TJERNLUND MPCI Installation Instructions Manual Download Page 13

12

ADJUSTING DRAFT

Reference the heater manufacturer's instructions for its specified draft range and for where the draft should be sampled. In gen-
eral, most heaters will operate efficiently with a draft of -0.02 to -0.05" w.c. measured in the vent riser between the flue outlet and
barometric draft control (if present). The MPCI has a default draft set point of -0.10" w.c. This vent manifold pressure may need to
be adjusted up or down to meet the draft requirements of the interlocked heating equipment. 

Do not

reduce set point to less than

0.07” w.c. to avoid issues with the PSA-1 operating range.

BALANCING DRAFT OF HEATERS

1. Turn ON the service switch to all of the heaters.

2. Momentarily cycle each heater to verify that the Amber Burner Status Call LED on the UC1 or MAC-Series interlock 

control illuminates for each heater. If not, verify that wiring conforms to appropriate heater interlock wiring diagram.

3. Verify that all balancing baffles or blast gates are in the closed position. Adjust barometric controls (if present) to the most 

closed position.

4. Fire each heater individually, starting with the heater farthest from the Exhaust / Supply Air Fan. Slowly open balancing baffle or 

blast gate until the specified draft is achieved. Barometric draft controls should be closed when the heater is operating within its 
specified draft range. Adjust weight on barometric draft control so that it does not open until the manufacturer’s recommended 
maximum draft is reached. If additional draft is needed increase the set point on the MPCI.

5. After adjusting draft levels on all connected heaters, fire heaters in random order and simultaneously to verify draft levels remain

within the manufacturer’s specified range prior to ignition and during operation. 

CHANGING MPCI PRESSURE CONTROL PROGRAM DEFAULTS

THE FACTORY PRESET PROGRAM SETTINGS ARE AS FOLLOWS:

PROGRAM OPTION

FACTORY PRESETS

ADJUSTMENT RANGE

Pressure Units of Measure

Units InH2O

Units PA

Operating Mode

Control Mode

Do Not Change

Parameter

Diff. Pressure

Do Not Change

Setpoint 1 (Use for Draft)

0.10

0 to 40 (PA 0 to 100)*

Setpoint 2 (Use for Supply/Comb Air)

0

0 to 40 (PA 0 to 100)* 

NOTE:

A negative value can not be set on the Pressure Control, however, the Pressure Control can display a negative 

pressure reading. Pressure Control will read either negative or positive pressures depending on what sensing port is used 
and type of application. See “Sample and Reference Pressure Connections”, Page 2.

Output Voltage

V=10.0 V

Do Not Change

P-Parameter

50

1-999 (Acceleration Rate)

I-Parameter

3.15

Do Not Change

Controlling Mode

Positive/Heating

Do Not Change

Alarm Delay Time

10s

1 Second to 15 Minutes

The MPCI Pressure Control must be powered to enter the program mode. 

WARNING: 

Disrupt supply power to MPCI when remov-

ing and reconnecting wire from UC1 MTR terminal. With supply power OFF, remove wire from MTR on the bottom of the integral
UC1 Interlock Control and connect to the XL terminal of UC1. Reestablish power to MPCI and push the Pressure Control left but-
ton (T1), make any necessary program changes and cycle through the remaining programs by pushing the T2 button until the dis-
play reads MENU. Remove supply power to MPCI and remove lead from XL on UC1 and reconnect to MTR. Reestablish supply
power to MPCI.

To enable the SET POINT 2 for supply/combustion air a jumper wire must be installed between the last two terminals 8 & 9 on the
right hand side or the Pressure Control. See “Supply Make-Up / Combustion Air Pressure Set Point”, Page 5.

Summary of Contents for MPCI

Page 1: ...TALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONIN...

Page 2: ...in the space or duct GENERAL INFORMATION Each MPCI Controller is electrically factory line tested before shipment After opening carton inspect thoroughly for hidden dam age If any damage is found noti...

Page 3: ...NG TUBING TO MPCI AND PSA 1 FAN PROVER BAROMETRIC DRAFT CONTROL IF PRESENT HEATER FURTHEST FROM THE INDUCER IF POSSIBLE THE SENSING TUBE SHOULD BE LOCATED TWICE THE MANIFOLD DIAMETER BEHIND THE HEATER...

Page 4: ...oned between the blower inlet and intake opening FOR OPEN MAKE UP AIR APPLICATIONS In Open mode the mechanical room air is sampled and an adjacent space is referenced Referencing an adjacent space wit...

Page 5: ...ol set point is outside of the PSA 1 operating range 1 Mount the PSA 1 Pressure Switch within 6 feet of the sensing tube location The switch must be mounted in a vertical position so that the sampling...

Page 6: ...ATION An intercepted call for heat is sensed at terminals A B or 1 2 of the integral UC1 Interlock Control or MAC Series interlock expansion modules The Amber LED of the UC1 will turn on 1 This closes...

Page 7: ...6...

Page 8: ...e the UC1 will continue to operate in post purge mode to allow the fan to purge the heater and vent of residual flue gases A factory post purge time is set at 2 minutes and is adjustable up to 16 minu...

Page 9: ...mper in proper location based on appliance call interlock voltage SEE WARNING 2 IMPORTANT LED 1 AMBER LED 2 BLUE LED 3 GREEN LED 4 RED LED 5 RED LED 6 RED POWER LED DRY 24 V 115 V APPLIANCE INTERLOCK...

Page 10: ...ayed Any new fault will replace any previous fault 9 ON PRE PURGE SETTINGS SEE PRE PURGE ON PAGE 3 PRIOR TO SETTING 0 Seconds 15 Seconds 30 Seconds 60 Seconds 1 2 1 2 1 2 1 2 0 Seconds 5 Seconds 20 Se...

Page 11: ...controls The steps listed under each diagram are intended as a supplement to the diagram Wiring colors or designations may vary by manufacturer If you are unable to wire the UC1 as outlined in these i...

Page 12: ...ng the MPCI external RED light with audible alarm as well as any external alarm or BMS that are wired to the alarm circuit Reconnect the pneumatic tubing to the sampling tube The safety circuit will r...

Page 13: ...y draft levels remain within the manufacturer s specified range prior to ignition and during operation CHANGING MPCI PRESSURE CONTROL PROGRAM DEFAULTS THE FACTORY PRESET PROGRAM SETTINGS ARE AS FOLLOW...

Page 14: ...13...

Page 15: ...d any service agency who performed work on the system Date of original installation and dates any service work was performed Details of the problem as you can best describe them Tjernlund Products Inc...

Reviews: