background image

TOPAZ

 

Owner’s Manual

Condensate Pump

Due to the large amount of condensate produced by the 

TZ-60B models, condensate tanks are not furnished or 

available on these units. Condensate pumps are furnished 

as standard on the TZ-60B models, and must be piped to 

a suitable drain.

Cord Kit (LCDI) (TZ-18B, 24B, 36B)

The LCDI cord kit provides both personal shock as well 

as cord arcing and fire protection. The LCDI cord kit is 

preinstalled and must be replaced with an identical cord 

kit, available from Temp-Air, Inc., if damaged or if it fails 

to operate properly.

OPTIONAL FEATURES:

See “Accessory” section on page 12 for the correct 

accessory part numbers.

Condenser Duct:

Condenser discharge air can be removed from the con-

ditioned space with flexible duct. Use 40 feet maximum 

for all models. Allow six feet for every 90˚ bend. Do not 

exceed 0.10 in. w.c. external static pressure at the con-

denser.

Ceiling Panel Duct Kit:

A ceiling panel duct kit comes complete with flexible 

duct and a 2 foot by 2 foot ceiling tile adapter, which al-

lows condenser air to be vented to the plenum area above 

a suspended ceiling.

Discharge Nozzle Kit:

A dual-nozzle, discharge air assembly optimizes the abil-

ity to direct cool air precisely where needed. The flexible 

nozzles are attached to a mounting plate that fits over the 

evaporator air grille.

Condensate Pump:

A condensate pump automatically drains from the 

condensate pan by removing evaporator coil condensate 

water allowing continuous operation. The pump must be 

connected to the condensate drain and to the air condi-

tioner’s power supply. A hose must be run from the unit 

to a convenient drain or outdoor location.
Condensate pumps are standard on the TZ-60B models

and optional on all others. 

INSTALLATION INSTRUCTIONS:

Before Installing:

Check unit for damage. Air conditioners are inspected at 

the factory. If any damage has occurred, save the packag-

ing and file a claim with the delivering carrier within fif-

teen working days. TOPAZ units require minimal instal-

lation. The smaller units (TZ-18B though TZ-36B) can be 

plugged into the proper receptacle, and are ready to run 

immediately. The larger TZ-60B units must be wired to 

a plug or power source, and the condensate hose run to a 

suitable drain or outdoor location before starting the unit.

Electrical Supply:

Determine the proper power by checking the unit’s rat-

ing plate. For the models from the TZ-18B through the 

TZ-36B use the wall outlets and receptacles shown in the 

table above. For the TZ-60B, B3 and B4, the units must 

be wired to a suitable power supply using the appropriate 

cord and circuit protection for the electrical ratings on the 

nameplate.
Operating the units at an improper voltage, frequency, or 

improper phase orientation (see TZ-60B3 and 4 – 3 Phase 

Wiring Instructions below) voids the warranty. 

Note: 

Extension cords may be used if rated at a 

    minimum of 120VAC at 20 amps for the model    

    TZ-18B,  230VAC at 20 amps for the model  

 

    TZ-24B, and 230VAC at 30 amps for the model    

    TZ-36B. All extension cords must have a 

    functional grounding connector and fit the LCDI    

    cord supplied with the unit.
    Extension cords cannot be used on the TZ-60B    

   models.

TZ-60B3 and B4 – 3 Phase Wiring Instructions:

Only qualified personnel should install TZ-60B units.  

Extra care is required on the three phase units, the TZ-

Model

Plug Configuration Receptacle

TZ-18B
115V

15A/115V
NEMA 5-15P

NEMA 5-15P

TZ-24B
208-230V

20A/230V
NEMA 6-20P

NEMA 6-20P

TZ-36B
208-230V

30A/230V
NEMA 6-30P

NEMA 6-30P

G

X

W

Y

G

G

G

X

W

G

G

X

W

Y

G

G

G

X

W

G

G

Summary of Contents for TZ-12B

Page 1: ...TZ 60B4 21 Are you equipped to handle the heat Portable Air Conditioners 1 800 836 7432 Warning Improper installation adjust ment alteration service or maintenance can cause injury or property damage Please read instructions before install ing operating or servicing the TOPAZ unit Avertissement Le fait de modifier ou de mal installer régler réparer ou entretenir cet appareil peut entraîner des ble...

Page 2: ...60 40 20 Maximum Overcurrent Protective Device Amps 80 50 25 NEMA Plug Type 5 15P 6 20P 6 30P Wired Wired Wired Evaporator CFM Free Discharge 500 750 1 200 2 300 2 300 2 300 Condenser CFM 1 000 1 000 1 500 3 900 3 900 3 900 Maximum ESP InWC 0 10 0 10 0 10 0 50 0 50 0 50 Maximum Duct Length ft 40 40 40 40 40 40 Condensate Pump Head ft 15 15 15 15 15 15 Operating Limits min max F 65 110 65 105 65 10...

Page 3: ...d pressing the button located on the back wall of the enclosure On the TZ 60B units the reset button is located in the cord pocket enclosure which is accessible from outside the unit High Pressure Safety Switch All models feature a manual reset high pressure switch If the refrigeration circuit exceeds the controls pressure setting power to the compressor and other critical com ponents is cutoff to...

Page 4: ...e pumps are standard on the TZ 60B models and optional on all others INSTALLATION INSTRUCTIONS Before Installing Check unit for damage Air conditioners are inspected at the factory If any damage has occurred save the packag ing and file a claim with the delivering carrier within fif teen working days TOPAZ units require minimal instal lation The smaller units TZ 18B though TZ 36B can be plugged in...

Page 5: ...WER BUTTON to start the unit The evaporator cooling fan will start and the current space temperature will be shown on the digital display The unit will start in the last mode used 2 Select the Cooling mode by using the MODE button to step through the three available modes Cool Heat and Fan until the cooling mode indicator light comes on The unit is now in the cooling mode 3 Press the Up or Down te...

Page 6: ...connect the unit from its power supply when performing any form of service requiring the removal of grilles or panels Filters Dirty filters can restrict airflow causing the unit to oper ate with a reduced efficiency Inspect the filters every six weeks or more frequently when operating in a dirty en vironment Replace the filters when dirty with an equiva lent filter Do not attempt to clean the filt...

Page 7: ...nly The condenser fan on the TZ 60B series of air condition ers utilizes an adjustable sheave on the motor to drive the blower The sheave is preset at the factory and should not be adjusted However the blower motor and drives should periodically be checked for tightness and align ment Check the setscrews that connect the sheaves and blower wheel to the shafts to make sure they are secure Make sure...

Page 8: ...tactor coil defective Contactor stuck open burned or dirty Replace transformer Check and replace or reset if necessary Check and tighten if necessary Replace contactor Repair or replace contactor Evaporator fan runs but compressor and con denser fan do not Thermostat satisfied The evaporator runs anytime the thermostat is on The compressor and condenser only run if there is a demand for cooling Th...

Page 9: ...k rotation Change if necessary Loose cabinet or component part Check all panels and components to make sure they are fastened securely Check motors blower wheels drives bearings shafts etc and tighten as required Bad motor compressor or bearing Replace as necessary Water leaks from pan Condensate tank or condensate pump not installed Drain pan plugged Remove obstruction Loose evaporator drain or c...

Page 10: ...re replaced as a package The individual components are not available 1 Turn the unit OFF and disconnect the power cord from the power supply 2 Remove the grilles filters side panels and top panel from the unit 3 Disconnect the motor wiring from the rest of the circuit Tag the connections and write down where they connect to aid in wiring the replacement motor 4 The blower housing has to be removed...

Page 11: ... of the evaporator coil 3 Disconnect wires from motor Tag the wires so they can be attached to the same terminals or wires on the new motor Note that some of the wires are not used but must be capped to avoid shorting them out 4 Loosen the setscrews holding the blower wheel to the motor shaft Make sure the wheel is loose on the shaft The setscrews are accessible through the blower housing inlet op...

Page 12: ...n condenser return air plenum TZ 18B CP 24B 14 in condenser return air plenum TZ 24B CP 36B 14 in condenser return air plenum TZ 36B CP 4B 20 in condenser return air plenum TZ 60B TZ 60B3 and TZ 60B4 EP 2B 14 in evaporator return air plenum TZ 18B EP 24B 14 in evaporator return air plenum TZ 24B EP 36B 14 in evaporator return air plenum TZ 36B EP 4B 20 in evaporator return air plenum TZ 60B TZ 60B...

Page 13: ...0 119 83100 118 evaporator blower 80500 151 evaporator motor 85600 132 85600 139 condenser blower motor assembly 83100 116 83100 205 83100 118 condenser blower 80500 154 80500 137 condenser motor 85600 145 85600 217 85600 101 compressor 82200 028 82200 061 82200 060 82200 071 82200 079 82200 066 evaporator motor capacitor 85601 713 85601 724 85601 021 85601 740 85601 727 condenser motor capacitor ...

Page 14: ... 306 81400 299 3 in caster 2 per unit 81000 051 3 in swivel caster 2 per unit 81000 050 5 in caster 2 per unit 81000 045 5 in swivel caster 2 per unit 81000 046 high pressure switch 87500 424 manual thermostat 87800 102 thermostat knob 82000 081 digital thermostat 87800 888 87800 889 condensate tank 99900 717 tank well cap 06000 615 spring clip 3 8 in 81300 030 door latch snap in 84900 054 handle ...

Page 15: ...Portable Air Conditioners 15 Wiring Schematic TZ 12B ...

Page 16: ...TOPAZ Owner s Manual Wiring Schematic TZ 18B ...

Page 17: ...Portable Air Conditioners 17 Wiring Schematic TZ 24B ...

Page 18: ...TOPAZ Owner s Manual Wiring Schematic TZ 36B ...

Page 19: ...Portable Air Conditioners 19 Wiring Schematic TZ 60B ...

Page 20: ...TOPAZ Owner s Manual Wiring Schematic TZ 60B3 ...

Page 21: ...Portable Air Conditioners 21 Wiring Schematic TZ 60B4 ...

Page 22: ...TOPAZ Owner s Manual TEMP AIR 3700 West Preserve Boulevard Burnsville Minnesota 55337 7746 TZ MAN BD1 2013 TEMP AIR Inc Printed in USA 1 800 836 7432 ...

Reviews: