3 Electrical
Electrical and instrument connections are wired internally via 2 x PG7 Cable glands and 5mm
pitch terminal block connectors.
To access these connectors, simply undo the 4 rear screws and carefully remove the front
cover.
Description
Specification
Terminal Connection
Power Supply
15-24Vdc Regulated
0.1 amp
+24VDC
→
Power Input +V
0VDC
→
Power Input 0V
Flowmeter Input
Pulse (max. 5kHz)
Reed Switch (max. 400Hz)
+VDC Supply to meter
→
Flo5V Out
0VDC Supply to Flowmeter
→
Flowmeter 0V
Pulse from flowmeter
→
Flowmeter
Sensor Supply 5Vdc 50mA max
room temperature. (25mA at
high temperature)
Pull up/down resistor required for NPN/PNP
– see
wiring diagrams
Output Pulse
NPN/PNP 2.5kHz
24V@20mA max.
Scalable pulse per litre
Pulse Output to PLC/display
→
Digital Output
NPN or PNP
Pull up/down resistor required for NPN/PNP
– see
wiring diagrams
Output Analog
0-5Vdc / 0-10Vdc
16 bit
Adjustable flow range
+VDC to PLC/Display
→
Analog Output V Out
0VDC of circuit
→
Analog Output 0V
4-20mA ACTIVE
16 bit
Adjustable flow range
+mA to PLC/Display
→
Analog Output mA Out
0VDC of circuit
→
Analog Output 0V