TIF TIF XP-1A Owner'S Manual Download Page 10

2.   Take care not to contaminate the detector probe tip if the part being tested is

contaminated. If the part is particularly dirty, or condensate (moisture) is present,
it should be wiped off with a dry shop towel or blown off with shop air. No clean-
ers or solvents should be used, since the detector may be sensitive to their
ingredients.

3.   Visually trace the entire refrigerant system, and look for signs of air  conditioning

lubricant leakage, damage, and corrosion on all lines, hoses, and components.
Each questionable area should be carefully checked with the detector probe, as
well as all fittings, hose to line couplings, refrigerant controls, service ports with
caps in place, brazed or welded areas, and areas around attachment points and
hold-downs on lines and components.

4.  Always follow the refrigerant system around in a continuous path so that no

areas of potential leaks are missed. If a leak is found, always continue to test the
remainder of the system.

5.  At each area checked, the probe should be moved around the location, at a rate

no more than 25 to 50 mm/second (1-2 in/second), and no more than 5 mm (1/4
in) from the surface, completely around the position. Slower and closer move-
ment of the probe greatly improves the likelihood of finding a leak (see fig. 7).
Any increase in beep rate is indicative of a leak.

6.   An apparent leak shall be verified at least once as follows: 

    a) Blow shop air into the area of the suspected leak, if necessary, and repeat the

check of the area. In cases of very large leaks, blowing out the area with shop
air often helps locate the exact position of the leak.

    
    b) First move the probe to fresh air and reset. Then hold the probe tip a close as

possible to the indicated leak source and  slowly move around it until the leak is
confirmed. 

Automotive A/C Systems only - 
7.   Leak testing of the evaporator core while in the air conditioning module shall be

accomplished by turning the air conditioning blower on high for a period of 15
seconds minimum, shutting it off, then waiting for the refrigerant to accumulate in
the case for 10 minutes. 

After such time, insert the leak detector probe into the blower resistor block or con-
densate drain hole, if no water is present, or into the closest opening in the
heating/ventilation/air conditioning case to the evaporator, such as the heater duct or
a vent duct. If the detector alarms, a leak apparently has been found.

DEUTSCH

TIF XP-1A

“HALOGEN HAWK”

AUTOMATISCHER HALOGEN-LECKDETEKTOR

Bedienungsanleitung

ALLGEMEINES

Der TIF XP-1Aist die Krönung von über 30 Jahren Erfahrung in der Herstellung von
Leckdetektoren. TIF ist stolz, dieses Gerät als den stabilsten und empfindlichsten
Negativ-Corona-Leckdetektor aller Zeiten vorstellen zu können. In ihm sind alle
unsere Erfahrungen und das Feedback, das wir über Jahre hinweg von unseren
Kunden bezüglich dieses Produkts erhalten haben, vereint. Damit hoffen wir,
unseren geschätzten Kunden im Hinblick auf Preis, Leistung und Zuverlässigkeit
das Beste zu bieten. 

Der Kern des Gerätes besteht aus einem hochmodernen Mikroprozessor, dessen
Verarbeitung des Digitalsignals eine wesentlich verbessere Verwaltung der
Schaltung und des Sondenspitzensignals zuläßt. Außerdem wurde die Anzahl der
Komponenten in der Schaltung um fast 40 % verringert, was zu größerer
Zuverlässigkeit und höherer Leistung führt. Der Mikroprozessor kontrolliert die
Sondenspitze und die Spannung der Batterie 4000 Mal pro Sekunde, um selbst die
geringste Schwankung im Signal auszugleichen. Dies führt zu einem stabilen und
zuverlässigen Gerät, das sich in fast jeder Umgebung auszeichnet.
Aufgrund der zusätzlichen praktischen Merkmale eignet sich der XP-1Afür viele
Zwecke. Sieben Empfindlichkeitsstufen erlauben eine 64-fache
Empfindlichkeitssteigerung von Stufe 1 bis 7. Einzigartige dreifarbige LEDs liefern
eine progressive und breite Leckgrößenanzeige, geben die Empfindlichkeitsstufe
an und lassen den Spannungsstatus der Batterie erkennen. Die Betriebsfunktionen
werden über ein Tastenfeld bedient. Das revolutionäre neue Gehäusedesign läßt
sich gut greifen und stellt sicher, daß die Sichtanzeigen während des Betriebs gut
zu sehen sind.

Lesen Sie die folgenden Seiten bitte kurz durch, damit Sie sämtliche Funktionen
des neuen XP-1Akennen- und nutzen lernen. Wir sind sicher, daß Sie mit Ihrem
Kauf hundertprozentig zufrieden sein werden. 

8

29

OPERATING TIPS

D

E

U

T

S
C
H

Summary of Contents for TIF XP-1A

Page 1: ...s Manual Manual del Propietario Guide de l utilisateur Bedienungsanleitung 100599TIF REVA Miramar Florida Toll Free 800 327 5060 Phone 954 499 5400 Fax 954 499 5454 www tif com Designed Engineered in the USA Manufactured in China ADVANCETESTPRODUCTS ...

Page 2: ...dbuch genau durchzuge hen um zu sehen ob sich das Problem eventuell leicht beheben läßt Sicherstellen daß die Sondenspitze und oder Schutzkappe VOR dem Einschicken des Gerätes zur Reparatur ausgewechselt oder gereinigt wurde Falls das Gerät noch immer nicht richtig funktioniert kann es zur Reparatur an die Adresse auf der Rückseite dieses Handbuchs eingeschickt werden Für reparierte oder ersetzte ...

Page 3: ...iehlt es sich die Teilenummer bei der Bestellungsaufgabe durchzugeben Ersatzteile TIFXP 2 Wartungssatz 3Sondenspitzen und 3 Spitzenschutzkappen TIFXP 4A Luxus Tragekoffer TIF5201 Leckquelle TECHNISCHE DATEN Stromaufnahme 3 V zwei Alkali Batterien der Größe C Höchstempfindlichkeit Gemäß SAE J1627 Klassifizierung Zugelassen für R12 R22 und R134a zu 14 g Jahr 0 5 oz Jahr Unterste Empfindlichkeit Unte...

Page 4: ...Certified to SAE J1627 for R134a R12 R22 Detects ALL Halogenated Refrigerants True mechanical pumping provides positive airflow through sensing tip Mute feature included Cordless and Portable operates on 2 C cell batteries Carrying case included 14 35 5cm flexible stainless probe Optional Carrying Holster Optional Reference Leak Source Three Year Warranty 2 35 GENERAL INFORMATION FEATURES ANWENDUN...

Page 5: ... erneut untersuchen Bei sehr großen Lecks hilft ein Ausblasen des Bereichs mit Werkluft oftmals bei der genauen Bestimmung der undichten Stelle b Die Sonde erst an die frische Luft halten und die Einstellung überprüfen Dann die Sondenspitze so nahe wie möglich an die vermutliche Leckstelle halten und langsam hin und herbewegen bis das Leck bestätigt ist Nur Autoklimaanlagen 7 Zum Lecktest des Verd...

Page 6: ... Taste SENSITIVITY a oder SENSITIVITY b wie vorstehend beschrieben verändert werden 4 Mit der Suche nach Lecks beginnen Sobald Kühlmittel entdeckt wird verwandelt sich der Ton in einen sirenenartigen Laut der sich eindeutig von dem normalen Piepton unterscheidet Außerdem leuchten die Sichtanzeigen nacheinander wie im Abschnitt Alarmanzeigen beschrieben auf 5 Die Empfindlichkeit kann mit den Tasten...

Page 7: ...ING FEATURES Battery Test Function This feature is activated by pressing the Battery Test key When pressed the LED s will display a three color bargraph indication of true battery voltage See Fig 4 The LED s correspond to voltage as shown in the figure Not all LEDs will always be on the number of LEDs on indicate the voltage level The battery voltage display will remain as long as the BATTERY TEST...

Page 8: ...urch Drücken der Taste BATTERY TEST aktiviert Auf Tastendruck erscheint eine dreifarbige Balkengrafik LED um den aktuellen Stand der Batteriespannung anzuzeigen siehe Abb 4 Die LEDs entsprechen der in der Abbildung gezeigten Spannung Nicht alle LEDs sind immer erleuchtet die Zahl der erleuchteten LEDs entspricht dem Spannungsniveau Die Batteriespannungsanzeige bleibt solange eingeschaltet wie die ...

Page 9: ...justed by pressing the SENSI TIVITY a or SENSITIVITY b key as described above 4 Begin searching for leaks When refrigerant is detected the audible tone will change to a siren type sound distinctly different from the base beep rate Additionally the visual indicators will light progressively as described in the Alarm Indications section 5 Sensitivity can be adjusted at any time during operation by u...

Page 10: ...ime insert the leak detector probe into the blower resistor block or con densate drain hole if no water is present or into the closest opening in the heating ventilation air conditioning case to the evaporator such as the heater duct or a vent duct If the detector alarms a leak apparently has been found DEUTSCH TIF XP 1A HALOGEN HAWK AUTOMATISCHER HALOGEN LECKDETEKTOR Bedienungsanleitung ALLGEMEIN...

Page 11: ...T de retourner l appareil Si l appareil ne fonctionne tou jours pas convenablement envoyez le au service de réparation dont l adresse figure au dos de ce manuel Les instruments réparés ou échangés feront l objet d une garantie supplémentaire de 90 jours All Systems 8 Following any service to the refrigerant system and any other service which dis turbs the refrigerant system a leak test of the repa...

Page 12: ...nettoyer REMARQUE N employez jamais de produits solvants tels que de l essence de la térébenthine du white spirit etc parce qu ils laissent un résidu détectable et réduisent la sensibilité de votre appareil Remplacement de la tête de détection la tête finira par s user et devra être remplacée Il est difficile de prévoir exactement quand cela se passera étant donné que la vie utile de la tête est d...

Page 13: ... N utilisez jamais l appareil sans que le protège tête soit en place Avant d utiliser l appareil inspectez toujours la tête et son protecteur pour voir s ils ne sont pas sales ou enduits de graisse Pour nettoyer 1 Enlevez le protecteur en le retirant de la tête 2 Nettoyez le protecteur avec un chiffon et ou de l air comprimé 3 Si la tête est sale elle peut être nettoyée en la plongeant dans un pro...

Page 14: ...urs perturbateurs lorsque vous essayez de détecter une fuite Procédures recommandées selon les normes SAE J1628 REMARQUE Sur les systèmes de climatisation automobiles procédez à la détec tion de fuite avec le moteur arrêté 1 Le système de climatisation ou de réfrigération devrait être chargé avec suff isamment de réfrigérant pour afficher une pression à la jauge d au moins 340kPa 50psi lorsqu il n...

Page 15: ... sur la fuite avec précision 2 Dans des endroits fortement contaminés par le gaz vous pouvez remettre l ap pareil à zéro pour bloquer la contamination ambiante de gaz La sonde ne devrait pas être déplacée lorsque vous êtes en train de la remettre à zéro L appareil peut être remis à zéro autant de fois que cela s avérera nécessaire Bombeo mecánico verdadero proporciona flujo de aire positivo a trav...

Page 16: ...cuit pour qu il ignore le niveau de réfrigérant présent à la tête Cela permet à l utilisateur de se diriger automatiquement sur la source de la fuite concentration plus élevée De même l appareil peut être déplacé à l air frais et remis à zéro pour une sensibilité maximum La remise à zéro de l appareil en l absence de réfrigérant air frais permet la détection de tout niveau supérieur à zéro Chaque ...

Page 17: ...e reajuste Ajuste de la sensibilidad El TIF XP 1A proporciona siete niveles de sensibilidad El nível de sensibilidad se indica en la visualización cuando se Dresiona alguna de las teclas de SENSITIVITY hacia arriba o hacia abajo El tono base del sonido intermitente es también una indi cación del nivel de sensibilidad Cuando se enciende la unidad está ajustada al nivel 5 de sensibilidad 1 Para ajus...

Page 18: ...hacia la fuga 2 En las áreas muy contaminadas con gas se puede reajustar la unidad para bloquear la concentración de gas en el ambiente No se debe mover la sonda mientras se esté reajustando la unidad La unidad se puede reajustar todas las veces que sea necesario lors de l utilisation Veuillez prendre quelques instants pour lire les pages suivantes avec soin afin de comprendre et de profiter de to...

Page 19: ... En las áreas donde hay mucho viento hasta una fuga grande puede ser muy difícil de encontrar En estas condiciones es mejor resguardar el área de fuga potencial 4 Tenga presente que el detector puede sonar la alarma si la punta sensora entra en contacto con humedad y o solventes Por lo tanto evite el contacto con ellos cuan do esté comprobando fugas Procedimiento recomendado por la SAE J1628 NOTA ...

Page 20: ...ándolo de la punta 2 Limpie el protector con una toalla de taller y o aire comprimido 3 Si la punta está sucia se puede limpiar sumergiéndola en un disolvente suave como el alcohol durante unos segundos y después usando aire a presión y o una toalla de taller para limpiarla NOTA Nunca use disolventes como gasolina aguarrás alcoholes minerales etc ya que dejarán un residuo detectable y desensibiliz...

Reviews: