DESCRIPTION
FUN
MIN
MAX
UNIT
DEF.
FUNCTION
Timer trigger mode
Defines the timer triggering mode:
[MAN]
= Manual, through the
$
key.
[INI]
= Start up, when the controller is
powered up
[TMP]
=Temperature, when the oven working
temperature is reached.
NOTE:
In modes
[INI]
and
[TMP]
the
$
key only cancels the timer.
[F12]
MAN
TMP
-
MAN
Timer counting direction
Defines the direction the timer counts:
[DEC]
= time count down;
[CRE]
= time count up;
[F13]
DEC
CRE
-
DEC
Time base of the timer
Defines the time base of the timer:
[MM:SS]
= minutes, maximum time 99:59
minutes;
[HH:MM]
= hours, maximum time 99:59 hours;
[F14]
MM:SS HH:MM
-
MM:SS
Timer reset mode
Defines the timer reset mode, essentially
whether the audible alarm will be switched off
manually or by time:
[MAN]
=Manually through the
$
key;
[AUT]
=Automatically according to the time
defined in parameter F17;
NOTE:
The timer also resets when the door of
the oven is opened, independently of the mode
defined in this parameter.
[F15]
MAN
AUT
-
MAN
Timer reset time base
Defines the time base when the timer is reset:
[MM:SS]
=minutes, maximum time 99:59
minutes;
[HH:MM]
=hours, maximum time 99:59 hours;
[F16]
-
Time to reset the timer
(aut mode)
Defines the time to reset the timer if automatic
reset is selected in parameter F15.
[F17]
0:01
99:59
F16
0:05
Steam working mode
Defines the steam operating mode for the
selected preset
[rCnF]
:
[OFF,]
OFF: does not inject steam.
[MAN,]
Manual: injects steam when the
%
key is pressed.
[AUT,]
Automatic: automatically injects
steam after the timer is activated. The steam is
activated after the time set in F19 has elapsed.
[CYC,]
Cyclic: injects steam in cycles using
the times configured in
[UAon]
and
[Uaof]
.
[F18]
OFF
CYC
-
MAN
Delay to activate the
automatic steam
Defines the delay before injecting steam in the
oven after the timer is activated. This
parameter is valid when automatic steam is
adjusted in parameter F18.
[f19]
1
180
seg.
5
Time interval between steam
activations
Defines the minimum time interval between
steam activations, i.e. once the steam output is
activated, the controller will not activate it again
before the time adjusted in this parameter has
elapsed. To disable this function, displace the
adjustment to the minimum until
[no,]
is
displayed.
NOTE:
This parameter is disregarded when
the type of steam selected is cyclic.
[f20]
no(0)
30
mín.
no(0)
Minimum temperature to
activate the steam
Defines the minimum temperature in the oven
to allow activating the steam output. To disable
this function, displace the adjustment to the
minimum until
[no,]
is displayed.
[f21]
no(-10)
no(14)
500
(932)
ºC
(ºF)
no(-10)
no(14)
Lapm time on
[f22]
no(0)
180
seg.
15
Time for functions lock
Defines the time to lock / unlock the functions.
For more information see item 7.3 - Functions
Lock.
[f24]
1
30
seg.
10
Functions lock
Defines the functions lock mode:
[OFF,]
= functions lock disabled;
[LOC1]
= partial functions lock 1 - prevents
advanced configuration parameters from being
changed;
[FULL]
= full functions lock, does not allow
any parameter adjustment;
[f23]
-
MM:SS HH:MM
-
MM:SS
OFF
FULL
-
LOC1
Determines the time for automatic lamp
shutdown after the key is pressed.
NOTE:
If set to
[no,]
the lamp is switched on
/ off with each press of the button.
@
DESCRIÇÃO
FUN
MÍN
MÁX UNID. PADR.
FUNÇÃO
Minimum value allowed to
configure the oven
temperature setpoint
These parameters serve as the lower and
upper threshold for the adjustment of
parameter “SP”- oven temperature setpoint.
They are used to block temperature
adjustment and avoid an improper
configuration for the operation of the oven.
[F02]
-10
(14)
F03
°C
(°F)
0
(32)
Maximum value allowed to
configure the oven
temperature setpoint
[F03]
F02
500
(932)
°C
(°F)
230
(446)
Oven temperature differential
(Hysteresis)
The temperature difference to switch on the
heating output. This function allows defining a
temperature interval within which the heating
output will remain on.
[F04]
1
(1)
20
(36)
ºC
(ºF)
3
(5)
Delay to switch off the
temperature control when the
door of the oven is opened
Defines the delay to switch off the temperature
control when the oven door is opened to allow
furnishing the oven without switching off the
control. To disable this function, displace the
adjustment to the minimum until
[no,]
, is
displayed. In this case, the temperature control
is switched off as soon as the door is opened.
[F05]
no(0)
180
seg.
90
Number of attempts to ignite
the flame
(GAS-FIRED OVEN)
Defines the maximum number of attempts the
controller will try to ignite the flame. After using
up all attempts, the controller will signal error
[Er5]
-Out of Gas.
NOTE:
This parameter is used when the type
of oven selected is GAS.
[f06]
1
5
-
3
Delay to activate the ignition
output after controller start up
(GAS-FIRED OVEN)
Defines the delay to activate the ignition output
after the gas output is activated in the first
attempt to ignite the flame. This time is used so
that the gas from the cylinder reaches the
burner and then the ignition is activated.
NOTE:
This parameter is used when the type
of oven selected is GAS.
[F09]
no
(0)
15
seg.
2
Delay of the temperature
control after controller start
up
(GAS-FIRED OVEN)
When the controller is powered up, the fan is
activated first and then the flame ignition
process commences after the time adjusted in
this parameter has elapsed.
NOTE:
This parameter is used when the type
of oven selected is GAS.
[F10]
no
(0)
30
seg.
15
Delay of the temperature
control
(GAS-FIRED OVEN)
When the controller tries to ignite the flame, for
example after the door is opened, the fan is
activated first and then the flame ignition
process commences after the time adjusted in
this parameter has elapsed.
NOTE:
This parameter is used when the type
of oven selected is GAS.
[F11]
no
(0)
30
seg.
5
Interval between ignition
output activation
(GAS-FIRED OVEN)
Defines the interval between attempts to
activate the flame.
NOTE:
This parameter is used when the type
of oven selected is GAS.
[f08]
1
15
seg.
5
Ignition output on time
(GAS-FIRED OVEN)
Defines the time the ignition output will stay
switched on to try igniting the flame.
NOTE:
This parameter is used when the type
of oven selected is GAS.
[f07]
1
15
seg.
3
Reason:
Temperature sensor disconnected or out of range.
Providence:
Check sensor connections and operation.
Reason:
Flame sensor shorted with the burner.
Providence:
Check whether the flame sensor is making contact with the burner.
Reason:
Out of gas, the controller does not detect a flame.
Providence:
First check if there is gas available for the oven to operate. Check the presence of flame and
the distance between the flame sensor and the burner. Other possibilities for this failure are: flame sensor
disconnected or dirty / oxidized, damaged ignition module or gas valve.
9.4 Other signaling
Indicates that the oven door is open.
Note:
The message keeps cycling on the lower display.
Requests the operator to close the door. Indicates that the door was kept
open for the time adjusted in parameter F05. In this mode the controller
switches off the heating and activates the audible alarm.
Note:
The message keeps cycling on the lower display.
9.1 Operating mode signaling
Upon power up the controller indicates the operating mode of the oven.
Electric Oven
Controller configured with the electric oven logic.
Gas-fired Oven
Controller configured with the gas-fired oven logic.
Wood-fired oven
Controller configured with the wood-fired oven logic.
9. SIGNALING
Parameter adjustment denied
Enter access code in parameter
[Cod]
, to adjust the parameter value.
Functions lock active
Does not allow adjusting the parameter.
To deactivate functions lock see item 7.4 - Functions lock.
9.2 Programming signaling
Receiving data by EasyProg* (programming key)
Updating the parameter table via EasyProg*.
*sold separately
flame sensor monitoring. For more information see item 7.4 Enable Default (standard) operating
mode;
Controller configured with gas-fired oven logic with Default (standard) mode enabled, without
Default Mode (standard)
9.3 Process signaling
If the controller detects an error that interferes in the operation of the system, the controller switches off the outputs,
switches on the audible alarm intermittently, and indicates the detected failure on the display. To leave error mode, the
controller must be switched off, the fault corrected, and the controller switched on again.
Providence:
Reconfigure the function values.
Providence:
Contact Full Gauge Controls.
@