Troubleshooting Guide
Service, other than routine maintenance, should be performed by a qualified electrical and refrigeration professional.
Problem
Cause
Remedy
Unit does not run
Power interruption
Check external power supply. Look for blown
fuses or tripped circuit breakers. Reset or replace.
Thermostat inoperable
Setting may be too high. Check and reset.
Thermostat may be out of calibration or
defective. Replace.
Electrical Panel
Check output of transformer.
-24-Volt transformer defective (TZ-12AB, 18AB,
If not supplying 24 volts, replace.
24AB, 36AB and 60AB only)
-Contactor coil defective
Replace.
-Contacts stuck open, burned or dirty
Correct or change.
-Wires loose
Tighten connections.
Evaporator fan runs,
Low voltage
Check power supply for voltage outside
but compressor and
the range of 106 to 126-V on 115-V
condenser fan does
units and 187 to 253-V 208/230- V units.
not start
Thermostat
Examine control unit for loose wires and
tighten. Wait four minutes before re-starting.
High-pressure control switch
Clean condenser coil filter.
turning unit off
Clean condenser discharge screen.
Check for defective condenser fan motor.
Replace if necessary.
Restricted duct.
Short cycle timer not timed out (TZ-12A, 18AB,
Wait 5 min for timer to allow compressor to restart.
24AB, 36AB, and 60AB only)
Compressor contactor open or burned
Replace.
Refrigerant leak - no freon
Locate leak and repair. Evacuate unit
and recharge.
Loose or defective wires,
Check for loose or shorted conductors. Secure
contact between wires and connectors. Repair
or replace as necessary.
Defective compressor
Check for shorts, opens, and grounds.
Compressor replacement should be done by a
service technician.
Condensate tank-full
Empty tank and replace.
(See pg. 5 - condensate tank)
Red indicator light defective
Check tank, if full, remove tank, empty and
replace. If unit comes back on replace defective
light. (See pg. 10)
Shorted or open run capacitor(s)
Replace.
Condensate jumper plug or condensate
Unit must have either condensate pump
pump not installed
or condensate jump plug installed to
operate unit.
Compressor runs,
Open fan motor coil circuit
Replace fan motor.
but fan does not run
Shorted or open fan-motor capacitor
Replace capacitor.
Loose or defective wires
Trace and repair.
Overload relay tripped (TZ-60AB only)
Open rear access cover, push in red manual
reset button on overload relay, wait 5 min for
compressor to restart.
TOPAZ
®
Owner’s Manual
Summary of Contents for TZ-12AB
Page 13: ...TOPAZ Owner s Manual Wiring Schematic TZ 12AB TZ 24AB and TZ 36AB Portable Air Conditioners ...
Page 14: ...15 Wiring Schematic TZ 18AB Portable Air Conditioners ...
Page 15: ...TOPAZ Owner s Manual Wiring Schematic TZ 60AB Portable Air Conditioners ...
Page 16: ...17 Portable Air Conditioners Wiring Schematic TZ 60AB4 ...
Page 17: ...Portable Air Conditioners ...