Thermolec DCC-12 Installation Manual Download Page 9

9

LIGHTS CODE

Green 

The charging station is energized.

Green 

The charging station is energized.  

The total load exceeds 80%. If the loads 
exceed 80% for a predetermined period, 
the charging station will be de-energized.

Yellow 

The charging station is not energized. 

The total loads exceed 80%. The resump-
tion time will start when the total load is 
lower than 80%.

Yellow 

The charging station is not energized. 

The total load is lower than 80% and the 
recovery time is in progress. Each flash 
mean two (2) minutes before the resump-
tion of power to the charging station. (ex: 
3 flashes = 6 minutes before power to the 
charging station). During that period, if 
the total load exceeds 80%, the recovery 
time will restart from the beginning.

Red 

Malfunction: 

1) Check all connections and voltage. 
2) Check the DIP switch configuration 
settings. 
3) Check if the current transformers (CT) 
are properly connected and interlocked. 
4) Check if the connection for the current 
transformers are properly connected to 
the PCB electronics. 
5) If the problem persists, send pictures 
of the installation at [email protected]  
and then call 1 (833) 717-1355.

OFF 

No power. Check the power source.

Charging station power supply

1. Put the circuit breaker in the ON position.
2. Check if the electric vehicle supply equipment (EVSE) is powered:

EVSE powered: go to the next step.
EVSE not energized: check the charging station connections.

STEP 7: SECURE AND RE-ENERGIZE

Secure

1. Turn off the power on the DCC.
2. Put the cover back.

Re-energize

1. Supply electrical power to the DCC.

STEP 8: IDENTIFICATION

1. Identify the branch circuit breaker.
2. Register all configuration settings of the charging station in the 

space provided on the cover.

APPLICATION

Electric vehicle recovery time

Following a power cut to the electric vehicle supply equipment (EVSE), 
a 15 minutes’ delay is initiated to monitor the total consumption of the 
electrical system. Power to the vehicle will then be restored if the total 
load consumption is lower than 80% of the main circuit breaker rating.   

Electric vehicle charging time 

It is recommended to schedule the charging vehicle program during 
hours of low electrical consumption to minimize interruptions to the 
electric charging station.

MAINTENANCE

Do not use any cleaning solvents to clean the DCC.

Summary of Contents for DCC-12

Page 1: ...NTATION PRINCIPALE 240 208V Monophas 60A 70A 80A 90A 100A 125A 150A 200A APPROVED MARKET North America MARCH AGR Am rique du Nord V1 Read and save these instructions Lire et garder ces instructions Ne...

Page 2: ...2...

Page 3: ...LECTRIQUE and its licensors This installa tion manual cannot be modified reproduced or copied without a prior written authorisation from THERMOLEC LTE E RECHARGE V HI CULE LECTRIQUE and its licensors...

Page 4: ...damages It is the installer s responsibility to make sure that the electric power source is adequate for the use of one or more DCC Charge controller for electric vehicles Do not use any cleaning solv...

Page 5: ...ler for electric vehicles will provide power to a charging station through a 30A 40A 50A or 60A 240 208V AC cir cuit breaker L1 L2 and ground The DCC 12 is NOT equipped with an internal breaker The br...

Page 6: ...nstallation may be done in any direction DCC INSTALLATION STEP 1 CHECK THE PACKAGE CONTENTS 1 x DCC 12 2 x Current transformer CT with 25 feet of wire 1 INSTALLATION MANUAL MANUEL D INSTALLATION MODEL...

Page 7: ...wiring supplied with the current transformers Additional wire must be 300V rated minimum 18 AWG 1mm 4 conductors shielded twisted ex FT4 SHIELD 4C FAS 18 or equivalent STEP 5 A DIP SWITCH PROGRAMMING...

Page 8: ...RELAIS DE PUISSANCE 12VA Yellow Jaune Orange Orange R1 L1 T1 L2 T2 G Red Rouge Red Rouge Black Noir Black Noir Black Noir White Blanc Black Noir White Blanc G R2 ELECTRIC VEHICLE CHARGER BORNE DE REC...

Page 9: ...res of the installation at support dccelectric com and then call 1 833 717 1355 OFF No power Check the power source Charging station power supply 1 Put the circuit breaker in the ON position 2 Check i...

Page 10: ...DES MATI RES propos de ce manuel 10 Information de s curit 10 Sp cifications 12 Caract ristiques 12 Exemple d installation 13 Installation du DCC 13 Utilisation 17 Maintenance 17 Code de lumi re 17 F...

Page 11: ...le DCC Contr leur de charge pour v hicules lectriques proxi mit de mat riaux inflammables explo sifs ou combustibles produits chimiques et des vapeurs Ne jamais asperger le DCC Contr leur de charge po...

Page 12: ...rcharge d une distribution lectrique en coupant momentan ment l alimentation de la borne de recharge lorsque la demande exc de 80 de la capacit du disjonc teur principale Disjoncteur Alimentation prin...

Page 13: ...6 m tres de fil inclus 1 INSTALLATION MANUAL MANUEL D INSTALLATION MODEL MOD LE DCC 12 Manufactured by Manufactur par MAIN POWER SUPPLY 240 208V Single Phase 60A 70A 80A 90A 100A 125A 150A 200A ALIMEN...

Page 14: ...tour du c ble d alimentation principale de l entr e lectrique 3 V rifier la polarit des CT 4 Raccorder les c bles des CT aux borniers l int rieur du DCC 12 pr vus cet effet TAPE 2 PR PARATION L INSTAL...

Page 15: ...RELAIS DE PUISSANCE 12VA Yellow Jaune Orange Orange R1 L1 T1 L2 T2 G Red Rouge Red Rouge Black Noir Black Noir Black Noir White Blanc Black Noir White Blanc G R2 ELECTRIC VEHICLE CHARGER BORNE DE REC...

Page 16: ...e contacteur est enclench 4 V rifier le t moin lumineux VERT en permanence l installation est conforme passer la prochaine tape ROUGE se r f rer la section Code de lumi re Alimentation de la borne de...

Page 17: ...ert La borne de recharge est aliment e en lectricit Vert La borne de recharge est aliment e en lectricit La charge totale exc de 80 Si la charge exc de 80 pendant la p riode pr d termin e l alimentati...

Reviews: