T1216W-C
MARINEW-P-I
1
11/12
PAGE 22 of 39
SW 2/6 - Enable Zonal Alarms, SW 2/7- Pulse
Non Alarm Zones:
MODE
SW 2/6
SW 2/7
General Alarms
OFF
OFF
Crew Mode
OFF
ON
Zonal Alarms
ON
OFF
Zonal Alarms with Alert
ON
ON
o
General Alarms
– all sounders operate
(continuously or pulsed
– DIL SW 2/2) until
silenced.
o
Zonal Alarms
– Only the Alarm circuit(s) for
the zone(s) in fire will operate (continuously
or pulsed
– DIL SW 2/2) until silenced.
Note: Zonal alarms on the T1216W-C affects
only the expansion module sounder circuits, the
motherboard sounder circuits always operate as
General Alarms.
o
Zonal Alarms with Alert
– The Alarm
circuit(s) for the zone(s) in fire will operate
(continuously or pulsed
– DIL SW 2/2) until
silenced. All other Alarm circuits will pulse.
Note: Zonal alarms on the T1216W-C affects
only the expansion module sounder circuits,
the motherboard sounder circuits always
operate as General Alarms.
o
Crew Mode
– Sounder circuit 2 is pre-
assigned to Bridge area, Sounder circuit 1 is
pre-assigned to machinery space zones,
Sounder circuits 3 & 4 are for all other areas:
Sounder circuits cannot be manually
configured for delayed operation.
Sounder circuit 2 on the panel control
board always operates immediately on
any fire alarm condition.
Sounder circuit 1 will operate immediately
if there is a fire in a machinery space
zone, but will be delayed for 2 minutes for
a fire on any other zone.
Sounder circuits 3 & 4 on the control
board and any output board sounder
circuits are always delayed by 2-minutes.
The fire Output & Fire Protection Outputs
can be optionally configured to be delayed
along with the sounders.
Operation of Silence Alarms will stop the
delay if operated within the 2-minute delay
period, preventing all delayed outputs
from operating.
Operation of Resound alarms will clear
the delay and operate all delayed outputs.
Operation of a manual call point or the
Delay Override button will clear the delay
& operate all delayed outputs.
The delay can be configured to restart for
a new fire condition if the alarms are
silenced within the 2-minute delay period
(see SW 2/3 details above).
SW 2/8 - Silent Zone Test:
Select sounder response in One Man [Detector]
Test Mode:
o
OFF
: Sounders operate once on each test.
o
ON
: Sounders do not respond to a zone test.
SW 2/9 - Buzzer Disable:
Enable/disable panel fire/fault buzzer.
o
OFF
: Buzzer is enabled.
o
ON
: Buzzer is disabled. General Disablement
LED illuminated.
This is not compliant to EN54-2 & is provided for
commissioning purposes only. The buzzer will
continue to sound for a system fault or for total
power failure if the 9V battery is fitted.
SW 2/10 - Latched Faults:
When enabled, all fault conditions latch until
the Reset switch is operated.
o
OFF
: Non-latched faults.
o
ON
: Latched faults.