TX7302 Addressable Flashing Beacon Base
Installation & Operation Manual
configuration information of the Addressable Flashing Beacon Base, as shown in Figure 10.
6.
Press “Exit” key to go back main menu when all the information is set up. And then press
“Power” key
to switch-off the programmer.
Note:
If display “Success”
,
means the entered information is confirmed. If display “Fail”
,
means failure to program the information. And it is need to re-operate.
1.Read
2.Write T
3.R/W Config 7
4.Set
②
No Cod
①
Code
③
Single
④
Dual
⑦
Strobe
⑥
Saving
⑤
Typ
⑧
Sound
⑨
Dual1
Fig.6 Main menu Fig.7 Parameter setting
Address:001
Next Address:003
Success
Tone:014
Success
Success
Address:001,002
Tone:014
ID:000000000000
Fig.8 Address setting Fig.9 Alarm sound setting Fig.10 Configuration information
3.3 Encoding Mode Setting
The TX7302 Addressable Flashing Beacon Base has three different encoding modes such as
Single-encoding Mode, Dual-encoding Mode 1 and Dual-encoding Mode 2. Different
encoding modes correspond to different ways of operation. It can be change the encoding
mode by a programming tool.
Single-encoding Mode
In Single-encoding Mode, the Addressable Flashing Beacon Base has an address. It can be
started, silenced and stopped by a controller. It can also be started by other front-end
devices. And it can be started by a detector which mounted on the Addressable Flashing
Beacon Base.
No matter what kind of start mode, the Addressable Flashing Beacon Base will
issue a fire alarm tone and optical signal.
Dual-encoding Mode 1
In Dual-encoding Mode 1, the Addressable Flashing Beacon Base has two addresses. And
the high address of the Addressable Flashing Beacon Base is shared with a detector. It can
be started, silenced and stopped by a controller with alarm tone and optical signal. It can
also be started by other front-end devices. As in Single-encoding Mode, it can be controlled
by a detector which mounted on it with warning tone and optical signal.
4050100452-Rev1.0-0917
TANDA UK
Specifications are subject to change without prior notice