background image

                                                                                                       TX7302 Addressable Flashing Beacon Base 

 

 

        Installation & Operation Manual  

1 Introduction  

 

1.1 Overview  

The TX7302 Addressable Flashing Beacon Base is an alarm warning device used to notify persons in 

the vicinity of the occurrence fire emergency in order the person to take appropriate measures. The 

unit adopt multi-application device starting from the types, parameters and wiring layout in single 

unit.  The  TX7302  Addressable Flashing Beacon Base  is powered by the communication  bus.  The 

TX7302 can change into different encoding modes such as Single-encoding Mode, Dual-encoding 

Mode 1 and Dual-encoding Mode 2 using a programming tool.

 

And it has different starting modes 

such as started by a detector, a controller or other front-end linkage. In addition, the alarm tone can 

be configured according to the requirement from 17 different tones.  

The unit manufactured base on the requirement of EN 54 part 3, European Standard. The unit is 

aesthetically pleasing with unobtrusive design that will complement modern building designs and its 

plug-in type assembles make installation and maintenance more convenient to the installer. The unit 

is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel, produced by single 

manufacture T&A, to avoid addressable communication compatibility problem.  

1.2 Feature and Benefits  

 

EN54-3 compliance 

 

Built-in MCU processor and digital addressing  

 

17 tones Programmable sound output  

 

Encoding modes such as Single-encoding Mode, Dual-encoding Mode 1 and Dual-

encoding Mode 2 

 

Programmable Evacuate or Pre-alarm/Evacuate signal  

 

8 highlights LED status cluster 

 

Be started directly by a detector 

 

Onsite adjustable parameters 

 

Loop power input  

 

Aesthetically pleasing design 

 

Universal mounting with fix base for simple installation 

 

1.3 Technical Specification  

 

Listed   

 

 

  

LPCB Pending 

 

Compliance     

 

 

EN54-3 

 

Input Voltage   

 

 

Loop Power: 24VDC [16V to 28V] 

  

 

Current Consumption   

 

Standby: 

0.8mA, Alarm: 

5mA 

 

 

 

 

Protocol/Addressing    

 

T&A, Value range from 1 to 254 

 

Address Sequence 

 

 

Single-encoding Mode: Alarm 

Dual-encoding Mode 1:1

st

 Alarm / 2

nd

 Warning 

Dual-encoding Mode 2: 1

st

 Warning / 2

nd

 Alarm 

 

Strobe Light      

 

             8 highlights LED 

 

Material / Colour  

 

 

ABS / White glossy finishing  

 

Dimension / Height 

 

 

Diameter 140mm / 59.1mm (with a cover)  

 

Weight  

 

 

 

198g (with a cover)/180g (without a cover) 

 

Class   

 

 

 

Type A, Indoors 

 

Operating Temperature 

 

-10°C to +55°C 

 

Ingress Protection Rating 

 

IP30 

 

Humidity 

 

  

 

0 to 95% Relative Humidity, Non condensing 

2 Installation   

 

                                                                                                                               4050100452-Rev1.0-0917                                                                       

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

      

 

Summary of Contents for TX7302

Page 1: ...TX7302 Addressable Flashing Beacon Base Installation and Operation Manual TANDA UK Technology Copyright 2017 All right reserved ...

Page 2: ...European Union directive 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information please visit the website at www recyclethis info 4050100452 Rev1...

Page 3: ...and Wiring 5 3 Addressable Flashing Beacon Base Configuration 6 3 1 Preparation 6 3 2 Parameter setting 6 3 3 Encoding Mode Setting 7 3 4 Tone Setting 9 3 5 Read Configuration 10 4 General Maintenance 10 5 Troubleshooting Guide 10 Appendix 1 10 Operational Performance Data for LPCB Approved Tones 10 Limitation of Addressable Flashing Beacon Base 11 4050100452 Rev1 0 0917 TANDA UK Specifications ar...

Page 4: ...04 Analogue Intelligent Fire Alarm Control Panel produced by single manufacture T A to avoid addressable communication compatibility problem 1 2 Feature and Benefits EN54 3 compliance Built in MCU processor and digital addressing 17 tones Programmable sound output Encoding modes such as Single encoding Mode Dual encoding Mode 1 and Dual encoding Mode 2 Programmable Evacuate or Pre alarm Evacuate s...

Page 5: ... 4 7 are used to connect remote indicators Where terminals 3 4 are positive and terminals 7 8 are negative TX3980 type base structure and the terminals connection diagram as shown in Figure 1 2 The bottom structure of the Addressable Flashing Beacon Base as shown in Figure 2 Install the Addressable Flashing Beacon Base on the TX3980 type base with the installation terminals of the two devices are ...

Page 6: ...ayout before placing from the Terminal Base Warning Disconnect the loop connection whilst connecting to the handheld programmer 3 2 Parameter setting 1 Connect the programming cable to Z1 and Z2 terminals as shown in Figure 5 Press Power to switch on the unit The main menu after the boot as shown in Figure 6 2 Switch on the programmer then press button 3 to set encoding mode Select the desired enc...

Page 7: ...Mode 1 and Dual encoding Mode 2 Different encoding modes correspond to different ways of operation It can be change the encoding mode by a programming tool Single encoding Mode In Single encoding Mode the Addressable Flashing Beacon Base has an address It can be started silenced and stopped by a controller It can also be started by other front end devices And it can be started by a detector which ...

Page 8: ...ns that the success or not of the encoding mode setting as shown in figure 12 and figure 13 Success Fail No Cod Single Strobe Typ Code Dual Saving Sound Fig 11 Encoding mode setting Fig 12 Success to setting Fig 13 Fail to setting Press button 9 to distinguish the two different dual encoding modes of the Addressable Flashing Beacon Base Dual1 means the Dual encoding Mode 1 and Dual2 means the Dual...

Page 9: ...esired tone as shown in figure 16 Write the number of the corresponding tone and click the button write The word Success or Fail on the screen means that the success or not of the encoding mode setting as shown in figure 17 and figure 18 3 Press Exit key to go back Main Menu Press Power to switch off the programmer Parameter Tone Code Description 1 01 970Hz 2 02 800Hz 970Hz 2Hz 3 03 800Hz 970Hz 1H...

Page 10: ... of the alarm warning device it may affect the operation to respond to a fire condition and will void the manufacturer s warranty 4 Use a damp cloth to clean the surface 5 Notify again proper personnel after conducting the maintenance and make sure to enable the alarm warning device and confirm if up and running 6 Perform the maintenance on semi annually or depending on the site conditions 5 Troub...

Page 11: ...0 1 77 9 79 1 105 81 8 81 4 78 9 79 6 135 78 3 79 4 77 9 77 8 165 79 1 79 9 78 2 79 2 3 Tone 17 Volume dB A Table 4 Sound pressure level of tone 17 at different bus voltage with 3 meters away Angle 3m Horizontal Plane Vertical Plane Max 28V Min 16V Max 28V Min 16V 15 81 1 79 6 72 6 72 5 45 74 5 78 6 73 2 70 6 75 74 3 76 5 71 7 71 1 105 74 7 80 7 76 2 76 1 135 71 7 74 5 74 5 75 2 165 75 1 75 2 73 7...

Page 12: ... test your alarm warning device at least every half year according to national codes or laws Any fire alarm devices or any other components of the system must be repaired and or replaced immediately as they fail This product is not approved to EN54 23 Beacon Functionality and must not be used as a visual alarm device or to provide a primary warning notification of fire 4050100452 Rev1 0 0917 TANDA...

Reviews: