Output relays
The following are available:
• 6 electromechanical relays (KS1-1...KS1-1...6),
• 4 solid state relays
Each final relay is independently programmable with operating mode normally excited or de-excit-
ed (
EXCITED/DE-EXCITED LOGIC
) and non-memorised, pulse or memorized operating mode
(
NON-MEMORISED/PULSE/MEMORIZED OPERATING MODE
).
A programmable timer is available for each final relay, which sets the minimum pulse duration of the
relay itself. The parameters can be set in the menu
Set \ Relays.
Programming and configuration area available at any time, even with the relay in service, inde-
pendently for each relay.
Detailed information:
• If a final relay is set to normally de-excited, it remains in standby at input values corresponding to
no trip
• If a final relay is set to normally excited, it remains in operation when powered and at input values
corresponding to no trip
• If the relay is set to automatic reset (
Operating mode NON-MEMORIZED
), it switches to
standby when the anomalous condition of the input value ceases. A timer can be set for each final
relay to set the minimum hold time when the relay is actuated (Minimum operating time)
• If manual reset is set (
Operating mode MEMORIZED
), the final relay remains actuated until
the RESET button is pressed or the respective command is sent via software (ThySetter of comms
bus)
• If set to pulse mode (
Operating mode PULSE
), the final relay switches to standby after a pro-
grammable delay (Minimum operating time) regardless of the condition of the input values
Output relays KS1-1...KS1-6 can be assigned independently in the menu for the individual; protection
functions, as shown in the matrix described below (Tripping Matrix).
[1][2]
Each relay on the external DMRIS0 board (DMRIS01-1...DMRIS01-12 and DMRIS02-1...DMRIS02-12)
can be mapped to one of the default functions listed below..
FUNCTIONS
Output relays
Output DMRIS01-1
Output DMRIS01-2
CH-port for (BLP) block
No TFN/ HV client riser (80S)
Note 1 When assigning functions to the output relays, take care to avoid conflicts between different functions.
The default factory settings provide for deactivation of all output relays.
Note2 The functions of the solid state outputs are not programmable
INPUT
OUTPUT MEMORIZED
OUTPUT NOT MEMORIZED
PULSE OUTPUT
Final relay operating modes
Minimum activation time
tTR
Relay-timers.ai
t
tTR