.
3.
If leaving the machine, rotate the key to the O
FF
position and remove it from the engine (
).
Start, Stop, and Inactivity Time
out
The remote control activates (powers up) when any push
button is pressed. To conserve battery power, the remote
control stays active for approximately 3 seconds before
automatically shutting down unless there is button activity
within the 3 second limit. When the unit times out and
powers down, all remote control LED activity stops (
). Pressing any button will reactivate the remote control
Figure 17
1.
LED light
5.
Rotate right
2.
Rotate left
6.
Increase engine speed
3.
Decrease engine speed
7.
Engine stop
4.
Engine start
Power Save Mode (inactive)
The RF2CAN and TEC2403 controllers will revert to Power
Save Mode ― until a power cycle occurs ― if the base unit
is inactive for more than 2.5 hours without communication
from the remote control. Power Save Mode is a low current
state of the base unit. In Power Save Mode, the base unit will
not communicate with the remote control, will not activate
outputs, and will not generally function as normal.
•
When in the time-out mode the engine will not run (or
will quit running) and the remote control will not control
any function.
•
To wake controller in time-out mode, turn the key switch
to the O
FF
position and then turn the key switch to the
R
UN
position.
•
To avoid controller time-out during operation, use the
remote control to rotate the chute or change the engine
speed at least every 2.5 hours.
15