2.2.1 Device's Installation Flow Chart Illustrated as following

Inventory

Check

Mounting 

In Rack

2.2.2 Environment Requirement

Item 

Machine Hall 

Space 

When  user  installs  machine  frame  array  in

hall,  the  distance  between  2  rows  of  machine  frames 

should be 1.2~1.5m and the distance against wall should 

be no less than 0.8m.

Machine Hall 

Floor 

Electric Isolation, Dust Free

Volume 

resistivity 

of 

ground 

anti

material:1X10

resistance:  1M  (Floor  bearing  should  be  greater  than 

450Kg/

Environment 

Temperature 

5~40

installing air

Relative 

Humidity 

20%~80% sustainable    10%~90% short time

Pressure 

86~105KPa

Door & Window 

Installing rubber strip for sealing door

glasses for window 

Wall 

It can be covered with wallpaper, or brightness less paint.

Fire Protection 

Fire alarm system and extinguisher

Power 

Requiring 

lighting  power  are  independent  to  each  other.  Device 

power  requires  AC  power  100

carefully check before running.

H-HD-IRD

6 

s Installation Flow Chart Illustrated as following

 

Connecting 

Grouding 

Wire and 

Power 

Cord

Setting 

Parameter

Connecting 
Signal Wire

2.2.2 Environment Requirements 

Requirement 

When  user  installs  machine  frame  array  in  one  machine 

hall,  the  distance  between  2  rows  of  machine  frames 

should be 1.2~1.5m and the distance against wall should 

be no less than 0.8m. 

Electric Isolation, Dust Free 

Volume 

resistivity 

of 

ground 

anti-

material:1X10

7

~1X10

10

Grounding  current  limiting 

resistance:  1M  (Floor  bearing  should  be  greater  than 

450Kg/

(sustainable )

0~45

(short time)

 

installing air-conditioning is recommended 

20%~80% sustainable    10%~90% short time 

86~105KPa 

Installing rubber strip for sealing door-gaps and dual level 

glasses for window   

It can be covered with wallpaper, or brightness less paint.

Fire alarm system and extinguisher 

Requiring  device  power,  air-conditioning  power  and 

lighting  power  are  independent  to  each  other.  Device 

power  requires  AC  power 100-240V  50-60Hz  2A.  Please 

carefully check before running. 

IRD-V3  User  Manual 

Running 

Device

 

one  machine 

hall,  the  distance  between  2  rows  of  machine  frames 

should be 1.2~1.5m and the distance against wall should 

-static 

Grounding  current  limiting 

resistance:  1M  (Floor  bearing  should  be  greater  than 

gaps and dual level 

It can be covered with wallpaper, or brightness less paint. 

conditioning  power  and 

lighting  power  are  independent  to  each  other.  Device 

.  Please 

Summary of Contents for H-IRD-V3s

Page 1: ...User User s M s M s M s Manual anual anual anual Broadcast integrated receiver decoder for satellite and terrestrial program injection for broadcast headends Supports advanced stream operations for R...

Page 2: ...ion Preparation 2 3 Wire s Connection 2 4 Signal Cable Connection Chapter 3 Operation 3 1 Main Interface 3 2 General Setting Chapter 4 NMS Setting Chapter 5 Troubleshooting H HD IRD V3 User Manual DIR...

Page 3: ...he LCD or IP sources Dual slots for industry standard CAM module multiplex and de encryptcomplete carrier TS streams programs can be inserted to the MPTS for ASI and IP outputs while simultaneously de...

Page 4: ...erfaces M modules Max decryption of 8 SD programs mode E s Management and dual TS outputs programming after power failure Supports Closed Captioning streams for both 608 and 708 standards Supports man...

Page 5: ...cator 3 Power Indicator 4 Up Down Left Right 5 Enter confirming 6 Menu Key 7 Lock Key Indicator 8 LCD Monitor 9 Switch Button 10 PCMCIA interface Rear Panel Illustration H HD IRD 3 1 5 Appearance and...

Page 6: ...egrated power switch and socket 19 Grounding Wire H HD IRD 4 S S2 Loop Out Interface Interface Interface ut3 and ASI Out4 Interface Output Single TS Stream from and ASI Out2 Interface Output multiplex...

Page 7: ...necessary H HD IRD 5 Chapter 2 Installation Guide Thor will provide standard interface cabling for the end users application Please check the included packing list that came with your order and confi...

Page 8: ...ironment Requirements Requirement When user installs machine frame array in one machine hall the distance between 2 rows of machine frames should be 1 2 1 5m and the distance against wall should be no...

Page 9: ...umb make sure the device is grounded when installing anywhere Always use copper wire When applied correctly the ground must be wrapped well to ensure maximum conduction so it can reduce any high frequ...

Page 10: ...upply socket while insert the other end to AC power When the device solely connects to protective ground it should adopt this power in an pendent way Especially if you share the same ground with other...

Page 11: ...ut Cable I Component Output CVBS Illustration ASI Input and Output Cable Illustration H HD IRD 9 llustration Out Cable Illustration utput CVBS Output and Sound Channel Output Cable Input and Output Ca...

Page 12: ...e device according to the described on the rear panel illustration connect the cable as shown below RF IN interface of satellite receiver while the other end connected to the satellite signal source e...

Page 13: ...ASI OUT interface the other end of the wire is encoder and multiplexer As follows CVBS Output and Sound Channel Output Users can find the YPbPr CVBS and Left Right sound channel interface on the devic...

Page 14: ...wire is output interface of the HD IRD the other end of the wire is OUT INPUT as follows Connection Illustration interface on the device according to the connector mark described on the rear panel il...

Page 15: ...l available configuration settings can be accessed through the interface menu tree Please refer to the following guide for rd Function Description entered value resume previous setting Return to previ...

Page 16: ...below are available from these 9 root menu trees key to enter into the menu of the input setting S2 signal in as an example The page menu from 1 1 to 1 3 represents the tuner ASI and IP input ports of...

Page 17: ...programs check and set the satellite frequency LNB frequency and symbol rate of its 1 1 3 1 1 4 At the submenu 1 1 5 user can decide which LNB voltage to apply choose to turn on the 22 KHz to search...

Page 18: ...bmenus H HD IRD 16 menu to enter into 1 2 ASI IN and users can view the program multiplexed displays below page Similarly 1 3 1 Prog Parse offers the same information with 1 1 1 and 1 2 1 User also co...

Page 19: ...nd search can enter into below submenu by pressing the Enter key from the assortment of presets of the following Resolution and choose whether to turn on or turn off the following Finger Switch of the...

Page 20: ...mpressed and OFF Auto and 2 Channels under 3 2 5 sers can select the inputting programs to encode under this menu by pressing up down represents the program number and CCTV 1 represents the program Us...

Page 21: ...corresponding submenu users can select the source of signals check card information select programs to be descrambled and choose nder 4 2 BISS menu users can choose between Mode 1 and Mode E key to e...

Page 22: ...0 22 HW 1 0 H HD IRD 20 choosing the menu 7 2 Default Config s hardware version and software version at this submenu HD IRD has two language versions English and Chinese For convenient system setting...

Page 23: ...ically 192 168 1 136 however this may be modified during configuration prior to shipping The s management IP address can be easily set or identified from the front panel interface Please refer to the...

Reviews: