background image

Portable Air Conditioners

5

60B3 and TZ-60B4, to insure they are connected in phase 

with the incoming power. If the unit is not in phase the 

condenser fan and compressor operate in reverse and 

damage the compressor. If the unit is not in phase with 

the power supply, the compressor will make more noise 

than normal and the condenser fan will deliver very 

little air. The evaporator fan can not be used to check the 

phase. It has a single phase motor that operates in the cor-

rect direction regardless of the phase sequence.
If the wiring phase sequence is incorrect, reversing any 

two of the three incoming power leads will solve the 

problem. 

UNIT OPERATION:

Placing the Unit:

1.  Locate the unit on a flat, level service.
2.  Keep entering and leaving air openings free of 

  obstructions. Maintain at least 18” of clearance  

 

  between air inlet or outlet and any wall or other  

 

 obstruction.
3.  For a unit with a condensate tank, check the tank    

  to make sure it is in place and empty.
4.  For a unit with condensate pump, make sure the  

 

  condensate discharge tubing is connected to the outlet  

  connection of the unit and runs to a suitable drain    

  or outside location. Do not crimp or bend the tubing,   

  or place it where something might be set on the 

  tubing restricting its flow. No portion of the 

  discharge tube should be more than 10 feet above the  

  level of the pump.
5.  Attach any required accessories and ductwork.
6.  Plug in or wire the unit to an acceptable power source.
7.  When power is applied 06 should appear briefly on    

  the control display and disappear. The unit is now    

  ready for use.

Cooling Operation:

1.  Press the POWER BUTTON to start the unit. The    

  evaporator (cooling) fan will start and the current    

  space temperature will be shown on the digital  

 

  display. The unit will start in the last mode used. 
2.  Select the Cooling mode by using the MODE button   

  to step through the three available modes (Cool, Heat  

  and Fan) until the cooling mode indicator light comes  

  on. The unit is now in the cooling mode.
3.  Press the Up or Down temperature button to see the    

  current cooling setpoint temperature. Adjust the  

 

  setpoint temperature to the desired value by pressing   

  the Up or Down temperature button repeatedly, until   

  the desired temperature is reached. The display will    

  flash six times at the new setpoint then the actual    

  room temperature will be displayed. In the cooling    

  mode up to five minutes may lapse between turning    

  the unit on or resetting the temperature and the  

 

  compressor starting. This delay is a result of the anti   

  short cycling program in the thermostat. A green dot   

  will appear in the lower right hand corner of the  

 

  temperature display when the compressor is being    

 energized.
4.  The compressor and condenser fan will continue  

 

  to operate until the space temperature drops to the    

  setpoint temperature. At that point the compressor    

  and condenser fan will shut off, but the evaporator    

  fan will continue to run until the unit is turned off.

Fan Operation:

1.  Press the POWER BUTTON to start the unit. The    

  evaporator (cooling) fan will start and the current    

  space temperature will be shown on the digital  

 

  display. The unit will start in last mode used. 
2.  Select the Fan mode using the MODE button to step   

  through the two available modes (Cool and    

 

      Fan) until the fan mode indicator light comes on. The  

  unit is now in the Fan mode.
3.  Pressing the Up or Down temperature buttons has no  

TIMER

SLEEP

HOUR

TEMP

HOUR

TEMP

MODE

COOL

FAN

Summary of Contents for TZ-12B

Page 1: ...TZ 60B4 21 Are you equipped to handle the heat Portable Air Conditioners 1 800 836 7432 Warning Improper installation adjust ment alteration service or maintenance can cause injury or property damage Please read instructions before install ing operating or servicing the TOPAZ unit Avertissement Le fait de modifier ou de mal installer régler réparer ou entretenir cet appareil peut entraîner des ble...

Page 2: ...60 40 20 Maximum Overcurrent Protective Device Amps 80 50 25 NEMA Plug Type 5 15P 6 20P 6 30P Wired Wired Wired Evaporator CFM Free Discharge 500 750 1 200 2 300 2 300 2 300 Condenser CFM 1 000 1 000 1 500 3 900 3 900 3 900 Maximum ESP InWC 0 10 0 10 0 10 0 50 0 50 0 50 Maximum Duct Length ft 40 40 40 40 40 40 Condensate Pump Head ft 15 15 15 15 15 15 Operating Limits min max F 65 110 65 105 65 10...

Page 3: ...d pressing the button located on the back wall of the enclosure On the TZ 60B units the reset button is located in the cord pocket enclosure which is accessible from outside the unit High Pressure Safety Switch All models feature a manual reset high pressure switch If the refrigeration circuit exceeds the controls pressure setting power to the compressor and other critical com ponents is cutoff to...

Page 4: ...e pumps are standard on the TZ 60B models and optional on all others INSTALLATION INSTRUCTIONS Before Installing Check unit for damage Air conditioners are inspected at the factory If any damage has occurred save the packag ing and file a claim with the delivering carrier within fif teen working days TOPAZ units require minimal instal lation The smaller units TZ 18B though TZ 36B can be plugged in...

Page 5: ...WER BUTTON to start the unit The evaporator cooling fan will start and the current space temperature will be shown on the digital display The unit will start in the last mode used 2 Select the Cooling mode by using the MODE button to step through the three available modes Cool Heat and Fan until the cooling mode indicator light comes on The unit is now in the cooling mode 3 Press the Up or Down te...

Page 6: ...connect the unit from its power supply when performing any form of service requiring the removal of grilles or panels Filters Dirty filters can restrict airflow causing the unit to oper ate with a reduced efficiency Inspect the filters every six weeks or more frequently when operating in a dirty en vironment Replace the filters when dirty with an equiva lent filter Do not attempt to clean the filt...

Page 7: ...nly The condenser fan on the TZ 60B series of air condition ers utilizes an adjustable sheave on the motor to drive the blower The sheave is preset at the factory and should not be adjusted However the blower motor and drives should periodically be checked for tightness and align ment Check the setscrews that connect the sheaves and blower wheel to the shafts to make sure they are secure Make sure...

Page 8: ...tactor coil defective Contactor stuck open burned or dirty Replace transformer Check and replace or reset if necessary Check and tighten if necessary Replace contactor Repair or replace contactor Evaporator fan runs but compressor and con denser fan do not Thermostat satisfied The evaporator runs anytime the thermostat is on The compressor and condenser only run if there is a demand for cooling Th...

Page 9: ...k rotation Change if necessary Loose cabinet or component part Check all panels and components to make sure they are fastened securely Check motors blower wheels drives bearings shafts etc and tighten as required Bad motor compressor or bearing Replace as necessary Water leaks from pan Condensate tank or condensate pump not installed Drain pan plugged Remove obstruction Loose evaporator drain or c...

Page 10: ...re replaced as a package The individual components are not available 1 Turn the unit OFF and disconnect the power cord from the power supply 2 Remove the grilles filters side panels and top panel from the unit 3 Disconnect the motor wiring from the rest of the circuit Tag the connections and write down where they connect to aid in wiring the replacement motor 4 The blower housing has to be removed...

Page 11: ... of the evaporator coil 3 Disconnect wires from motor Tag the wires so they can be attached to the same terminals or wires on the new motor Note that some of the wires are not used but must be capped to avoid shorting them out 4 Loosen the setscrews holding the blower wheel to the motor shaft Make sure the wheel is loose on the shaft The setscrews are accessible through the blower housing inlet op...

Page 12: ...n condenser return air plenum TZ 18B CP 24B 14 in condenser return air plenum TZ 24B CP 36B 14 in condenser return air plenum TZ 36B CP 4B 20 in condenser return air plenum TZ 60B TZ 60B3 and TZ 60B4 EP 2B 14 in evaporator return air plenum TZ 18B EP 24B 14 in evaporator return air plenum TZ 24B EP 36B 14 in evaporator return air plenum TZ 36B EP 4B 20 in evaporator return air plenum TZ 60B TZ 60B...

Page 13: ...0 119 83100 118 evaporator blower 80500 151 evaporator motor 85600 132 85600 139 condenser blower motor assembly 83100 116 83100 205 83100 118 condenser blower 80500 154 80500 137 condenser motor 85600 145 85600 217 85600 101 compressor 82200 028 82200 061 82200 060 82200 071 82200 079 82200 066 evaporator motor capacitor 85601 713 85601 724 85601 021 85601 740 85601 727 condenser motor capacitor ...

Page 14: ... 306 81400 299 3 in caster 2 per unit 81000 051 3 in swivel caster 2 per unit 81000 050 5 in caster 2 per unit 81000 045 5 in swivel caster 2 per unit 81000 046 high pressure switch 87500 424 manual thermostat 87800 102 thermostat knob 82000 081 digital thermostat 87800 888 87800 889 condensate tank 99900 717 tank well cap 06000 615 spring clip 3 8 in 81300 030 door latch snap in 84900 054 handle ...

Page 15: ...Portable Air Conditioners 15 Wiring Schematic TZ 12B ...

Page 16: ...TOPAZ Owner s Manual Wiring Schematic TZ 18B ...

Page 17: ...Portable Air Conditioners 17 Wiring Schematic TZ 24B ...

Page 18: ...TOPAZ Owner s Manual Wiring Schematic TZ 36B ...

Page 19: ...Portable Air Conditioners 19 Wiring Schematic TZ 60B ...

Page 20: ...TOPAZ Owner s Manual Wiring Schematic TZ 60B3 ...

Page 21: ...Portable Air Conditioners 21 Wiring Schematic TZ 60B4 ...

Page 22: ...TOPAZ Owner s Manual TEMP AIR 3700 West Preserve Boulevard Burnsville Minnesota 55337 7746 TZ MAN BD1 2013 TEMP AIR Inc Printed in USA 1 800 836 7432 ...

Reviews: