T1216W-C
MARINEW-P-I
1
11/12
PAGE 24 of 39
7.8
DIL switch settings on the
Repeater Interface Board:
DIL switch SW1 on the C1631 Repeater Interface
PCB is used to set the quantity of repeaters and the
repeater addresses as follows:
o
To set the repeater quantity, set SW1 on the
C1631 fitted to the fire alarm panel in line with
Table 2
– C1631 settings for repeater quantity.
Table 2
– C1631 settings for repeater quantity
SW 1
Repeater Quantity
0
1
2
3
4
5
1-1
Off
On
Off
On
Off
On
1-2
Off
Off
On
On
Off
Off
1-3
Off
Off
Off
Off
On
On
o
To set the addresses of the individual repeater
panels, set SW1 on the C1631 fitted to each
repeater panel in line with Table 3
– C1631
setting for repeater addresses. Note that each
repeater must have a different address.
Table 3
– C1631 setting for repeater addresses
SW 1
Repeater Address
0 *
1
2
3
4
5
1-1
Off
On
Off
On
Off
On
1-2
Off
Off
On
On
Off
Off
1-3
Off
Off
Off
Off
On
On
* Note: Address 0 = repeater disabled.
7.8.1 C1630 Output Interface
Configuration
The C1630 PCB is fitted to connectors on the
C1627 board. It provides the communications path
to the output expansion modules [C1633, C1634
and C1635]. The quantity and type of output
expansion boards are set on DIL switches on the
C1630. For the standard T1216W-C panel, the
C1630 will be configured at works prior to dispatch.
If further output expansion modules are to be added
the configuration setting on the C1630 will need to
be changed accordingly.
Table 4
– Setting Quantity and Type of O/P
Modules on the C1630
C1630
DIL Switch
setting
Qty of
board
s
Type of board
F/P0
F/P1
C1634 or C1635 configured
to FP [Fire protection
Output]. See configuration
details in T1200E-C Manual.
Off
Off
0
On
Off
1
Off
On
2
On
On
4
S/C0
S/C1
C1635 configured as
sounder module. See
C1635 configuration details
in T1200E-C Manual.
Off
Off
0
On
Off
1
Off
On
2
On
On
4
LED0 LED1
C1633 open collector output
module. See C1633
configuration details in
T1200E-C Manual.
Off
Off
0
On
Off
1
Off
On
2
On
On
4
VDR
VDR [Voyage Data
Recorder Output Module]
C1714 for relay and serial
data outputs.
Off
0
On
1
Note: Select switch to left hand side for OFF and
right-hand side for ON.
7.8.2 C1634 8 way volt free relay output
module configuration
Table 5
– Setting C1634 Board Address
SW1
Function
AD0
AD1
Board Address
Off
Off
0
On
Off
1
Off
On
2
On
On
3
Table 6
– Setting C1634 Zone Range
SW1
Function
Zonal
ZN0
ZN1
O/P 1-8 zone range
Off
N/A
N/A
All O/Ps operate on
any zonal fire
On
Off
Off
Z1-Z8
On
On
Off
Z9-Z16
On
Off
On
Z17-Z24
On
On
On
Z25-Z32