21 

FAULT DIAGNOSIS 

 

GAS OPERATION 

FAULT OBSERVED 

CAUSE 

SOLUTION 

Burner will not adjust 

(continuously on low or high 

flame setting) 

Gas pressure 

Blocked jet 

Control tap fault 

 

Check gas pressure correct 

Clear blockage from jet and check the 

jet size 

Inspect / test the control tap 

 

Burner causes soot deposits 

Gas pressure 

Check and adjust the gas pressure. 

Low pressure is usually the cause of 

soot deposits 

Burner flame lift 

Gas Pressure 

Check and adjust the gas pressure. 

High pressure may cause the flames to 

lift 

Burner – no Spark Ignition 

Power supply 

Poor connection 

Spark generator 

Check power supply 

Check all connections 

Test spark generator and check for 

earth leakage due to damaged wire 

Burner will not remain lit 

Thermocouple failure. 

Blocked jet 

Test & replace thermocouple if required 

Check thermocouple in flame path 

Clear jet blockage 

INDUCTION OPERATION 

FAULT OBSERVED 

CAUSE

 

SOLUTION

 

LED Display shows U 

No pan detected or 

pan not suitable for 

induction heating 

Use a suitable pan placed centrally 

over the induction heating zone. 

LED Display shows E or 

┌┘on 

start up

 

Internal fault detected.  Disconnect electric supply and refer to 

Thetford approved Service Agent.  

LED Display shows ‘H’ after 

use 

Residual heat 

detected, glass 

surface is still hot. 

This is normal, allow the appliance to 

cool after use. 

 

 

For assistance with service, please contact your authorised local Service Agent 

giving details of the model and serial number on the data badge as shown below, 

plus date of purchase. 

 

 

 

 

Summary of Contents for SHB981 Series

Page 1: ...l For use with mains electricity and Universal LPG INS1021Z 0 User and installation instructions Please read and keep for future reference For use in Australia THETFORD AUSTRALIA PTY LTD 41 LARA WAY C...

Page 2: ...y aerosols in the vicinity of this appliance whilst it is in operation This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack...

Page 3: ...ce is installed in marine craft or in caravans it shall not be used as a space heater This appliance is not intended to be operated by means of an external timer or separate remote control system Do n...

Page 4: ...the appliance may call for additional ventilation for example opening of a window or more effective ventilation for example increasing the level of mechanical ventilation where present The room conta...

Page 5: ...burner ignition is automatic whilst the knob is depressed 4 After the burner is lit continue depressing the knob for approximately 10 15 seconds 5 Release the knob and turn it to the required heat set...

Page 6: ...our Induction hob we recommend the use of pans which are specifically made for this type of appliance Choose pans which show a coil symbol and state Induction on the underside If however you wish to u...

Page 7: ...ting zone on the hob is controlled separately using the rotary control switch Fig 2 An LED indicator illuminates when the induction hob is activated and when the hob is hot during or after use Fig 2 I...

Page 8: ...used or there is no pan on the induction heating zone when the heater is activated the LED light displays U After 30 seconds in this condition if no suitable pan is placed on the induction zone the he...

Page 9: ...educes the power to the pre set level which is then displayed The Automatic Heat up function operates in accordance with the times shown in the table below Power Level Auto Heat up Time at 100 power i...

Page 10: ...cooking with an induction hob some noise may be emitted by the pan This is normal and depends on the type of construction of the pan which may affect the noise High power settings may produce the mos...

Page 11: ...re first use and regularly after use DO Remove spills as promptly as possible to prevent food residue burning on the hob surface Gas Leaks If a smell of gas becomes apparent the gas supply should be t...

Page 12: ...Input MJ hr kW 9 70 2 69 Induction Hob Power Consumption kW Max Amps 230 240V AC 50 Hz 1 4 6 Amps Spark Ignition 12 Volt DC Gas Universal LPG 2 75 kPa ELECTRICAL ENERGY CONSUMPTION MEASUREMENT AND CAL...

Page 13: ...13 INSTALLATION Fig 2a Worktop Cut Out Details SHB981XXZ Series The worktop cut out and fixing holes must be prepared to the dimensions shown below 4 X 10mm fixing holes required...

Page 14: ...eened and baffled to prevent direct draughts to the appliance see Fig 4 Air vents and gas dispersal holes must be kept clear The manufacturer cannot accept responsibility for failure in performance if...

Page 15: ...all cases the national standards with regard to ventilation for the particular vehicle into which the appliance is to be installed must be adhered to AS NZS 5601 2 LP Gas installations in caravans and...

Page 16: ...of 200mm must exist between the edge of the burners and combustible material unless protected by a layer of non combustible material A non combustible heat shield splash back should be fitted onto the...

Page 17: ...ure fitted around the unit MUST be performed The design is deemed permissible providing the results of this test comply with the allowable temperature rise specified above and with all standards in fo...

Page 18: ...utes continuous use and there is an LED indication of power on and residual heat Pan detection for induction heater after 30 seconds without a pan or with an unsuitable type of pan the heater switches...

Page 19: ...e the mains electricity supply and disconnect appliance from the supply 2 Turn off the gas and disconnect the appliance from the gas supply 3 Disconnect the appliance from the 12V DC electricity suppl...

Page 20: ...emoval Disconnect from gas and electrical supplies and remove the appliance from worktop as above Disconnect the 12v power wires from the spark generator Pull off the fixing clip on the burner and rem...

Page 21: ...and check for earth leakage due to damaged wire Burner will not remain lit Thermocouple failure Blocked jet Test replace thermocouple if required Check thermocouple in flame path Clear jet blockage I...

Page 22: ...22 Fig 6 Mains Wiring Diagram...