GPU - 406
GPU - 409
AC Diff Rate –
Set the Rate (Incremental Update time) for AC Volts Differential Regulation.
Default = 0 (For Build B) or Default = 0 (For Build A)
ACV Int Gain
– Set the level of Integral Gain in the AC Voltage Regulation.
Default = 0 (For Build B) or Default = 1000 (For Build A)
ACV Int-Rate
– set the Rate (Incremental Update Time) for AC Integral Voltage regulation.
Default = 1 (For Build B) or Default = 2 (For Build A)
Fast Int Enable
– Set to On or Off the AC Fast Integral Regulation.
For tuning response to fast transient load increase.
Default = 1 (On) (For Build B) or Default = 1 (On) (For Build A)
ACV Fast Int-Rate
– set the Rate (Incremental Update Time) for AC Fast Integral Voltage
regulation.
For tuning response to fast transient load increase.
Default = 0 (For Build B) or Default = 1 (For Build A)
DCV P-GAIN
– Set the level of the DC Voltage proportional Gain
For tuning response of the 28.5V DC Regulation.
Default = 3
Idle RPM Enable
– Enable (1) or Disable (0) the GCM2 control of the engine RPM at Idle.
For Tier4f GPU fitted with Exhaust After Treatment this setting will automatically change 0 (Disable)
For units without DEF this setting may be set to 0 or 1.
Default = 1 (Enable Idle RPM Adjust) except for Tier4f
RTC Date, RTC Year, RTC Time
- Set the GCM2 Internal Real Time Clock.
The RTC is set to UTC (or GMT) universal time, not to local time.
This is set at factory calibration and does not normally need to be changed.
Default – None, time is Set at factory test.
DC Limit Slope
– Set the slope (Gain) of the DC Current Limiting.
If set too high the current will hunt (oscillate) when the load is higher than the set DC Current Limit
value.
If set too low the current limit will not reduce the current enough.
Default = 3
AC + DC Compensation
– Select the option for AC+DC comp.
For tuning Regulation when Both AC and DC outputs are enabled at the same time, the DC Output
Voltage target is moved up or down to keep AC Voltage within target window. May be set to 0 (Off)
to 4(Max)
Default = 1
Property of American Airlines
Summary of Contents for GPU-406
Page 4: ...P r o p e r t y o f A m e r i c a n A i r l i n e s...
Page 18: ...P r o p e r t y o f A m e r i c a n A i r l i n e s...
Page 22: ...P r o p e r t y o f A m e r i c a n A i r l i n e s...
Page 48: ...P r o p e r t y o f A m e r i c a n A i r l i n e s...
Page 54: ...P r o p e r t y o f A m e r i c a n A i r l i n e s...