
46
These pages allow to configure the Lockout input and the interlock output parameters. To be active, those options
need to be assigned to an Input or an Output on the I/O board.
Lockout is an Input that disables the motor from starting.
- Enable in emergency: If checked, this option will prevent the electronic assistance on an Emergency start.
- Enable in manual mode: If checked, this option will prevent the Manual start.
- Enable in automatic mode: If checked, this option will prevent the Automatic start.
- Enable in remote manual mode: If checked, this option will prevent the Remote Manual start.
- Enable in "start/stop" mode: If checked, this option will prevent the "start/stop" mode.
- Shutdown Motor: If enabled, the lockout signal will also act as a shutdown and will stop the motor if it is running.
Interlock is an Output that prevents a second motor from starting.
- Enable in emergency: If checked, this option will activate the output "interlock" on an Emergency start.
- Enable in manual mode: If checked, this option will activate the output "interlock" on a Manual start.
- Enable in automatic: If checked, this option will activate the output "interlock" on a Automatic start.
- Enable in Remote Manual mode: If checked, this option will activate the output "interlock" on a Remote Manual
start.
- Enable in "start/stop" mode: If checked, this option will activate the output "interlock" on a "start/stop" mode.
- Main Coil required: If enabled, the controller will wait to have the Main Coil signal active before activating the
Interlock output.
Summary of Contents for GLU
Page 16: ...16 The First Start up is now completed The controller is fully installed and configured ...
Page 40: ...40 ...
Page 61: ...61 ...