CAUTION:
The following procedure must be implemented if UPS is connected to a genset, which should have a power
twice the UPS minimum:
x
Start up the genset and when its voltage is stable connect the UPS to genset output. Then start up the UPS
and connect its load gradually.
5.
Maintenance
Once installed, the UPS requires few maintenance..
5.1
Battery Maintenance
There are sealed lead acid maintenance free batteries inside this series. Battery lifetime depends on
environment temperature and discharge/charge cycles, it will be shortened if temperature raised or deep
discharged. Periodical maintenance is required so as to keep battery in good condition.
1) The most proper working temperature is 15 to 25 Celsius degree.
2)
Avoid small discharging current. Don’t let UPS work in battery mode continuously for 24 hours.
3) Charge battery for at least 12 hours every 3 months if it is free of operation. If the environment
temperature is high, charge it once every 2 months..
4) In normal operating conditions, battery lifetime is about 2-3 years. If any problem occurs in autonomy
time or a battery alarm is detected on the display, then contact the technical assistance for
replacement.
5) In case of battery replacement (must be done by a technician), all battery blocks must be replaced.
WARNING:
x
Before replacing batteries, first turn off the UPS and the mains. Remove your metallic adornment such as
finger rings, watch and so on..
x
When replaces batteries, please use a screwdriver with insulating handle. Don
’
t lay any tools or metallic
goods on the battery.
x
Never reverse or shortcircuit between battery anode and chatode..
5.2
Fan maintenance
Please check the fan periodically. Regularly check that the ventilation grids on the UPS panels are not blocked
and, if necessary, remove dirt with a cloth or vacuum cleaner.
If you encounter foreign objects blocking the ventilation contact the technical assistance.
6.
Trouble shooting and UPS features
1.
If the UPS is not operating properly, it may be due to an installation problem, a wrong connection or to a
failure on the UPS itself. Please, check all these conditions before contacting the technical assistance.
Then provide the technical support of the following information in order to solve the problem:
z
UPS model, serial number and purchase date.
z
Detailed description of the problem, including the list of messages on LCD panel.
6.1
Troubleshooting
In case of failure, check the table below. If problem cannot be solved please contact your Distributor or
technical assistance.
FAILURE
PROBABLE CAUSE
SOLUTION
No display on the LCD, no self-
diagnostics
A Input power absent
B Low input
Use Multi-meter to measure the input to see if it
is normal or not.
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK