23
DMC3S - Manual - 08 - 2021
Operating time (
t
ED
>
inv
)
0.02...60.0
s
0.02...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
Threshold I
ED
>>a
Type of characteristic
(
I
ED
>>
a
Curve)
DEFINITE,
IEC/BS A, B, C, B-LI
Reset delay
(
t
ED
>>
aRES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Second definite time threshold (
I
ED
>>
adef
-
U
ED
>>
adef
)
Residual current operating time
0.005...25.0
I
En
0.005...0.995
I
En
(step 0.005
I
En
)
1.00...9.99
I
En
(step 0.01
I
En
)
10.0...25.0
I
En
(step 0.1
I
En
)
Residual current trip value
0.001...1.000
U
En
(step 0.001
U
En
)
Characteristic
angle
0...359°
(step 1°)
Operating
half-sector
1...180°
(step 1°)
Operating time (
t
ED
>>
adef
)
0.05...1000
s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Back-up time (
t
rED
>>
adef
)
0.05...0.50 s (step 0.01 s)
Shrink time trip (
t
cIED
>>
adef
)
0.05...1000
s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Shrink time operating time (
t
atcIED
>>
adef
)
1...60 s (step 1 s)
Inverse time
[1]
Second inverse time threshold (
I
ED
>>
ainv
-
U
ED
>>
ainv
)
Residual current operating time
0.005...20.00
I
En
0.005...0.995
I
En
(step 0.005
I
En
)
1.00...20.00
I
En
(step 0.01
I
En
)
Residual current trip value
0.001...1.000
U
En
(step 0.001
U
En
)
Characteristic
angle
0...359°
(step 1°)
Operating
half-sector
1...180°
(step 1°)
Operating time (
t
ED
>>
ainv
) 0.02...60.0
s
0.02...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
Threshold I
ED
>>b
Reset delay
(
t
ED
>>
bRES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Third definite time threshold (
I
ED
>>
bdef
-
U
ED
>>
bdef
)
Residual current operating time
0.005...25.0
I
En
0.005...0.995
I
En
(step 0.005
I
En
)
1.00...9.99
I
En
(step 0.01
I
En
)
10.0...25.0
I
En
(step 0.1
I
En
)
Residual current trip value
0.001...1.000
U
En
(step 0.001
U
En
)
Characteristic
angle
0...359°
(step 1°)
Operating
half-sector
1...180°
(step 1°)
Operating time (
t
ED
>>
bdef
)
0.05...1000
s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Back-up time (
t
rED
>>
bdef
)
0.05...0.50 s (step 0.01 s)
Shrink time trip (
t
cIED
>>
bdef
)
0.05...1000
s
0.05...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Shrink time operating time (
t
atcIED
>>
bdef
)
1...60 s (step 1 s)
Note1
Inverse time curve IEC 255-3/BS142 (type A or SIT):
t = 0.14 · t
ED
>>
inv
/ [(I
E
/I
ED
>>
inv
)
0.02
- 1]
Very inverse time curve IEC 255-3/BS142 (type B or VIT):
t = 13.5 ·
t
ED
>>
inv
/ [(I
E
/I
ED
>>
inv
) - 1]
Long inverse time curve (IEC 255-3/BS B LTI):
t = 120 ·
t
ED
>>
inv
/ [(I
E
/I
ED
>>
inv
) - 1]
Extremely inverse time curve IEC 255-3/BS142 (type C or EIT):
t = 80 ·
t
ED
>>
inv
/ [(I
E
/I
ED
>>
inv
)
2
- 1]
t
:
operating time
t
ED
>>
inv
:
operating time regulation
I
ED
>>
inv
:
trip threshold regulation
I
E
:
measured residual current
Asymptotic reference value:
1.1
I
ED
>>
inv
Minimum operating time:
0.1
s
Dynamic: 1.1 ≤ I
E
/I
ED
>>
inv
≤ 20
With regulation I
ED
>>
inv
greater than
0.5
I
E
n
, the upper limit of the measurement range is
10
I
E
n