background image

TOPAZ

®

Owner’s Manual

Inspection

1. Inspect unit on delivery.
2. Report any damage to the delivery carrier.
3. Request a written inspection report from the Claims

Inspector to substantiate claim.

4. File claims with the delivery carrier.
5. Compare unit received with description of product

ordered.

General Description

Topaz Portable Air Conditioners are designed to spot

cool industrial, commercial, institutional, and

construction sites. Six models provide 11,900 to 77,500

BTU/hr. Options include discharge nozzles to direct

conditioned air precisely where needed, and flexible duct

to transfer condenser hot air either outside or to an

adjacent area.
Topaz Portable Air Conditioners are completely self-

contained and housed within an insulated cabinet. The

unit’s exterior is constructed of galvanized steel and

protected with a tough powder-coated, polyester finish.

All models are equipped standard heavy-duty casters for

portability.

General Requirements

Topaz Portable Air Conditioners are designed for ease of

operation and rugged dependability. Follow installation

and maintenance instructions completely. Fill out and

return the warranty registration card within 30 days of

purchase to register the warranty.

Standard Features

Serviceability

Topaz Portable Air Conditioners have removable side

panels for easier servicing from all sides.
The interior of the unit is divided into four sub-

compartments. The upper right encloses the evaporator

coil and fan, and provides access to the thermostat and

fan switch. The lower right contains the condensate tank

and access to the high-pressure switch.
The condenser fan on air-cooled models can be found in

the upper left compartment. The lower left compartment

encases the condenser coil, compressor, and most

electrical components.

High-Pressure Safety Switch

All models feature a manual reset, high-pressure switch.

If refrigeration circuit pressure exceeds control limits,

power shuts off to protect the compressor and other

critical components.

Note:

Wait four minutes to restart unit after high-

pressure safety switch trips.

Freeze Protection Control

The TZ-12AB, 24AB, 36AB, 60AB and 60AB4 models

are equipped with an automatic freeze protection control.

This control turns the compressor off if moisture on the

evaporator coil freezes and blocks the coil. Normal

cooling operation resumes when the temperature of the

coil rises and the ice melts.

Short Cycle Protection Timer

The TZ-12AB, 24AB, 36AB, 60AB and 60AB4 models

are equipped with a short cycle protection timer. The

timer provides a five-minute delay before the refrigerant

compressor restarts. Under normal conditions, no

adjustments are necessary.

Summary of Contents for TZ-12AB

Page 1: ...anual is the property of the owner Leave with the unit when set up and start up are complete TEMP AIR Inc reserves the right to change design and specifications without prior notice Warning Improper installation adjustment alteration service or maintenance can cause injury or property damage Please read instructions before installing operating or servicing the TOPAZ unit Avertissement Le fait de m...

Page 2: ...rcuit Amps 15 0 15 0 20 0 30 0 60 0 20 0 NEMA Plug Type 5 15P 5 15P 6 20P 6 30P wired wired CER Rating 10 4 12 8 10 3 10 0 8 9 8 3 Evaporator CFM free discharge 350 600 750 1 200 2 300 2 300 Condenser CFM 500 1 000 1 000 1 500 3 900 3 900 Maximum ESP in wc 0 10 0 10 0 10 0 10 0 50 0 50 Maximum Duct Length ft 40 40 40 40 40 40 Condensate Pump Head ft 15 15 15 15 15 15 Operating Limits min max F 65 ...

Page 3: ...ures Serviceability Topaz Portable Air Conditioners have removable side panels for easier servicing from all sides The interior of the unit is divided into four sub compartments The upper right encloses the evaporator coil and fan and provides access to the thermostat and fan switch The lower right contains the condensate tank and access to the high pressure switch The condenser fan on air cooled ...

Page 4: ...eration Optional Features Condenser Duct Condenser discharge air can be removed from the conditioned space with flexible duct Use 40 ft maximum for all models Allow six feet for every 90 bend Do not exceed 0 10 in wc external static pressure at the condenser Ceiling Panel Duct Kit A ceiling panel duct kit comes complete with flexible duct and a 2 ft by 2 ft ceiling tile adapter which allows conden...

