102
DMC3S - Manual - 08 - 2021
F_51-IECC-Char.ai
1.1
2
3
4
5
6 7 8 9 10
20
I /I >inv
0.01
0.1
1
10
100
1000
10000
100000
t [s]
10 s
60 s
5 s
1 s
0.5 s
0.2 s
0.02 s
0.1 s
t =t>inv
·
[(I/I>inv)2-1]
80
Note: the set operating time refers to a ratio I/I>inv = 9
t>inv
—
DMC3S - IEC extremely inverse curves (type B)