www.smstork.com
17
c. Proportional Card Settings
• Control Signal Selection
Control signals are selected with the INPUT switch shown in Figure 13. Proportional electric
actuators are factory adjusted according to the 4-20mA control signal. The control signal
selection can be made according to Table 4 by changing the pins of the INPUT switch.
• Output Signal (Feedback) Selection
Output signal selection is made with the OUTPUT switch shown in Figure 14.
Proportional electric actuator is set to 4 - 20 mA output signal as factory setting. Output
signal selection with OUTPUT switch is shown in Table 5.
Table 4.
Control Signal of Proportional Electric Actuator
Figure 13.
Input control signal selection switch
INPUT CONTROL SIGNAL ADJUSTMENT SWITCH
Control
Signals
Pin Positions
1
2
3
4
0 - 10 mA
OPEN
CLOSE CLOSE CLOSE
0 - 20 mA
OPEN
CLOSE CLOSE
OPEN
2 - 10 mA
OPEN
CLOSE
OPEN
CLOSE
4 - 20 mA
OPEN
CLOSE
OPEN
OPEN
0 - 5 V DC
CLOSE
OPEN
CLOSE CLOSE
0 - 10 V DC
CLOSE
OPEN
CLOSE
OPEN
1 - 5 V DC
CLOSE
OPEN
OPEN
CLOSE
2 - 10 V DC
CLOSE
OPEN
OPEN
OPEN
Table 5. Output Signal Selection Table
Figure 14.
Output Signal (Feedback) Selection Switch
OUTPUT CONTROL SIGNAL SELECTION
SWITCHER
Control Signals
Pin Positions
1
2
3
0 - 10 mA
CLOSE CLOSE CLOSE
0 - 20 mA
CLOSE CLOSE
OPEN
2 - 10 mA
CLOSE
OPEN
CLOSE
4 - 20 mA
CLOSE
OPEN
OPEN
0 - 5 V DC
OPEN
CLOSE CLOSE
0 - 10 V DC
OPEN
CLOSE
OPEN
1 - 5 V DC
OPEN
OPEN
CLOSE
2 - 10 V DC
OPEN
OPEN
OPEN
• Error Positions
When the input control signal connected to the proportional electric actuator is interrupted
for any reason, the actuator behaves according to the pre-set action with the SETTINGS
switch. In the loss of signal, there are 3 different settings: keep the valve in its position,
open the valve and close the valve. As the factory setting, the valve is set to remain in its
Summary of Contents for TREA 0060
Page 11: ...www smstork com 11 Figure 6 Mounting the Electric Actuator to the Valve with Bracket ...
Page 22: ...SMS TORK Endüstriyel Otomasyon Ürünleri San Tic Ltd Şti 22 230VAC On Off Wiring Scheme ...
Page 23: ...www smstork com 23 24VDC On Off Wiring Scheme ...
Page 25: ...www smstork com 25 24 VDC OProportional Electric Actuator Wiring Scheme ...
Page 31: ...www smstork com 31 ...
Page 32: ...KUL TREA0080 05 01 2021 Rev 02 EN sms tork SMSTORK www smstork com ...