Page 5: ...FAN AUTO switch for cycling the fan operating on and off with the cooling circuit Cooling Cycle 1 Set the desired temperature by adjusting the WARMER COOLER dial from 68º 115º Note Wait 4 minutes between turning cooling mode off and on Preventative Maintenance TOPAZ provides maximum performance and reliability with minimum maintenance The refrigeration and electrical circuits of the system should ...

Page 6: ... equipped with adjustable sheaves on the evaporator and condenser fans Conditioned air and condenser air are controlled using double inlet forward curved fans driven by belt and sheave combinations Adjust belt tension for 3 16 in deflection with 2 lbs force Sheave Adjustment The evaporator fan and condenser fan sheaves are factory pre set and should not be adjusted Periodically check that sheaves ...

Page 7: ...ive condenser fan motor Replace if necessary Restricted duct Short cycle timer not timed out TZ 12A 18AB Wait 5 min for timer to allow compressor to restart 24AB 36AB and 60AB only Compressor contactor open or burned Replace Refrigerant leak no freon Locate leak and repair Evacuate unit and recharge Loose or defective wires Check for loose or shorted conductors Secure contact between wires and con...

Page 8: ... Level unit base Blower motor bearing defective Replace blower motor Water leaks from pan Leaky drain pan Replace pan Drain plugged Check and clear obstruction Loose evaporator drain or condensate Tighten connections pump hose Defective condensate pump or excessive If elevation exceeds 20 ft a larger pump is lift on pump required Pump does not operate properly if combination of lift height and len...

Page 9: ...le in side of unit to a convenient drain or outdoor location Fan Motors TZ 12AB through TZ 36AB 1 Remove cabinet s side panels 2 Disconnect evaporator motor wires at the connector plug 3 Disconnect condenser motor wires at the connector plug 4 Remove unit s top and disconnect thermostat at connector plug 5 Remove screws securing blower mounts All screws are external and visible 6 Remove motors and...

Page 10: ...Z 12AB CP 2 14 in condenser return air plenum TZ 18AB and TZ 24AB CP 3 14 in condenser return air plenum TZ 36AB CP 4 20 in condenser return air plenum TZ 60AB and TZ 60AB4 CS 1 condenser screen TZ 12AB CS 2 condenser screen TZ 18AB and TZ 24AB CS 3 condenser screen TZ 36AB CS 4 condenser screen TZ 60AB and TZ 60AB4 EP 1 10 in evaporator return air plenum TZ 12AB EP 2 14 in evaporator return air p...

Page 11: ...orator motor 85600 1 21 condenser blower motor assembly 85600 101 83100 116 85400 160 83100 118 83100 119 condenser blower 80500 137 condenser motor 85600 2 17 85600 101 compressor 82200 023 82200 028 82200 061 82200 060 82200 065 82200 066 evaporator motor capacitor 85601 713 85601 724 85601 714 85601 723 85601 727 condenser motor capacitor 85601 724 85601 021 2 85601 713 compressor motor capacit...

Page 12: ...er unit 81000 035 3 1 4 in caster 2 per unit 81000 041 3 1 4 in swivel caster 2 per unit 81000 042 high pressure switch 87500 424 manual thermostat 87800 102 condensate tank 99900 299 condensate pan adjusting spring 88600 104 lower spring 88600 107 remote indoor sensor 86700 024 spring clip 3 8 in 81300 030 door snap in switch 84900 054 freeze protection control 87800 090 87800 091 87800 092 remot...

Page 13: ...TOPAZ Owner s Manual Wiring Schematic TZ 12AB TZ 24AB and TZ 36AB Portable Air Conditioners ...

Page 14: ...15 Wiring Schematic TZ 18AB Portable Air Conditioners ...

Page 15: ...TOPAZ Owner s Manual Wiring Schematic TZ 60AB Portable Air Conditioners ...

Page 16: ...17 Portable Air Conditioners Wiring Schematic TZ 60AB4 ...

Page 17: ...Portable Air Conditioners ...

Page 18: ...TOPAZ Owner s Manual TEMP AIR 3700 West Preserve Boulevard Burnsville Minnesota 55337 7746 89500 316 2010 TEMP AIR Inc Printed in USA 1 800 836 7432 ...