background image

P a g e

 | 

18 

 

18-5-10 

TCH-150 & 460 

MAINTENANCE 

Apart from the normal levels of cleanliness, the chamber should be regularly maintained to ensure 
trouble free operation. A “periodic inspection and maintenance” programme can be arranged in 
some Australian locations, or a service manual can be purchased from Thermoline if you wish to 
do your own repairs. 
 
Lubrication of moving parts is not necessary since all bearings are sealed, but there are one or two 
essential maintenance chores that should be performed regularly: 
 
CLEANING: 
The internal and external surfaces of the cabinet can be cleaned with a soft damp cloth. Always 
have in place a program of regular cleaning using a soft 

damp

 cloth with a mild solution of soap 

and water and allow to dry. 

CARING FOR STAINLESS STEEL 

Stainless steel is under most conditions extremely resistant to corrosion. This is in part due to the 
addition of chromium and nickel to the steel and the formation of a durable chromium oxide at the 
surface during the manufacturing process. There are several chemicals which will attack the 
surface of stainless steel, plus the lack of oxygen at the surface will cause rusting, corrosion and 
pitting. 

Note: 

Deionised water is particularly corrosive, to minimise, maintain a Neutral pH (7-9).  

 

WATER TROUGH

The water trough inside the cabinet provides the humidity for the cabinet. Since water is constantly 
evaporating from this trough, mineral deposits can be left behind (especially if town water is used. 
Regular draining of the humidifier will help to keep these deposits to a minimum.  
To drain the humidity trough: 

  Turn the power off. 

  Turn the water supply off. 

  Open the drain valve and allow the trough to drain. (See photograph on page 3 for location 

of drain valve). 

  Remove the stainless deflector panel by simply lifting it to gain access to the trough. Use a 

soft damp cloth to clean the trough. 

  Close the drain valve and turn the water back on again. The trough will automatically fill 

with water again. 

  After flushing the trough it will take a while for the water to heat back up again and for the 

temperature and humidity to stabilise. 

You should perform this procedure every 3 months if town water is used, less often if distilled water 
is used. 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for TCH-150

Page 1: ...t Pty Ltd T A Thermoline Scientific ABN 80 000 859 129 10 12 Ross Place Wetherill Park N S W 2164 Australia P O Box 6862 Wetherill Park Delivery Centre N S W 1851 Australia Phone 02 9604 3911 Internat...

Page 2: ...pment be aware of the ALERT BOXES that appear throughout these operating instructions INDEX IMPORTANT INFORMATION Page 1 INDEX Page 1 2 PRODUCT WARRANTY Page 3 INTRODUCTION Page 4 THE MANUAL Page 4 UN...

Page 3: ...HANGING THE SET VALUE Pages 13 ADJUSTING THE VENTS Pages 14 15 SENSOR CORRECTION FOR CALIBRATION PURPOSES Page 16 MEASURING EQUIPMENT Page 16 ADJUSTING THE CALIBRATION OFFSET Page 17 MAINTENANCE CLEAN...

Page 4: ...stralia This warranty does not apply to refrigeration compressor s that are not protected by Thermoline Scientific factory installed VFP Voltage Fluctuation Protection unit 4 Limitation of Liability E...

Page 5: ...ese items could be included as part of the packing list if ordered Water supply bottle 25 litre bottle complete with hose connection fittings 1 x 4 pin plug for retransmission connection Circular char...

Page 6: ...d 10 amp power point WARNING Ensure that the electrical outlet is earthed is the correct voltage and capable of carrying the stated current Model TCH 150 is suitable for bench top or floor use whereas...

Page 7: ...HE CABINET DURING SERVICE ASSEMBLY INSTALLATION ASSEMBLY SHELVES Place the shelves at the required level The shelf runners are fixed at 100mm centres PERSPEX HOLDER This holder is provided so that the...

Page 8: ...er to gain access to the drain valve see photo 3 below The drain valve is shown in the closed position Note Prior to leaving the factory the water pressure regulator has been left fully open as it sho...

Page 9: ...of products within the range shown below in the control envelope NOTE Temperature and humidity inside the cabinet can only be controlled at temperatures above the ambient WARNING Do not use flammable...

Page 10: ...justable vents on top of the cabinet an air inlet and an air exhaust The operator can adjust these vents to increase or decrease the amount of ambient air that is mixed with the air inside the cabinet...

Page 11: ...P a g e 10 18 5 10 TCH 150 460 Figure 1 Section side view of cabinet showing air flow EXPLANATION OF CONTROLS Figure 2 Control Panel Layout...

Page 12: ...and quick recovery times Maximum recommended temperature is 80 C Humidity control This is a Eurotherm 3216 microprocessor based instrument with digital indication of set humidity and operating humidi...

Page 13: ...off the fan and heating elements when the door is open 4 Position the mains switch to the ON position reset and immediately both controllers will go through a short initiation period the two displays...

Page 14: ...e alarm will switch off all forms of heating if the actual temperature exceeds the set temperature by 2 0 C This will be indicated by a red flashing indicator and a scrolling message of Over Temperatu...

Page 15: ...gher humidity both vents will be closed for lower humidity the vents will be more open The ambient temperature and humidity will have a large bearing on the temperature and humidity attainable inside...

Page 16: ...P a g e 15 18 5 10 TCH 150 460...

Page 17: ...the operator access level so that it can be used to correct the displayed operating value If adjustments need to be made use the calibration procedure below MEASURING EQUIPMENT Ensure that the equipme...

Page 18: ...e should be carefully considered If in doubt return the value to zero and recalculate the offset value Press the scroll key again to return to the original screen The offset value will have changed to...

Page 19: ...rocess There are several chemicals which will attack the surface of stainless steel plus the lack of oxygen at the surface will cause rusting corrosion and pitting Note Deionised water is particularly...

Page 20: ...lly there is still enough pressure reduction through the valve even when fully open to reduce bounce When mains water is connected to the cabinet As described previously when town water is connected a...

Page 21: ...65 Fan motor Betts 50D503 86A 5 70 Centrifugal blower wheel 5 66 Cooling fan blade 4 30 MRA Bit 02 pressure regulator 4 32 Water solenoid valve L171B13 ZZ23A 1 8 TECHNICAL ASSISTANCE If you require ad...

Page 22: ...the cabinet for connection to an outside monitoring system which is able to accept the 4 20mA signals representing 0 0 to 100 0 C and 0 to 100 RH Maximum load to be applied to the analogue output is 5...

Reviews:

Related manuals for TCH-150