USER PARAMETER CONFIGURATION - PROBE READING
Push the
up
and
down
buttons simultaneously and hold down for more than 3
seconds.
The label [
Loc
] is visualised.
Utilise the
up
and
down
buttons to scroll the sensor probe readings and the user
parameters.
Press the
enter
key to confirm your selection and enter the mode for reading probes
or changing parameters.
The current value blinks on the display.
Use the keys
to select the new value, applicable to parameters only.
Press the
enter
key to exit or confirm the selection of the parameter new value; the
setting stops blinking.
DEFAULT PARAMETER RECOVERY
Information accessible to qualified staff only.
On starting the appliance, a “LAMPTEST” phase will start.
If you press the
enter
key 3 times consecutively during this phase, all default
parameters will be reset.
The display shows [
rLd
] indicating the reset of the values pre-set by the
manufacturer.
ATTENTION:
the default values in memory refer to the configurations (
tn, bts, btv, PrA
) exclusively.
ALARMS
UNIT WITH BROKEN SENSOR PROBES DURING CONSERVATION
Room probe error
If the room probe is broken or the relevant connection interrupted, the display shows the label [
E0
].
The appliance keeps operating in storing according to the values given to parameters
C5
and
C6
.
The inner fan keeps operating according to the value given to “
F3
”
Evaporator fan error (only on -22°C / +5°C units)
If the room probe is broken or the relevant connection interrupted, the display shows the label [
E1
].
The inner fan operates according to the value given to parameter “
F3
”.
If the three probes are broken or disconnected,
E0
,
E1
, and
E2
alternate on the display.
Humidity sensor Error (only on +14°C/+16°C units)
In the event that the humidity sensor is broken or its connection is interrupted
on the display the label [
E8
], is
visualised; the humidity control device is automatically deactivated.
Condenser probe error
If the condenser probe is broken or the relevant connection interrupted, the display shows the label [
E2
].
The condenser fan keeps operating according to the value given to parameter “
F8
”.
If the three probes are broken or disconnected,
E0
,
E1
, and
E2
alternate on the display.