background image

Ver02

17.11.2014

1) Manual By-Pass

2) Parallel Port 

#

1 (disabled)

3) Parallel Port 

#

2 (disabled)

4) Intelligent Slot for Relay / SNMP card (cards are optional)
5)

EPO connector

6)

COM port (RS232)

7)

USB port

8)

Input/Output switches

9)

Terminal blocks (Input/Output/Batteries)

2.2

UPS operating principles

The system can work as a single unit or parallel one, so as to enhance its reliability 

1. AC input filter    for filtering input disturbances.
2. Rectifier. To convert AC input voltage into a DC voltage and to increase (boost) the DC

voltage at Inverter.

3. DC/DC Converter (booster): When UPs operates in battery mode, it increase the DC voltage

and supply the inverter.

4. Inverter: to convert the DC voltage into an AC filtered voltage at the output.
5. Bypass: When UPS face an overload or a failure on the inverter, the load is automatically

transferred to Bypass line without any interruption of power to the load.

6. Battery charger: The standard charger feeds the batteries with 1A current. For longer

autonomy times, an optional battery charger at 10A max. is available

7. Battery: VRLA Lead-acid, maintenance-free.
8. Output Filter: to filter the output voltage in order to feed the load with a clean voltage.
9. Maintenance bypass switch is provided so the supply to load will not be interrupted during

repair or maintenance.

Rectifier

Inverter

Switch

Charger

AC input

Input switch

Bypass

Maintenance  switch

AC Output

Battery

YOUR CONNECTION TO SAFETY

Thiele KG 

• V
orderer W

einberg 26 • D-71522 Backnang • T

el.: +49 (0)7191 3560-0 

• Fax.: +49 (0)7191 3560-19 

[email protected] 

• www

.thiele-kg.de

Thiele KG 

• V

orderer W

einberg 26 • D-71522 Backnang • T

el.: +49 (0)7191 3560-0 

• Fax.: +49 (0)7191 3560-19 

[email protected] 

• www

.thiele-kg.de

YOUR CONNECTION TO SAFETY

klick to

www

u-s-v

YOUR CONNECTION TO SAFETY

klick to

www

ACDC-DCDC

YOUR CONNECTION TO SAFETY

klick to

www

SYSTEME

YOUR CONNECTION TO SAFETY

klick to

www

CONTACT

YOUR CONNECTION TO SAFETY

klick to

www

CALLBACK

Summary of Contents for Tri-One 10000

Page 1: ...19 info thiele kg de www thiele kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de YOUR CONNECTION TO SAFETY klick to...

Page 2: ...Optional boards 25 9 Packaging contents 26 Warranty 27 Thank you for purchasing this UPS This series is an intelligent three phase in single phase out high frequency on line UPS With excellent electr...

Page 3: ...t for a long time o Area where the humidity and temperature is beyond the specified range temperature from 0 to 40 relative humidity 5 95 o Direct sunlight and location nearby heat o Area which can be...

Page 4: ...e of the safety symbol the detailed comments are shown as following Dangerous Indicate risk of serious injury or death or seriously damage of the equipment Warning Indicate risk of serious injury or d...

Page 5: ...0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de YO...

Page 6: ...interruption of power to the load 6 Battery charger The standard charger feeds the batteries with 1A current For longer autonomy times an optional battery charger at 10A max is available 7 Battery VRL...

Page 7: ...voltage frequency load temperature inside UPS etc o Perfect network power management can be achieved by using UPS monitoring software o Maintenance bypass switch is provided so the power supply to loa...

Page 8: ...r flammable gas corrosive gas dust direct sunlight and explosive things Don t lay the UPS outdoor PDU is required to connect to the UPS output so as to weaken the affection between loads In order to f...

Page 9: ...000 software 2 For remote monitoring of UPS an SNMP card optional must be installed A Remove the cover of SNMP slot at UPS rear panel and keep it for further use B Insert the SNMP card and tighten the...

Page 10: ...ar any watch rings or similar to avoid any accidental shortcircuit x Don t reverse nor shortcircuit the cables Red cable must be connected to positive pole and black cable must be connected to negativ...

Page 11: ...ank of which energy goes through inverter circuit The Inverter s and battery s indicators on LCD control panel will be on green and the alarm will beep every 2 seconds In battery mode if the battery v...

Page 12: ...4 3 1 LED and control panel display 1 ALARM LED red 2 BYPASS LED yellow 3 BATTERY LED yellow 4 INVERTER LED green 5 Display LCD 6 ENTER Scroll button 7 OFF button 8 ON button 4 3 2 LCD display NOTE T...

Page 13: ...rrent 07 Output YOUR CONNECTION TO SAFETY Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de Thiele KG Vorderer Weinberg 26 D...

Page 14: ...CONNECTION TO SAFETY Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel...

Page 15: ...is the flashing part After entering the setting menu it s mode setting defaulted and the mode setting line flashing as in above picture Use button Enter3 to choose different mode There are 3 differen...

Page 16: ...ashes as in above picture Use button Enter r to choose the different frequency There are 2 different frequency 50 60Hz Press or to exit the frequency setting save the frequency setting and goes to out...

Page 17: ...r limit setting press Off it goes to the battery quantity setting The battery quantity line flashes as in above picture x Use button Enter3 to choose the different battery quantity Battery quantity ra...

Page 18: ...r limit setting press On or when under parallel ID setting press Off it goes to the bypass lower limit setting The bypass lower limit line flashes as in above picture for negative positive does not ha...

Page 19: ...mode if the AC is failed The UPS will shut down automatically if batteries are drained When AC recovers the UPS will start the inverter automatically 4 5 3 Transfer to Bypass when overtemperature The...

Page 20: ...n start up OFF X X OFF 9 ECO Mode OFF X X X 10 EPO Mode ON OFF X OFF 11 Maintenance by pass Mode OFF OFF OFF OFF 12 Fault Mode ON X X X Nota X shows that it will determined by other conditions YOUR CO...

Page 21: ...ircuit 30 Rectifier over current 31 Bypass over current Bypass LED blinking 32 Overload Inverter or Bypass LED blinking 33 No battery Battery LED blinking 34 Battery under voltage 35 Battery low pre w...

Page 22: ...le Don t lay any tools or metallic goods on the battery x Never reverse or shortcircuit between battery anode and chatode 5 2 Fan maintenance Please check the fan periodically Regularly check that the...

Page 23: ...5Hz 50Hz 55 65Hz 60Hz Bypass voltage range 220Vac max default 25 10 15 20 optional 230Vac max default 20 10 15 optional 240Vac max default 15 10 optional min default 45 20 30 optional Bypass frequency...

Page 24: ...C 62040 2 EMS IEC 62040 2 MTBF 250 000 hours Isolation resistance 2M 500Vdc Isolation in voltage 2820Vdc 3 5mA 1min Surge Compliant IEC60664 1 1 2 50uS 8 20uS 6KV 3KA IP Protection IP20 6 3 Environmen...

Page 25: ...on speed 2400bps x Byte length 8bit x Stop bit 1bit x Parity control none 8 Optional boards NAME DESCRIPTION NOTE Parallel board Parallel cable For UPS parallel connection Not available on this model...

Page 26: ...7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de YOUR...

Page 27: ...costs of technical staff support and any transport from the customer s adress to Assistance Center and vice versa as well as all the risks involved x Damages due to a Improper use including but not l...

Reviews: