7 Troubleshooting
Symptom
Cause
Solution
LED light not seen
Power supply issue
Check wiring and supply is
15-24VDC
LED does not pulse with Flow
No output configured
Configure analog or pulse
output using Titan interface
Software
No Flow Reading from input
Incorrect Wiring
Check Pull Up or Pull Down
resistor are wired correctly
according to the diagrams in
the manual
No Pulse from meter
Check wiring and pulse
output from the flow meter
Flow Readings show zero values
Sample speed too high for
Hz received
Change Analog response
time using Titan Interface
Software
No Pulse Output on Wire but output
showing on Interface Software
Incorrect Wiring
Check Pull Up or Pull Down
resistor are wired correctly
according to the diagrams in
the manual
No Pulse Output on wire or showing
on Titan Interface Software
Incorrect settings
Check Settings installation
No analog output
Incorrect Configuration
Check that the correct
configuration and wiring is
used.
Ensure Values in the range
boxes are adequate for the
flow being measured
Indicated in “No Power” in
Value column of Flow
Details Tab of Interface
Software.
4-20mA circuit broken.
Check wiring
Check power wiring to meter
To function correctly
>15VDC
Component Failure on PCB
Note: +V into the V analog
output can cause it to fail
Return to Titan Enterprises
for repair
Analog output incorrect
Voltage too low
Increase power to meter to
>15VDC
Settings incorrect for Range Use Titan Interface software
to range the analog output
flow min and max points
Titan Interface Software Opens but
shows not connected to meter (no
spinning bars in bottom left of screen)
Two windows of the
Interface Software are open
Either drag window out of
the way or close second
window using task bar