background image

Cut and remove overjacket.

 7.

Trim away exposed braid from cable.

 8.

Cut and remove primary insulation jacket.

 9.

Installation Instructions

5

6

 10.

 11.

 12.

Cut and remove fiberglass braid.  Omit this step for FP
cable.

Cut and remove heating element and fiberglass overlay
(FP cable only).  Push any remaining heating element
wire under the primary insulation jacket.

Cut and remove pairing jacket.  Do not cut bus wire
insulation.

Summary of Contents for Terminator ZE-S

Page 1: ...ermination Kit Installation Instructions Terminator ZE S For End Termination Applications 1 2 Cables Standard 3 Cables w Optional End Cap for use with HPT power limiting and FP constant watt heating c...

Page 2: ...t comply with Thermon requirements and be installed in accordance with the NEC CEC or any other applicable national and local codes 1 2 3 4 5 6 Kit Contents 1 2 Certifications Approvals 3 1 Banding 4...

Page 3: ...iple cable installation tips 1 Insert cable into expediter If mounted on bottom of pipe punch out weep hole 2 Slide expediter toward pipe and route cable through support base entry 3 Insert banding gu...

Page 4: ...9 Installation Instructions 5 6 10 11 12 Cut and remove fiberglass braid Omit this step for FP cable Cut and remove heating element and fiberglass overlay FP cable only Push any remaining heating elem...

Page 5: ...d termination kit Make sure latch mechanism is in the locked position 17 To remove cap lift latch mechanism and unscrew cap 18 13 14 15 Stagger cut one of the bus wires Tape bus wires individually and...

Page 6: ...loop A1 Insert two cables into expediter A2 Two Cable Layout Tips 9 B1 Insert three cables into expediter B2 Mount expediter with three cables Do not band over cable B3 Locate bus connection and cable...

Page 7: ...Thermon Manufacturing Company 100 Thermon Drive P O Box 609 San Marcos Texas 78667 0609 Phone 512 396 5801 Fax 512 396 3627 1 800 820 HEAT www thermon com Form No 50823 08 25 04...

Reviews: