background image

T1216W-C

 

MARINEW-P-I

 

11/12

 

PAGE 18 of 39 

 

circuits.  At  the  panel  end,  measure  the 
resistance  across  the  positive  &  negative  ends 
of  the  cables  for  each  of  the  circuits;  ensuring 
the  value  does  not  exceed  20

.  Remember  to 

remove the wire links after the tests. 

Correct  polarity  throughout  all  circuits  must  be 
maintained. Check and rectify any faults. 

4.  All  sounders,  detector  heads  and  call  points 

should  now  be  connected  and  the  correct  end-
of-line  devices  fitted.  Use  the  spare  end-of-line 
devices  supplied  and  leave  the  EOL  devices  in 
the  panel  terminals  at  this  stage.  Remember  to 
remove  any  links  fitted  to  detector  bases.  Be 
very  careful  to  maintain  correct  polarity  at  each 
device. 

Warning: 

Intrinsically safe zone arrangement: 

1.  Ensure that the installation has been carried out 

in 

full 

accordance 

with 

the 

installation 

documentation  provided  with  the  I.S.  devices 
and  I.S.  barrier.  Failure  to  carry  out  the 
installation  correctly  is  likely  to  render  the 
system unsafe and risks causing an explosion.  

2.  End-of-line  resistors  with  a  value  of  10K

  must 

be  used.  Additionally,  these  resistors  must  also 
comply  with  the  requirements  laid  down  in  the 
installation  data  sheets  provided  with  the  I.S. 
barrier and the I.S. fire detection devices. 

3.  Any  zones  used  for  I.S.  applications  must  be 

configured to Intrinsically Safe mode. [Except for 
mixed I.S./Non-I.S. zones as detailed below]. 

4.  Recommended I.S. barrier - MTL5061/MTL5561 

[galvanic type]. 

5.  Mixed I.S and Non-I.S. Zones: 

Where  the  Safety  System  Documentation 
allows,  zones  can  contain  I.S.  and  Non  I.S. 
devices.  The  requirements  of  the  Safety 
Documentation must be applied and the number 
of I.S. devices must be limited to 3 in total. 

The  I.S.  devices  must  be  located  at  the  end  of 
the  zone  with  the  I.S.  barrier  located  in  an 
adjacent  safe  area.  All  of  the  non-I.S.  devices 
must  be  connected  in  the  zone  wiring  between 
the  barrier  and  the  panel.  The  I.S  devices 
should  be  connected  between  the  I.S.  barrier 
and the end of line. 

The  zone  must  be  configured  to  the  non-I.S. 
mode  [This  simply  sets  the  operating  detection 
thresholds and is not a safety issue]. 

The  non-I.S.  section  [safe  side  -  between  the 
panel and the I.S. barrier] will support full open 
and 

short 

circuit 

fault 

monitoring 

and 

detector/MCPs fire event discrimination. The I.S. 
section (hazardous side - between the IS barrier 
and  the  end  of  line  resistor)  will  support  open 
circuit  fault  monitoring  only  -  short  circuit  fault 
will  raise  a  detector  fire.  It  will  not  support 

detector/MCP  discrimination;  all  devices  will 
raise a detector fire indication. 

Intrinsically  Safe  alarm  devices  [sounders]  may  be 
connected  via  an  MTL  5021  or  MTL5521  galvanic 
isolator.  There  are  no  requirements  for  configuring 
the  panel’s  sounder  outputs. 

Note:  Galvanic 

isolators  prevent  fault  monitoring  of  the 
sounder  circuit.  Any  cable  fault  between  the 
isolator  and  I.S.  sounders  will  not  be  detected

The  3k9  end  of  line  monitoring  resistor  should  be 
connected  across  the  barrier  terminals  11  and  12 
[i.e.  in  parallel  with  the  sounder  circuit  input  to  the 
safe  area  terminals  on  the  IS  barrier].    The 
installation  requirements  supplied  with  the  I.S. 
barrier  and  the  I.S.  sounders  must  be  fully 
observed. 

6.5 

Powering up  

Prior  to  powering  up,  the  panel  will  have  been 
installed  in  accordance  with  the  installation 
instructions, all cabling will have been fully installed 
and  tested,  glanded  into  the  panel  enclosure  but 
not  connected  to  the  panel  terminals.  The  mains 
supply should be isolated externally to the panel. 

The  interface  connections  to  the  WMRCP  should 
be isolated prior to powering up the T1216W-C. 

1.  Connect the 9V battery lead to J4 on the rear of 

the display PCB. 

2.  Connect  the  buzzer  lead  to  J6.  The  buzzer  will 

sound. 

3.  Check the 24V battery connections are correct. 

4.  Check  the  Fault  Routing  Output  configuration 

link (3-way link at J6, J7, J8) has been removed. 
[Link located on the C1627 motherboard directly 
below the Fault Signal relay]. 

5.  Final battery connections: 

  Fit  the  connector  on  the  end  of  the  black  lead 

onto  the  negative  (black)  terminal  of  the  left-
hand  battery.  Fit  the  connector  on  the  end  of 
the red  lead onto the positive (red) terminal of 
the right-hand battery. 

  Connect  the  blue  battery  lead  between  the 

positive  (red)  terminal  of  the  left-hand  battery 
and  the  negative  (black)  terminal  of  the  right-
hand battery.  

Warning:  Connection  of  the  batteries  will 
power  up  the  panel  even  if  the  mains 
supply is not energised.

 

6.  Ensure  the  mains  supply  is  safely  isolated 

external to the panel. Remove the mains supply 
fuse  from  the  panel  mains  terminal  block.  Once 
the  permit  to  energise  the  mains  supply  is  in 
place, energise the mains. At the mains terminal 
block in the panel, check the voltage and polarity 
are  correct.  Isolate  the  mains  supply  again 
before  replacing  the  panel  fuse  and  finally  re-
energising. 

Summary of Contents for TYCO T1216W-C

Page 1: ...12 2012 Thorn Security Ltd PAGE 1 of 39 Registered Company Thorn Security Ltd Registered Office Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE TYCO T1216W C Marine Fire Detection Alarm Con...

Page 2: ...EW OF THE COMMISSIONING PROCEDURE 17 6 4 PRE COMMISSIONING WIRING CHECK 17 6 5 POWERING UP 18 6 6 CONFIGURATION 19 6 6 1 BASIC DEFAULT CONFIGURATION 19 6 6 2 VESSEL SPECIFIC CONFIGURATION 19 7 OPERATI...

Page 3: ...D SIDE OF DISPLAY PCB 32 FIGURE 12 C1634 RELAY OUTPUT MODULE 32 FIGURE 13 C1630 OUTPUT EXPANSION INTERFACE 33 FIGURE 14 C1631 REPEATER INTERFACE BOARD 33 FIGURE 15 C1665 MUSTER INTERFACE BOARD 33 FIGU...

Page 4: ...plicable Refer to the installation instructions in section 5 2 4 Commission the panel Refer to section 6 Commissioning 5 Installation The control panel must be installed by suitably qualified technici...

Page 5: ...and battery swelling Batteries are irrecoverable from this condition and should be replaced LOW TEMPERATURE will prolong battery life but reduce output capacity DANGER Do not incinerate batteries If...

Page 6: ...secure the door shut The screws will remain attached to the door 4 Open the door Note that the door will open past 180 degrees and will put tension on the hinges if no support is provided underneath...

Page 7: ...eck that neoprene seals have been fitted as shown in Figure 1 then fully tighten all of the fixing nuts bolts e Check that the enclosure is firmly seated against the bulk head and is not deformed in a...

Page 8: ...s in the back of the enclosure that are used to mount the enclosure b Mark the location of one of the upper fixing holes on the wall bulkhead Drill and fix with a suitably plated or stainless steel M5...

Page 9: ...to the repeater You can use two cores in the data cable for this purpose only if the voltage drop between the panel and repeater is not more than 2Vdc Notes One repeater will draw up to 75mA which me...

Page 10: ...t St an da rd s A pp ro va l 00 86 0 9 K M 95 74 4 F ir e A la rm S y s te m Is ol at e Su pp ly B ef or e 00 86 C PD 5 55 92 1 O pe ni ng C ov er TH IS U N IT M U ST B E EA R TH ED RATING LABEL T h...

Page 11: ...ff Top right hand corner of C1626 motherboard Figure 3 Repeater connection diagram M in Sin GND GND M out S out C1665 Muster Interface in Fire Panel M in Sin GND GND M out S out C1665 Muster Interface...

Page 12: ...in series with R50 2 6k8 Resistor TB5 3 TB5 4 313 314 R50 2 De energised fault condition Before Modification 10k Resistor TB5 3 TB5 4 313 314 R50 2 De energised fault condition After Modification Wir...

Page 13: ...necessary permits to work are in place The Engineer responsible for the commissioning of the WMRCP system is available and a procedure is in place which includes the allocation of the various tasks a...

Page 14: ...rm the other side identifies this switch as Muster Additional double sided inserts may be supplied for Chinese or Japanese applications 5 5 1 To change the inserts 1 Isolate the mains supply to the pa...

Page 15: ...nut by turning the nut a quarter of a turn Press the frame against the enclosure door using fingers only and check for any slack 22 Repeat step 21 until the frame is firmly seated Note Over tightenin...

Page 16: ...hinge These are used to secure the door stay enclosure mounting bracket 6 Offer the door stay door mounting bracket up to the studs on the display frame as shown in Figure 9 and fit one M6 washer and...

Page 17: ...basic wiring continuity is proven 6 3 An Overview of the Commissioning Procedure Commissioning is broken in to 3 sections 1 Pre commissioning wiring check 2 Powering the panel up with no field wiring...

Page 18: ...between the IS barrier and the end of line resistor will support open circuit fault monitoring only short circuit fault will raise a detector fire It will not support detector MCP discrimination all...

Page 19: ...tively Charts are provided in the System Log Book for planning recording the actual configuration This configuration is not lost when the panel is powered down 7 Operating the Engineer s functions 7 1...

Page 20: ...Any current alarms disablements will be re indicated along with any active status indications Delay on etc o Close and lock the panel door o Return the ACCESS keyswitch to the 0 position to disable th...

Page 21: ...Zones o OFF Configuration mode disabled o ON Enables selected zones to be configured to non latching fire mode via the Engineer s Select feature Not EN54 compliant function SW 1 5 Config I S Zones o...

Page 22: ...immediately if there is a fire in a machinery space zone but will be delayed for 2 minutes for a fire on any other zone Sounder circuits 3 4 on the control board and any output board sounder circuits...

Page 23: ...lt Output Fault monitored powered O P J6 J7 J8 Fitted C1627 motherboard to the right of the Fault Routing Output relay Volt Free C O relay O P Removed Fire Protection Output Fault monitored powered O...

Page 24: ...d type of output expansion boards are set on DIL switches on the C1630 For the standard T1216W C panel the C1630 will be configured at works prior to dispatch If further output expansion modules are t...

Page 25: ...Engine Top Zone 2 O P 2 Main Engine Top Zone 3 O P 3 Generator Sets 1 2 3 Zone 4 O P 4 Generator Sets 1 2 3 Zone 5 O P 5 Generator Engine 4 Zone 6 O P 6 Generator Engine 4 Zone 7 O P 7 Purifier Space...

Page 26: ...ate a fire condition on a zone to operate the output Check that the fire signal operates the interface relay adjacent to the fire protection equipment 4 Open circuit the field wiring and confirm that...

Page 27: ...he primary supply Note The battery requires a period in excess of 24hrs to achieve a fully charged condition 7 9 12 T1216W C WMRCP Interface This work must be carried out in conjunction with the Engin...

Page 28: ...enclosure Check that all Earth leads are correctly firmly connected Check that End Of Line resistors in unused circuits are positioned in a safe manner and are unlikely to create short circuit faults...

Page 29: ...led Yellow Flashes for a fault on the Fire Output Steady when Fire Output is disabled Fault Output Fault Disabled Yellow Flashes for a fault on the Fault Output Steady when Fault Output is disabled 1...

Page 30: ...When controls are unlocked Reset Resets any standing fire and or fault conditions When controls are unlocked and panel has fire and or fault conditions Silence Buzzer Press to stop the buzzer soundin...

Page 31: ...SW1 1 to SW1 10 J18 Earth Fault Monitoring Link Connector for C1632 Zone Expansion Board Alarm Circuits Marked with Active Polarity Aux DC Supply 24V 0V Remote Inputs Silence Alarms Evacuate Reset Aux...

Page 32: ...osition Muster mode Link removed Evacuate Muster modes disabled Figure 11 Rear Right Hand Side of Display PCB SW1Config switch Top to bottom AD0 AD1 ZN0 ZN1 ZONAL VDR OFF Comms Fault LED J2 Comms In o...

Page 33: ...ity and type of O P modules connected From top to bottom F P0 Fire Protection F P1 Fire Protection S C0 Sounder Controller S C1 Sounder controller LED0 LED driver LED1 LED driver VDR Voyage Data Recor...

Page 34: ...DIMENSIONS SHOWN WITH BOTTOM ENTRY CABLE GLAND PLATE IF TOP ENTRY REQUIRED REVERSE DIMENSIONS ENCLOSURE ENCLOSED SPACES SUBJECT TO TEMPERATURE HUMIDITY VIBRATION TECHNICAL DATA DIMENSIONS 400mm WIDE x...

Page 35: ...PPLY INCOMING PRIMARY AC MAINS SUPPLY OUTGOING AC MAINS SUPPLY TO PANEL INCOMING 24Vdc SUPPLY FROM PANEL 24V 0V AUX D C 24V 0V 4 SIL EVAC RST Panel Motherboard Auxiliary 24Vdc Terminals Mains Terminal...

Page 36: ...erminals C1634 Relay O P module address 2 zonal outputs 9 14 to Watermist panel C1634 Relay O P module address 1 zonal outputs 1 8 to Watermist panel Gland Plate Earth Wiring Screen Earth Terminal Blo...

Page 37: ...ect return to Aux 24V Zones 2 8 10k end of line resistor Zones 9 16 10k end of line resistor Field wiring terminals on panel PCB Detector base Manual Call Point Sounder 3k9 end of line resistor Aux 24...

Page 38: ...80R 1W activation resistor Z15 Z16 Z15 Z16 Wire Links Zones 15 16 from T1216W C panel 9 10 7 8 5 6 TB2 RL FLT I F Fault Signal from from T1216W C panel Watermist Control Panel Modification Note 1 Mods...

Page 39: ...with a suppression diode as shown in Figure 20 4 Remote Inputs Silence Alarms Evacuate Reset Class Change Connections Connect to 0V AUX DC via the Normally Open contact inactive condition 5 Remote Ou...

Reviews:

Related manuals for TYCO T1216W-C