T[p1] > F[p2] D(optional):
The relay opens when actual pressure falls below
threshold F[p2] and closes again as soon as actual pressure exceeds threshold
T[p1].
Setting T[p1] = F[p2] ist not allowed! A gap between the thresholds
being too small may result in flickering of the relay and can even
cause damage to the relay!
Setting E:
Relay closes in case of a device error.
Setting !E:
Relay opens in case of a device error.
Setting U:
Relay closes in case of pressure underrange.
Setting !U:
Relay opens in case of pressure underrange.
Setting O:
Relay closes in case of pressure overrange.
Setting !O:
Relay opens in case of pressure overrange.
Setting T0:
Open relay by software command (off).
Setting T1:
Close relay by software command (on).
The control LEDs on top of the transducer will be on as soon as
the related relay is closed.