TJERNLUND MPCI Installation Instructions Manual Download Page 8

7

PRESSURE FAULT SEQUENCE

If either the alarm circuit of the Pressure Control closes or the PSA-1 fan prover opens for more than 10 seconds, the UC1 inter-
lock control will disrupt the circuit from terminal 4 to the burner(s). The MPCI external Red fault light with audible alarm will come
on and sound alarm. The auxiliary alarm contacts will change state. Red LED 4 on the UC1 will flash continuously.

The Pressure Control will continue to try to obtain the set point for 10 minutes. If the alarm circuit opens and the PSA-1 fan prover
closes during this 10-minute period, the UC1 interlock will automatically reset and complete the circuit to the burner(s). The UC1
interlock will go into a hard lockout after 10 minutes without an automatic reset. Disrupting the call for heat or shutting off the MPCI
internal 120 VAC power switch for 10 seconds will reset the UC1 interlock control.

MPCI BURNER INTERLOCK FEATURING THE UC1

The UC1 is the standard interlock control for Tjernlund's full line of Power Venters, Draft Inducers and Combustion Air fans. It can
be interlocked with virtually any burner control circuit. Features include: adjustable pre & post purge, LED status / diagnostic indi-
cators, 10 second prover switch delay to avoid burner start up and wind induced short cycling. Interlocks with any 24-115 VAC
burner control circuit and also includes “dry” contact actuation option. After each burner cycle, the UC1 will continue to operate in
post-purge mode to allow the fan to purge the heater and vent of residual flue gases. A factory post-purge time is set at 2 minutes
and is adjustable up to 16 minutes, see “Pre / Post Purge and Prover Status Check Dip Switch Settings” on page 9.  

1. The UC1 Pre-Cycle Prover Status Check is deactivated from the factory to avoid nuisance lock out in applications where 

exhaust shafts or vents may be capable of creating enough chimney effect to make the pressure set point prior to a call for 
heat. When activated, the UC1 Universal Control checks across the P1 & P2 safety circuit Fan Prover to verify that the Fan 
Prover switch is “Open” upon a call for heat and not stuck “Closed”. See “Pre-Cycle Fan Prover Status Check”, page 9 for details.

2.  A post-purge on the UC1 has been factory set at 2 minutes.  Confirm that dip switch #5 is in the up or "on" position.  A longer 

post-purge may be necessary for longer vent runs or high heat retention, refractory lined combustion chambers. A shorter post-
purge may be desired for short vent lengths. If using the UC1 to control a combustion air fan a post-purge may not be desired.  
See “Pre / Post Purge and Prover Status Check Dip Switch Settings”, page 9 for details.

CAUTIONS

Disrupt supply power to the MPCI and heating equipment when making wiring connections and servicing the UC1 Control. Failure
to do so may result in personal injury and/or equipment damage.  UC1 LED #6 (Red) should be off with power removed.

All installation restrictions and instructions in the Exhaust/Supply Air Fan and/or VFD installation instructions must be adhered to.

Summary of Contents for MPCI

Page 1: ...TALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONIN...

Page 2: ...in the space or duct GENERAL INFORMATION Each MPCI Controller is electrically factory line tested before shipment After opening carton inspect thoroughly for hidden dam age If any damage is found noti...

Page 3: ...NG TUBING TO MPCI AND PSA 1 FAN PROVER BAROMETRIC DRAFT CONTROL IF PRESENT HEATER FURTHEST FROM THE INDUCER IF POSSIBLE THE SENSING TUBE SHOULD BE LOCATED TWICE THE MANIFOLD DIAMETER BEHIND THE HEATER...

Page 4: ...oned between the blower inlet and intake opening FOR OPEN MAKE UP AIR APPLICATIONS In Open mode the mechanical room air is sampled and an adjacent space is referenced Referencing an adjacent space wit...

Page 5: ...ol set point is outside of the PSA 1 operating range 1 Mount the PSA 1 Pressure Switch within 6 feet of the sensing tube location The switch must be mounted in a vertical position so that the sampling...

Page 6: ...ATION An intercepted call for heat is sensed at terminals A B or 1 2 of the integral UC1 Interlock Control or MAC Series interlock expansion modules The Amber LED of the UC1 will turn on 1 This closes...

Page 7: ...6...

Page 8: ...e the UC1 will continue to operate in post purge mode to allow the fan to purge the heater and vent of residual flue gases A factory post purge time is set at 2 minutes and is adjustable up to 16 minu...

Page 9: ...mper in proper location based on appliance call interlock voltage SEE WARNING 2 IMPORTANT LED 1 AMBER LED 2 BLUE LED 3 GREEN LED 4 RED LED 5 RED LED 6 RED POWER LED DRY 24 V 115 V APPLIANCE INTERLOCK...

Page 10: ...ayed Any new fault will replace any previous fault 9 ON PRE PURGE SETTINGS SEE PRE PURGE ON PAGE 3 PRIOR TO SETTING 0 Seconds 15 Seconds 30 Seconds 60 Seconds 1 2 1 2 1 2 1 2 0 Seconds 5 Seconds 20 Se...

Page 11: ...controls The steps listed under each diagram are intended as a supplement to the diagram Wiring colors or designations may vary by manufacturer If you are unable to wire the UC1 as outlined in these i...

Page 12: ...ng the MPCI external RED light with audible alarm as well as any external alarm or BMS that are wired to the alarm circuit Reconnect the pneumatic tubing to the sampling tube The safety circuit will r...

Page 13: ...y draft levels remain within the manufacturer s specified range prior to ignition and during operation CHANGING MPCI PRESSURE CONTROL PROGRAM DEFAULTS THE FACTORY PRESET PROGRAM SETTINGS ARE AS FOLLOW...

Page 14: ...13...

Page 15: ...d any service agency who performed work on the system Date of original installation and dates any service work was performed Details of the problem as you can best describe them Tjernlund Products Inc...

Reviews: