THERMOSTAHL PYROGAS 116 Instruction Manual Download Page 6

3.4. Dimensions 

 

 

3.5. Fuels 

PYROGAS  boiler  is  designed  to  burn  woods  and  briquettes.  You  should  be  very 
carefully with the woods that you use for the boiler. PYROGAS gasification boiler is 
designed  to  burn  wood  with  a  percentage  of  humidity  up  to  20%  and  briquettes, 
which are made of wood only, with humidity up to 10%. Woods with high amount of 
water create condensation in the boiler leading to corrosion. Be sure that the woods 
that you will use are dry and the amount of humidity is under the allowable limits. Use 
woods  from  oak,  beech  or  pine  and  do  not  mix  them  in  the  feeding  chamber.  Use 
only  one kind  of  wood  in every  feeding.  This  will  provide  a  constant  combustion of 
fuel.  

Fuel 

Heating 

Value 

Allowable 

diameter 

Max 

percentage 

of humidity  

Allowable 

ash 

percentage 

 

kWh/kg 

mm 

Woods 

 4,3 

80-150 

<20 

Wood briquettes 

5,2 

<10 

<4 

ATTENTION:

 Do not use inappropriate fuels. There is danger for the health and for 

the boiler. Do not as fuels woods that contain chemicals or explosive materials, MDF, 
household waste etc. Use only woods and wood briquette suitable for your boiler.    

During the manual feeding of the boiler, you should place the woods with the smaller 
diameter at the bottom and after the biggest woods. This will help start the boiler and 
offers a smooth operation of boiler.  

Type 

Α

 

Β

 

Φ1

 

Τ1

-

Τ2

 

T3- T4- 

T5 

Feeding 

Door 

Dimensions 

 

mm 

mm 

mm 

mm 

mm 

mm 

mm 

mm 

mm 

mm 

mm 

in 

in 

mm 

20 

670 

1290 

950 

 

620 

1460 

90 

1385 

690 

510 

460 

160 

1  ¼

 

½

 

350x466 

30 

670 

1290

 

1050 

620

 

1460

 

90

 

1385

 

690

 

610 

560 

160 

1  ¼

 

½

 

350x466

 

40 

670 

1290

 

1150 

620

 

1460

 

90

 

1385

 

690

 

710 

660 

160 

1  ¼

 

½

 

350x466

 

50 

670 

1290

 

1250 

620

 

1460

 

90

 

1385

 

690

 

810 

760 

180 

1  ½

 

½

 

350x466

 

65 

670 

1290

 

1350 

620

 

1460

 

90

 

1385

 

690

 

910 

860 

180 

½

 

350x466

 

80 

670 

1290

 

1450 

620

 

1460

 

90

 

1385

 

690

 

1010 

960 

200 

½

 

350x466

 

100 

670 

1290

 

1700 

620

 

1460

 

90

 

1385

 

690

 

1260 

1210 

220 

2  ½

 

½

 

350x466

 

Summary of Contents for PYROGAS 116

Page 1: ...Gasification boiler PYROGAS INSTRUCTION MANUAL ver 1 1...

Page 2: ...improper installation of the device and for failure to comply with the terms and conditions set forth in the Operation and Maintenance Documentation 2 SCOPE OF DELIVERY SHIPPING CONDITION PYROGAS boil...

Page 3: ...e paths into the smoke chamber and subsequently to the chimney An air fan is equipped at the front side of boiler and supplies with primary and secondary air the upper chamber and the area around the...

Page 4: ...ts the feeding chamber with the smoke chamber That helps the exhausts to leave from the feeding chamber to the chimney and not to the boiler room during the start of boiler and during the feeding proc...

Page 5: ...470 PYROGAS 47 40 47 3 172 3 62 436 176 570 PYROGAS 58 50 58 3 191 3 93 482 201 670 PYROGAS 69 60 76 3 210 4 24 527 226 770 PYROGAS 81 70 81 3 238 5 27 581 251 870 PYROGAS 93 80 93 3 257 5 58 656 276...

Page 6: ...d briquettes 5 2 10 4 ATTENTION Do not use inappropriate fuels There is danger for the health and for the boiler Do not as fuels woods that contain chemicals or explosive materials MDF household waste...

Page 7: ...f the boiler room should comply with the requirements relating to heat loads fire protection regulations and allow for them to be fitted out operated and maintained in compliance with the OHS regulati...

Page 8: ...ning outside under pressure with the clear width of min 0 9 m 4 3 Hydraulic system installation The system should be installed in accordance with the applicable regulations and best construction pract...

Page 9: ...y valve 19 20 21 22 23 24 Check valve Buffer tank VE Open type expansion tank PCI Circulator of heating system PRC Recirculation pump PB Circulator for buffer tank RP Pressure reducer F Y type straine...

Page 10: ...C Recirculation pump PB Buffer tank circulator RP Pressure reducer F Y type strainer A Automatic air vent FD Water filter 4 4 Installation safety 3 bar safety kit It consists of a collector manometer...

Page 11: ...wo ports which makes it easy to install and does not require any balancing valve in the bypass pipe The LTC100 has an integrated auto circulation function which makes the unit operational even during...

Page 12: ...with the drain for the disposal of the overheated water The T P valve should be connected nearby to the boiler and necessary at the outlet It provides safety in case of closed type expansion tank ins...

Page 13: ...of chimneys made of brick comply with the requirements of the PN89 B 10425 standard the technical parameters of the chimney should ensure its protection against the effects of the condensate resultin...

Page 14: ...mney the user should obtain a positive opinion of the chimney cleaners specialist A graph for selecting the chimney diameter in relation to the boiler power rating and the chimney height including the...

Page 15: ...ate 04 TEMP Bypass Water temperature that the bypass valve starts to operate 05 FAN AIR MAX Maximum power amount of the fan in the full burning process 06 DT WATER Temperature difference below the max...

Page 16: ...on process The water is evaporated during operation of the boiler But at the first operations the boiler should not be working at full load because the water content can be vaporized and create gaps i...

Page 17: ...condition and functioning properly The boiler should be cleaned daily by the combustion residues ash and unburned residues Clean both upper chamber and combustion chamber Clean walls and ceramic plate...

Page 18: ...the boiler despite intensive burning 1 Improper fuel too low calorific value or damp fuel 2 Incorrectly selected boiler in relation to the size of the building 3 No weak chimney draught 4 Incorrect a...

Page 19: ...of the boiler 2 Very low return temperature 3 Fuel with very high amount of moisture 4 Low chimney draft 5 Small section of chimney 6 Faulty connection to the chimney 7 Concentrates or rain entering...