28 |
P a g e
Tigo Energy, Inc.
|
www.tigoenergy.com
|
Fault state
Leaf
Red light flashes (1 second on, 1 second off)
Ring
Power ≤25%, LED B1 is on, LED B2/3/4 are off
Power ≤50%, LED B1/2 are on, LED B3/4 are off
Power ≤75%, LED B1/2/3 are on, LED B4 are off
Power >75%, LED B1/2/3/4 are on
Upgrade state
Leaf
Yellow light flashes (1 second on, 1 second off)
Ring
Power ≤25%, LED B1 is on, LED B2/3/4 are off
Power ≤50%, LED B1/2 are on, LED B3/4 are off
Power ≤75%, LED B1/2/3 are on, LED B4 are off
Power >75%, LED B1/2/3/4 are on
Manual forced
power ON
Leaf
Green light flashes (0.1 second on, 0.1 second off)
Ring
Power ≤25%, LED B1 is on, LED B2/3/4 are off
Power ≤50%, LED B1/2 are on, LED B3/4 are off
Power ≤75%, LED B1/2/3 are on, LED B4 are off
Power >75%, LED B1/2/3/4 are on
Manual forced
OFF
Leaf
Red light flashing (0.1 second on, 0.1 second off)
Ring
Power ≤25%, LED B1 is on, LED B2/3/4 are off
Power ≤50%, LED B1/2 are on, LED B3/4 are off
Power ≤75%, LED B1/2/3 are on, LED B4 are off
Power >75%, LED B1/2/3/4 are on
Powering Off the EI Solution
CAUTION
–
Risk of Shock and burns!
Wait 5 minutes after complete system shutdown has been initiated before
servicing the battery. Always wear appropriate PPE when servicing the
system.
•
Ensure the battery shutdown command is sent from the EI mobile
app. The app command prevents the inverter from entering backup
mode.
•
Power off battery system after the inverter has shut down.
•
Shut down grid, PV, and battery completely.
1.
Open the EI App
and send the “System Shutdown” command.
2.
Open/turn off the AC disconnect switch between inverter and the service entrance.
3.
Open/turn off the DC disconnect switch at the bottom of the inverter.
4.
Power off the battery