WATER COOLED AIR CONDITIONERS 

 

HORIZONTAL & VERTICAL MODELS

 

R410A 

 

INSTALLATION, OPERATION AND MAINTENANCE

 

SERIES 

 KACE-009A 

KACE-012A 

KACE-015A 

KACE-018A

 

 

 

KACE-024A 

KACE-030A 

KACE-036A 

KACE-042A 

KACE-048A 

KACE-060A 

KACE-072A 

KACE-096A 

KACE-120A 

KACE-144A

 

 

 

 

 
 

Warning 

Mechanical Thermostat may affect Electronic 
Control card in unit. Connect an electronic 
Thermostat to unit.

 

Each air conditioner has been operated and checked out 
prior to shipment. Failure to operate after installation 
indicates damage in transit or improper installation. 
 

INSPECTION

 

Check packaging during unloading. Note transit damage on 
all copies of bill of lading. Inspect air conditioners for hidden 
shipping damage after packaging is removed. Transit 
damage claims must be filed promptly with Freight 
Company by purchaser. 
 

HANDLING

 

Always handle 

Vertical units upright and Horizontal 

units flat on their base

. Moving a vertical unit on its side, 

placing a horizontal unit on end, or dropping it may damage 
internal parts and displace oil from the compressor's 
crankcase. 
 

STORAGE

 

If job site storage is necessary, place the unit in a clean, 
warm dry area. Follow instructions under Handling. 
 

LOCATION

 

Note that units with different capacities may have identical 
dimensions. Labels on unit packaging must be carefully 
scrutinized and matched to job location. These units are not 
approved for outdoor installation and therefore must be 
installed inside the space being conditioned. 
 

PLACEMENT

 

Install air conditioners in a level plane and locate unit 
around the service panel to ensure that proper access is 
available including that for filter removal. 

¨

 For Vertical Units: Install the air conditioner with a piece of 

sound insulating material between unit and floor to avoid 
possible transmission of noise into the building structure. 
(rubber backed carpeting will suffice for vertical models). 
For units installed in closets adjacent to conditioned space, 
provide insulated return air ducting with at least one 90

o

 

elbow or provide a sound baffle between the return air grille 
and unit filter.  

¨

 Horizontal units are provided with isolation hanger 

support. See Fig. 2 for proper installation when the unit is 
suspended. 
 

LOCATION OF SUPPLY & RETURN CONNECTIONS

 

(SEE FIG. 1 & 2) 

 

 

WIRING

 

All wiring should conform to the CEC and/or local code 
requirements. Power disconnect shall be field provided (by 
others). The wiring diagram is located on electrical box 
cover on vertical models and on the back of the service 
panel on horizontal models. Make certain the line voltage 
and the 24 volt control circuit are properly identified and 
wired in accordance with the unit wiring diagram. 

¨

 Water cooled air conditioners are classified as direct 

(permanently) connected devices by the CEC. Air 
conditioners must be properly grounded as per instructions 
on the unit wiring diagram. 
 

CONDENSATE DRAINAGE

 

Vertical Units

: Ensure that the plastic drain tube is 

connected to the bottom of the coil drain pan at one end 
and the other end of the condensate drain tube should 
extend through the left post on the front side of the unit, see 
Fig. 1. Connect the drain through a trap to the condensate 
drain system in conformance to local plumbing codes. 
Slope the drain line for proper gravity flow of condensate 
away from unit. The top of the trap and further connections 
must be below the unit drain connection level. 

Horizontal Units: 

The condensate drain tube should be 

connected to the side of the unit, see Fig. 2. Follow the 
above instructions (given for the vertical units) for proper 
condensate draining. 
 

WATER SUPPLY (UNIT CONNECTED ON OPEN WATER 
CIRCUIT)

 

The source of water for air conditioner operation is the 
responsibility of the owner and/or the installing contractor. 
The air conditioner 

must not function without water

, and 

predetermined rates of flow (l/s or USGPM) must be 
maintained for the unit to opera-te at rated capacity. Since 
the water function is to absorb heat from the refrigerant, the 
flow rate for each model varies with the entering water 
temperature (EWT). A pressure-operated water valve is 
installed for this reason inside the unit and SAE-13 calibra-

 

 

Summary of Contents for KACE Series

Page 1: ...ting with at least one 90o elbow or provide a sound baffle between the return air grille and unit filter Horizontal units are provided with isolation hanger support See Fig 2 for proper installation w...

Page 2: ...30 012 75 0 30 015 75 0 30 018 75 0 30 024 188 0 75 030 188 0 75 036 188 0 75 042 188 0 75 048 188 0 75 060 188 0 75 072 25 to 275 0 10 to 1 1 096 25 to 275 0 10 to 1 1 120 25 to 275 0 10 to 1 1 144 2...

Page 3: ...ONT BLOWER AND MOTOR ACCESS PANEL RETURN AIR SUPPLY AIR WATER IN WATER OUT CONDENSATE DRAIN TUBE LOW VOLTAGE IN POWER IN BLOWER ACCESS PANEL ELECTRICAL AND COMPRESSOR ACCESS PANEL ELECTRICAL ACCESS PA...

Page 4: ...N WATER OUT LOW VOLTAGE IN POWER IN ELECTRICAL ACCESS PANEL ELECTRICAL AND COMPRESSOR ACCESS PANEL WATER REGULATING VALVE ACCESS PANEL C Detail C 3 8 WASHER BY OTHERS 3 8 16 NUTS DOUBLE BY OTHERS 3 8...

Page 5: ...ts box Refer to the instruc tions included Separate the display into its three pieces Thread the end of the cable thorugh the hole in the sub base as shown Using care to maintain level screw the sub b...

Page 6: ...ration of the system Default screen present value set point is used to scroll downward through screens and to decrease settings Do not press and at the same time is used to scroll upward through scree...

Page 7: ...setting aa I O Board address bb Default Screen HUMIDITY aaa bbb ROOM AIR ccc ddd F xxxxxxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxxx Prg Esc 2 Simultaneously press and hold the and buttons for at least fiv...

Page 8: ...Read Sensors or Operation Read Sensors This screen is the gateway to other screens used for setting the operating set points of the unit The set points are protected by a user password See Startup Adj...

Page 9: ...should disconnect electric power and interchange any two of the branch circuit wires at the unit input lugs Torque the connectors as discussed earlier Do not move any factory installed wires 4 When ai...

Reviews: